Permit Number: T00CM00658
Parcel: 11604087A

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/FLOOD/WWM

Permit Number - T00CM00658
Review Name: RESIDENTIAL BLDG/ZONING/FLOOD/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2000 DOUG WILLIAMS FLOODPLAIN REVIEW Approved This project requires a floodplain use permit.
08/15/2000 DAN CASTRO ZONING REVIEW Approved
10/13/2000 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T00CM00658
10/13/00

PLEASE ADDRESS THE FOLLOWING COMMENTS. RESUBMIT TWO SETS OF CORRECTED PLANS. SUBMIT A COPY OF THIS LETTER , NOTING THE DETAIL AND OR SHEET WHERE THE CORRECTION MAY BE FOUND.

GENERAL REQUIREMENTS

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

NOTE: REMOVE ALL DETAILS, ENGINEERING, AND CALLOUTS FOR RETAINING WALLS AND PATIO WALLS WHICH WILL REQUIRE SEPARATE PERMITS

FOUNDATION PLAN

1. LOCATE AND DETAIL ALL FOOTINGS FOR THE FOLLOWING:
INTERIOR SHEAR WALLS
INTERIOR HOLD DOWNS

2. SHOW LOCATION OF UNDERGROUND RETURN AIR DUCTWORK ON THE FOUNDATION PLAN.----------AS WELL AS DETAILS FOR PENETRATIONS

3. CONNECTION MISSING FOR POST TENSION SLAB TO RETAINING WALL AT DETAIL 4-SD2

STRUCTURAL

1. PROVIDE DETAIL OF CONNECTION FOR SHEAR TRANSFER TO ROOF DIAPHRAM AT SHEAR WALL TO I-JOIST

2. SPECIFY MAKE AND MODEL NUMBER OF ALL CONNECTORS AND HANGERS.-----ITT14, U26, PA18, ETC.

SECTIONS - DETAILS - MISCELLANEOUS NOTES

1. ON STANDARD DETAIL SHEETS, CROSS-OUT ALL DETAILS THAT DO NOT APPLY OR ARE NOT USED.----------RETAINING WALLS AND PATIO WALLS

PLUMBING PLAN

1. GAS: PROVIDE THE LENGTH OF LINE TO EACH APPLIANCE

2. WATER LINES: PROVIDE TOTAL FIXTURE DEMAND AND MAXIMUM DEVELOPED LENGTH (UBC SEC. 610, TABLE 6-3 AND 6-4).

3. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS AND SHOWERHEADS 3 GALLONS PER MINUTE. UPC CH.15 W/LOCAL MODIFICATIONS.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS: @ 791-5550 EXT. 112
10/17/2000 CBUFORD WWM REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
10/20/2000 CLAUDIA BUFORD APPROVAL SHELF Passed
10/20/2000 CLAUDIA BUFORD OUT TO CUSTOMER Passed
10/20/2000 CLAUDIA BUFORD REJECT SHELF Passed