Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T00BU02444
Parcel: 137270060

Review Status: Completed

Review Details: GRADING

Permit Number - T00BU02444
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2001 JIM JOHNSEN ENGINEERING REVIEW Denied 1. The floodplain use permit referenced on sheet GR-2, permit no. 1075A, was issued for phase 1 of Czarina Heights, and does not address the lots on this phase. A separate floodplain use permit must be obtained prior to grading plan approval.
2. The two 7-foot drainage outlets from the turnaround at Bronte Place, sheet GR-4, should be protected with grouted rip-rap to the top of the channel bank similar to the two cul-de-sac drainage outlets.
3. Section A-A on sheet GR-6 shows the key-in along the south bank of the channel as being constructed outside of this subdivision on the adjacent property to the south. Consultant should provide notarized written permission from the adjacent property owner for construction of improvements on that property. Alternatively, the channel cross section should be corrected to show all improvements within the subdivision boundary per U.B.C. Chapter 33 requirements.
4. All redlines should be returned with the next plan submittal.
02/27/2001 DWILLIAM NPDES REVIEW Denied
02/27/2001 JOE LINVILLE NPPO REVIEW Denied
02/27/2001 JIM JOHNSEN FLOODPLAIN REVIEW Denied See Engineering comments.
03/05/2001 PETER MCLAUGHLIN ZONING REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
03/09/2001 DELMA ROBEY OUT TO CUSTOMER Completed