Plan Review Detail
Review Status: Completed
Review Details: LOT SPLIT REVIEW
Plan Number - S22-035
Review Name: LOT SPLIT REVIEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/07/2022 | SBEASLE1 | START | PLANS BEING WALKED THRU | Completed | |
06/08/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Passed | |
06/08/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that Lot A has a minimum width of 15-feet of frontage on a water main. This is a requirement for having a water meter. An easement is not considered to be frontage. Reference: Tucson Water Remote Meter Policy, Number IV-B.08, dated 07/14/2009. |
06/08/2022 | SBEASLE1 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Approved | Email from: Ray Munoz To: CDRC Wed 6/8/2022 3:31 PM Tucson Water approves this lot split. Thank you, Ray Munoz Tucson Water City of Tucson |
06/13/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | FROM: PDSD Zoning Review PROJECT: 2520 M Park Ave – R-3 S22-035 Land Split (1st Review) TRANSMITTAL DATE: June 13, 2022 SECTION 2-08.0.0: LAND SPLIT 2-08.2.0 CONTENT REQUIREMENTS 1. COMMENT: 2-08.5.C – As Park Ave is designated as a Collector on the COT MS&R Map provide dimensions from centerline of Park to the curb and from the curb to the property line. Also clearly demonstrate that a vehicle will be able to turn around of site with out backing out onto Park Ave when leave the site. 2. COMMENT: 2-08.5.G – Provide a lot coverage calculation that meets the requirements found at UDC Article 6.4.3. and the example shown on the Residential Plot Plan Requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf , for Lot B, on the plan. If you have any questions about this transmittal, please contact Nicholas Ross at Nicholas.Ross@tucsonaz.gov. |
07/28/2022 | SBEASLE1 | ZONING-RECORDATION | REVIEW | Reqs Change | Email from: COTDSDPermits To: Cyrus Moore Thu 7/28/2022 5:12 PM LAND SPLIT REVIEW NOTICE Returned for Corrections: S22-035 Land Split/Reconfiguration from an existing combined lot. Lots A and B. 2520 N PARK AV Fee Balance: $0 (zero) Thank you for the payment. YOUR NEXT STEPS 1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab - Reviews section - click on REVIEW DETAILS - Documents section - click on VIEW 2. Title your SECOND submittal documents accordingly, example: 2_Comment Response Letter 3. UPLOAD A RESUBMITTAL to Filedrop: - Comment Response Letter (your response to REQUIRES CHANGE comments) - Legal Descriptions - Survey - Any other documents requested by review staff FILEDROP https://docs.tucsonaz.gov/Forms/tucsonpermitapp - "Existing Application" Sharon Beasley, Certified Permit Technician City of Tucson, Planning & Development Services Dept. Email: COTDSDpermits@TucsonAz.gov (for development packages, land splits, Thursday Presubmittal meetings) Email: PDSDinquiries@TucsonAz.gov (for building permits) |
07/28/2022 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | 1. Provide dimensions as to show there is enough room for a vehicle to turn around on site without backing out onto N Park Av when the gate is closed. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |