Plan Number: S21-073
Parcel: Unknown

Review Status: Completed

Review Details: LOT SPLIT REVIEW

Plan Number - S21-073
Review Name: LOT SPLIT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2021 SBEASLE1 START PLANS BEING WALKED THRU Completed
10/05/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Exterior walls with a fire separation distance less than 3-foot to the neighboring property line require not less than one-hour fire-resistive construction. Show compliance with R302.1 (City of Tucson Amended) by providing a section detail of materials prescribed in IBC Table 721.1(2), Items 15-1.1 to 16-1.3.

Roof projections extending into the 3-foot fire separation distance require not less than one-hour fire-resistive construction on the underside, R302.1 (City of Tucson Amended). The fire protected overhang may not extend closer than 24" from the property line.
10/05/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: 914 S Magnolia Ave – R-1
S21-073
Land Split (1st Review)

TRANSMITTAL DATE: October 5, 2021

SECTION 2-08.0.0: LAND SPLIT

2-08.5.0 CONTENT REQUIREMENTS
This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (UDC Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9. This plan was reviewed for compliance with development standards within the Unified Development Code (UDC)
1. COMMENT: 2-08.5.A – The west property line distance & bearings on the record of survey do not match what is listed in the legal and on the exhibit for Parcel 1 & 2.

2. COMMENT: 2-08.5.G – Provide a lot coverage calculation for proposed parcel 1 and the existing residence. The lot coverage calculation shall meet the requirements of UDC Article 6.4.3 and the example shown on the Residential Plot Plan requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf.

3. Per UDC TABLE 6.3-2.A: DIMENSIONAL STANDARDS FOR THE R-1, R-2, R-3, MH-1, & MH-2 ZONES, R-1 ZONE, RESIDENTIAL USE TO RESIDENTIAL ZONE the required perimeter yard setback from the existing residence to the north property line of Parcel 1 is 6’-0’ or 2/3 the height of the exterior wall, greater of the two. Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. Provide a wall height dimension from design grade the where the wall meets the eave at the highest point. As the proposed setback, 1.60’ does not meet the minimum 6’-0”. A Design Development Option (DDO) must be submitted and approved to reduce the required setback prior to approval of the land split,
DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.

4. Per UDC Article 6.6.2.B An accessory building shall be built only on a lot occupied by a principal building or use. That said the land split cannot be approved with the existing detached garage and mobile storage units on Parcel 2 as shown.
5. As the existing wall crosses property lines some type of cross access or use agreements will need to be recorded to all this wall to remain in place.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
10/05/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/22/2021 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved Email from: Jeremiah.Jenkins@TucsonAz.gov
To: CDRC
Fri 10/22/2021 2:25 PM

Tucson Water approves of the split.
Thank you,

Jeremiah Jenkins
Water Services Supervisor
City of Tucson Water Department,
New Services
201 N Stone Ave, First Floor
Public Counter hours: Mon-Thur 8am to 4pm
Department Hours: Mon-Fri 8am to 4pm
Office: 520-791-5164
10/22/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change See zoning comments.
10/22/2021 SBEASLE1 ZONING-RECORDATION REVIEW Reqs Change Email from: COTDSDPermits
To: Earl Y.
Fri 10/22/2021 3:29 PM

LAND SPLIT PLAN
Returned for Corrections: S21-073
Description: Land Split - Frohberg. Divide one parcel into two parcels. 914 S MAGNOLIA AV

FEES DUE: $99.00
ONLINE PAYMENTS
https://www.tucsonaz.gov/pdsd/fees
If amount doesn't match "Fees Due", check back in a few hours after it is updated.
1- Click on: Pay Planning & Permit Fees
2- Enter your Permit Nbr, example: dp20-0000
(not case-sensitive but a hyphen-dash- is needed)
3- Business/Individual Name: Leave blank
4- Click "Continue"
5-Under the Pay column, check the boxes you want to pay
6- Click "Continue", then enter your credit card info

View the review comments and documents on PRO:
www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab and you will see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

YOUR NEXT STEPS
Submit the following items to the FILEDROP
1) Comment Response Letter (your response to the reviewer's Requires Change comments)
2) Survey or Exhibit (even if no changes were made)
3) Legal Descriptions
4) Any other items requested by reviewers

FILEDROP
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
Select "Existing Application", then in the "Permit Number" field, enter your number and any notes you want directed to the City staff

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson, Planning & Development Services Dept.
Email: COTDSDpermits@TucsonAz.gov
(disregard the email response that will be sent automatically)