Plan Review Detail
Review Status: Completed
Review Details: MINOR SUBDIVISION REVIEW
Plan Number - S21-066
Review Name: MINOR SUBDIVISION REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/02/2022 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | 1. Provide the correct basis of bearing in the general notes, or remove the b-o-b note from the general notes. 2. Provide the correct name for the City Clerk. Mr. Randolph has retired. The new City Clerk is Suzanne Mesech. Loren Makus loren.makus@tucsonaz.gov |
| 02/07/2022 | SBEASLE1 | ZONING-DECISION LETTER | REVIEW | Reqs Change | Email from: COTDSDPermits To: Grace Construction - Jeff Mon 2/7/2022 10:21 AM REVIEW NOTICE Returned for Corrections: S21-066 DESCRIPTION: Minor Subdivision - San Jose. Lots 1,2,3. 1691 S SAN JOSE DR FEE BALANCE: $ 1,116.50 Please pay at a minimum, the REVIEW category fees. A payment is required before your next submittal. ONLINE PAYMENT If amount doesn't match "Fees Due", check back in a few hours https://www.tucsonaz.gov/pdsd/fees 1- Click on: Pay Planning & Permit Fees 2- Enter Permit Nbr, example: dp20-0000 (not case-sensitive but a hyphen-dash- is needed) 3- Business/Individual Name: Leave this field blank 4- "Continue" 5- In the Pay column - check the boxes 6- "Continue" YOUR NEXT STEPS 1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro (If information is not available, check back later after data transfers to PRO.) - Home page, Activity Search, enter the Activity/Permit Number - Permits - click on blue tab to see different sections - Reviews section - click on REVIEW DETAILS - Documents section - click on VIEW 2. UPLOAD A RESUBMITTAL and include: 1) Comment Response Letter (your response to REQUIRES CHANGE comments) 2) Plan Set (all pages, full set, even if no changes were made) 3) Any other documents requested by review staff Please title your SECOND submittal documents according to this example: 2_Comment Response Letter FILEDROP for your Resubmittal https://docs.tucsonaz.gov/Forms/tucsonpermitapp - Select "Existing Application" - In the "Permit Number" field, enter the number and, if applicable, any notes for our staff - Select "PLANS" for documents for quicker downloading of your documents on our end Thank you. Sharon Beasley, Building Permit Specialist City of Tucson, Planning and Development Services Email: COTDSDpermits@TucsonAz.gov |
| 11/09/2021 | SBEASLE1 | UTILITIES | SOUTHWEST GAS | Passed | |
| 11/09/2021 | SBEASLE1 | START | PLANS SUBMITTED | Completed | |
| 11/09/2021 | SBEASLE1 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Reqs Change | To: Applicant From: Planning & Development Services Dept. Contact Tucson Water to request a Water Availability letter. Include the Letter in your next submittal. This is required before the last step of Mayor and Council's approval of the Minor Subdivision. |
| 11/09/2021 | SBEASLE1 | OTHER AGENCIES | U. S. POST OFFICE | Passed | |
| 11/09/2021 | SBEASLE1 | PIMA COUNTY | WASTEWATER | Reqs Change | To: Applicant From: Planning & Development Services Dept. Contact Pima County Wastewater at email: Sewer@Pima.gov or phone (520) 724-6500 to request their approval for wastewater. Submit the approval letter to the City of Tucson with your next submittal. |
| 11/09/2021 | SBEASLE1 | OTHER AGENCIES | PIMA ASSN OF GOVTS | Passed | |
| 11/17/2021 | SBEASLE1 | UTILITIES | TUCSON ELECTRIC POWER | Approved | Email from: TEP-DEVREV <TEPDEVREV@tep.com> To: CDRC Wed 11/17/2021 8:32 AM Tucson Electric Power Co. (TEP) has reviewed the plans submitted on November 8th , 2021, and has no objections at this time. Please call the New Construction Department at 520-918-8300 to apply for service. Submit a final set of approved plans including electrical load and offsite improvement plans to determine how TEP will serve this development. If easements are required, they will be obtained by separate instrument. Removal or relocation of existing TEP facilities will be at the Developer’s expense. Tucson Electric Power Co. Land Resources Department attn: Courtney Tejeda |
| 11/17/2021 | ED ABRIGO | PIMA COUNTY | ASSESSOR | Reqs Change | (This letter can be viewed in the "Documents" section of PRO: "Pima Co Assessors, review comments, first submittal, 11.16.21") FROM: Ada Janson, GIS Cartographer, Pima County Assessor’s Office DATE: November 16, 2021 RE: Assessor’s Review and Comments Regarding: S21-066 1ST SUBMITTAL SAN JOSE LOTS 1 - 3 ___X___ Plat does not meet Assessor’s Office requirements. COMMENTS: 1. THE TITLE BLOCK IN THE LOWER RIGHTHAND CORNER DOES NOT LIST A SUBDIVISION NAME, NUMBER OF LOTS OR UNITS OR BLOCKS OR ANY COMBINATION OF THESE. IF IT IS A RESUBDIVISION, IT MUST STATE THAT IT IS A RESUBDIVISION WITH THE PLAT NAME AND THE MAP AND PLAT. 2. THE LOCATION MAP MUST BE IN THE UPPER RIGHT HAND CORNER AND MUST HAVE THE SECTION, TOWNSHIP AND RANGE. THE PROJECT AREA SHOULD BE OUTLINED OR HAVE AN ARROW POINT TO IT. 3. GENERAL NOTES MUST HAVE THE TOTAL NUMBER OF LOTS (IT LISTS “2”, BUT 3 LOTS ILLISTRATED). 4. THERE MUST BE A SECTION TIE, WITH A BEARING AND DIMENSION FROM THE SECTION CORNER OR QUARTER CORNER TO THE POINT OF TIE ON THE SUBDIVISION. 5. ALL ADJACENT SUBDIVISIONS SHOULD BE NAMED, WITH MAP AND PLAT IN THE APPROPRIATE AREAS AROUND THE WHOLE SUBDIVISION. (MISSING WEST, EAST & SOUTH SIDES) 6. OWNERSHIP DOES NOT MATCH OUR RECORDS. OUR RECORDS INDICATE: SALAZAR INVESTMENTS PSP LLC, AS THE CURRENT OWNER. |
| 12/03/2021 | AWARNER1 | LANDSCAPE | REVIEW | Passed | |
| 12/06/2021 | ROBERT SHERRY | PLUMBING-RESIDENTIAL | REVIEW | Completed | |
| 12/06/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL FROM: PDSD Zoning Review PROJECT: 1691 S San Jose Dr – Lots 1-3 FINAL PLAT (1st Review) S21-066 TRANSMITTAL DATE: December 6, 2021 DUE DATE: December 8, 2021 2-07.1.0 APPLICABILITY Final plats, block plats, minor subdivisions, and condominium plats shall be prepared according to the requirements provided below. Hereafter referred to as “plat” or “plats.” A final plat serves as a survey document suitable for recordation of all or part of an approved tentative plat, if applicable. The final plat must conform to the approved tentative plat or site plan in lot configuration, design, and required conditions of development. The final plat, once approved, is recorded in the Pima County Recorder’s Office. The final plat is kept on file and becomes part of the permanent record for the subject site. 2-07.5.0 CONTENT REQUIREMENTS 2-07.5.1 General 1. Comment: 2-07.5.1.A - A project-location map must be drawn in the upper right corner of the first sheet of the plat at a scale of three inches equals one mile and include the following information: 2. Comment: 2-07.5.1.A.1. The project site approximately centered within a one square mile area; 3. Comment: 2-07.5.1.A.2. Label the section, township, and range; section corners; north arrow; and the scale; 4. Comment: 2-07.5.1.A.3. Subdivisions, arterial and collector streets, major watercourses, and railroads within the one-mile area; and, 5. Comment: 2-07.5.1.A.4. The city’s jurisdictional limits, if within the mapped area. 6. Comment: 2-07.5.1.E. Provide a title block in the lower right corner of each sheet with the following information: 7. Comment: 2-07.5.1.E.1- Subdivision name and the number of lots. 8. Comment: 2-07.5.1.E.3 - If the final plat is a resubdivision of a previously recorded plat, indicate the title and the book and page/sequence number reference of the existing subdivision; and 9. Comment: 2-07.5.1.E.4. State “FINAL PLAT” in the tittle and title block. 10. Comment: 2-07.5.1.H – Provide the subdivision case number, S21-066, in the lower right corner of the plat next to the title block on all sheets. The plat must include the following general notes. Additional notes specific to each project are required when pertinent. Fill in the blanks with the project-specific information. 11. Comment: 2-07.5.2.B – General Note 2 states “NUMBER OF LOTS IS 2” but you show 3. 2-07.5.3 Standard Paragraphs The plat must include the following statements, as applicable. All signatures must be in permanent, black, India ink and be accompanied by a notary signature and seal. 12. Comment: 2-07.5.3.D – Remove the Clerks name from the signature line of the approval block. 13. Comment: 2-07.5.3.D – The approval block shall match what is shown in AM 2-07. 2-07.5.4 Proposed Subdivision Information Provide the following information on the plat: 14. 2-07.5.4.E – Remove the perimeter yard setback lines and dimensions from the plat as they are not correct and are not required. If you have any questions about this transmittal, please contact Elisa Hamblin or Elisa.Hamblin@tucsonaz.gov. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Final Plat |
| 12/07/2021 | SBEASLE1 | COT NON-DSD | PARKS & RECREATION | Approved | Email from: Howard Dutt To: CDRC Tue 12/7/2021 1:50 PM No existing or proposed Tucson Parks and Recreation facilities are affected by this Minor Subdivision. Howard B. Dutt, RLA Landscape Architect Tucson Parks and Recreation (520) 631-2030 |
| 12/08/2021 | KAY MARKS | PIMA COUNTY | ADDRESSING | Reqs Change | (The ATTACHED PDF mentioned below can be viewed in the "Documents" section of PRO: "Pima Co Addressing, review comments, first submittal") Email from: <Addressing@pima.gov> To: CDRC Tue 12/7/2021 1:46 PM San Jose, S21-066, 1st submittal review is being Returned for Corrections by Pima County Addressing. The attached pdf contains Addressing’s comments. Please let me know if you have any questions or if I may assist further. Thank you, Robin Freiman, Addressing Official Pima County Development Services Department 201 N Stone AV – 1st Floor Tucson, AZ 85701 (520) 724-7570 |
| 12/08/2021 | JOSE ORTIZ | COT NON-DSD | TRAFFIC | Reqs Change | Email from: David.Stiffey@tucsonAz.gov To: CDRC Wed 12/8/2021 11:21 AM 1. Please provide information and details regarding new: a. Curb b. Sidewalk c. Curb Access Ramp Along San Jose Dr. 2. Show sidewalk along the frontage of San Luis Blvd. David Stiffey City of Tucson |
| 12/08/2021 | JIM EGAN | COT NON-DSD | FIRE | Approved |