The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Plan Number: S21-057
Parcel: Unknown

Review Status: Completed

Review Details: FINAL PLAT - REVIEW

Plan Number - S21-057
Review Name: FINAL PLAT - REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2021 SBEASLE1 START PLANS SUBMITTED Completed
08/23/2021 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Reqs Change To: Applicant
From: City of Tucson

Please contact Tucson Water to request a Water Availability letter. Include the Letter in your next submittal. Mayor and Council cannot grant final approval for this Final Plat until water is assured and available.
08/23/2021 SBEASLE1 UTILITIES SOUTHWEST GAS Passed
08/23/2021 SBEASLE1 PIMA COUNTY WASTEWATER Reqs Change To: Applicant
From: City of Tucson

Please contact Pima County Wastewater (email: Sewer@Pima.gov, phone 520-724-6500) and request approval. Include the Pima Co WW approval document in your next submittal. This will be required before the last step of Mayor and Council's final approval.
09/09/2021 STEVE SHIELDS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: Bella Tierra Phase 3 Lots 1-78
FINAL PLAT (1st Review)
S21-057

TRANSMITTAL DATE: September 9, 2021

DUE DATE: September 16, 2021

The Zoning Review Section conditionally approves the final plat for this project subject to the comment below. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised final plat to verify that those changes do not affect any zoning requirements.
2-07.5.0 CONTENT REQUIREMENTS
2-07.5.1.H – Provide the following case numbers, S20-057 & DP21-0060, in the lower right corner of the plat next to the title block on all sheets.
If you have any questions about this transmittal, please contact Elisa Hamblin or Elisa.Hamblin@tucsonaz.gov.
RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Final Plat
09/14/2021 SBEASLE1 PIMA COUNTY ADDRESSING Reqs Change (The entire email with the image can be viewed in the "Documents" section of PRO, titled "Pima Co Addressing, review comments, 09.13.21".)

Email from: <Addressing@pima.gov>
To: CDRC
Mon 9/13/2021 11:17 AM

Bella Tierra, S21-057, is Approved by Pima County Addressing conditional upon the correct project numbers being updated in the Title Block as follows:


Thank you,
Robin Freiman, Addressing Official

Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701
(520) 724-7570
09/20/2021 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved Email from: TEP-DEVREV <TEPDEVREV@tep.com>
To: CDRC
Sun 9/19/2021 10:48 AM

Tucson Electric Power Co. (TEP) has reviewed and has no objection to the Bella Tierra, S21-057, Blocks 1-2, submitted on August 23rd, 2021.

Please note TEP will not install facilities until the plat and any other land rights have not been recorded and contracts have been executed and received.

If removal or relocation of existing TEP facilities is required for this project, the developer will be responsible for any and all costs associated with such work.

Easements for TEP facilities, as identified on the Preliminary Drawing, must be shown on the final plat and provided to TEP for review prior to submittal for approval. Please note a Jurisdictional permit for any work done on Camino Seco Rd, Linderbrook Dr.,or Wingate. Should you have any easement questions, don't hesitate to get in touch with TEPDEVREV@TEP.COM

Diane Geerligs
Tucson Electric Power
09/29/2021 ED ABRIGO PIMA COUNTY ASSESSOR Approved (See full document in "Documents" section of PRO: "Pima Co Assessors approval letter, 09.27.21")

FROM: Julieann Arechederra, GIS Cartographer
Pima County Assessor’s Office
DATE: September 27, 2021

RE: Assessor’s Review and Comments Regarding:
BELLA TIERRA PHASE 3 S21-057

X Plat meets Assessor’s Office requirements.
10/12/2021 SBLOOD1 ENGINEERING REVIEW Approved
10/13/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email from: COTDSDPermits
To: C. Thompson
Wed 10/13/2021 2:49 PM

Returned for Corrections: S21-057
DESCRIPTION: Final Plat/FLD - Bella Tierra, 4855 S WINGATE BL

Fee Balance: $0 (zero) Thank you for the payment.

REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab and you will see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

INCLUDE IN RESUBMITTAL
1) Comment Response Letter (your response to any Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Please title your SECOND submittal documents according to this example: 2_Comment Response Letter

FILEDROP for Resubmittal
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- Select "Existing Application"
- In the "Permit Number" field, enter the number and, if applicable, any notes for our staff


Thank you.
Sharon Beasley, Permit Specialist

City of Tucson, Planning and Development Services
Email for Development Pkgs: COTDSDpermits@TucsonAz.gov
(disregard the email response that will be sent automatically)