Plan Number: S21-045
Parcel: Unknown

Address:
910 N RICHEY BL

Review Status: Completed

Review Details: MINOR SUBDIVISION REVIEW

Plan Number - S21-045
Review Name: MINOR SUBDIVISION REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2022 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Remove the unnecessary statements from the dedication section. For example, the second and third paragraphs don't apply to this subdivision.
2. Show distance and bearing for Richey Boulevard.
3. Show both monuments in 3rd Street that establish the basis of bearing.
4. Clearly label the section corner or quarter corner this project is tied to.

Loren Makus
loren.makus@tucsonaz.gov
01/17/2022 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email from: COTDSDPermits
To: Erin Harris
Mon 1/17/2022 12:01 PM

REVIEW NOTICE
Returned for Corrections: S21-045

DESCRIPTION: Minor Subdivision - 910 N. Richey Blvd, Lots A-1, A-2, and A-3.

Fee Balance: $0 (zero) Thank you for the payment.

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab to see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. UPLOAD A RESUBMITTAL and include:
1) Comment Response Letter (your response to REQUIRES CHANGE comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Please title your SECOND submittal documents according to this example: 2_Comment Response Letter

FILEDROP for your Resubmittal
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- Select "Existing Application"
- In the "Permit Number" field, enter the number and, if applicable, any notes for our staff


Thank you.
Sharon Beasley, Building Permit Specialist

City of Tucson, Planning and Development Services
Email: COTDSDpermits@TucsonAz.gov
11/01/2021 SBEASLE1 UTILITIES SOUTHWEST GAS Passed
11/01/2021 SBEASLE1 START PLANS SUBMITTED Completed
11/01/2021 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Reqs Change To: Applicant
From: Planning & Development Services Dept.

Please contact Tucson Water to request a Water Availability letter. Include the Letter in your next submittal. This is required before the last step of Mayor and Council's approval of the Minor Subdivision Final Plat.
11/01/2021 SBEASLE1 OTHER AGENCIES U. S. POST OFFICE Passed
11/01/2021 SBEASLE1 PIMA COUNTY WASTEWATER Reqs Change To: Applicant
From: Planning & Development Services Dept.

Contact Pima County Wastewater at email: Sewer@Pima.gov or phone (520) 724-6500 to request their approval for wastewater. Submit the approval letter to the City of Tucson with your next submittal.
11/01/2021 SBEASLE1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed
11/16/2021 AWARNER1 LANDSCAPE REVIEW Passed
11/16/2021 JIM EGAN COT NON-DSD FIRE Approved
11/18/2021 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: 910 N Richey Blvd
FINAL PLAT (1st Review)
S21-045

TRANSMITTAL DATE: November 18, 2021

DUE DATE: November 23, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

2-07.1.0 APPLICABILITY
Final plats, block plats, minor subdivisions, and condominium plats shall be prepared according to the requirements provided below. Hereafter referred to as “plat” or “plats.”
A final plat serves as a survey document suitable for recordation of all or part of an approved tentative plat, if applicable. The final plat must conform to the approved tentative plat or site plan in lot configuration, design, and required conditions of development. The final plat, once approved, is recorded in the Pima County Recorder’s Office. The final plat is kept on file and becomes part of the permanent record for the subject site.
2-07.4.0 FORMAT REQUIREMENTS
2-07.5.0 CONTENT REQUIREMENTS
1. COMMENT: 2-07.5.1.E.1 – Provide the number of proposed lots in the title block, i.e. “LOTS 1 & 2”.

2. COMMENT: 2-07.5.1.E.3 – Aa this plat is only a re-subdivision of a portion of Lot 12, Block 4 of Speedway View the title block should state this. Lot 12-A3 as shown on your plat was legally split off of Parcel 125-11-1400 under S17-024.

3. COMMENT: 2-07.5.1.H – Provide the subdivision case number, S21-045, in the lower right corner of the plat next to the title block on all sheets.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
11/19/2021 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved Email from: Howard Dutt
To: CDRC
Thu 11/18/2021 3:06 PM

No existing or proposed Tucson Parks and Recreation facilities are affected by this Minor Subdivision.

Howard B. Dutt, RLA
Landscape Architect
Tucson Parks and Recreation
(520) 631-2030
11/22/2021 ROBERT SHERRY PLUMBING-RESIDENTIAL REVIEW Completed
11/24/2021 SBEASLE1 UTILITIES TUCSON ELECTRIC POWER Approved Email from: TEP-DEVREV <TEPDEVREV@tep.com>
To: CDRC
Wed 11/24/2021 9:59 AM

Tucson Electric Power Co. (TEP) has reviewed the plans submitted on November 1st, 2021, and has no objections at this time.

If revisions are needed to the current design - additional easements are required for TEP facilities. They will need to be obtained by separate instrument.

Please call the New Construction Department at 520-918-8300 to apply for service. Submit a final set of approved plans including electrical load and offsite improvement plans to determine how TEP will serve this development. If easements are required, they will be obtained by separate instrument. Removal or relocation of existing TEP facilities will be at the Developer’s expense.

TEP
Attn: Courtney Tejeda
11/26/2021 KAY MARKS PIMA COUNTY ADDRESSING Reqs Change (The ATTACHED PDF mentioned below can be viewed in the "Documents" section of PRO: "Pima Co Addressing, review comments, first submittal, 11.22.21")

Email from: <Addressing@pima.gov>
To: CDRC
Mon 11/22/2021 9:22 AM

Minor Subdivision - 910 N. Richey Blvd., 1st submittal review, S21-045 is being Returned for Corrections by Pima County Addressing.
The attached pdf contains Addressing’s comments.
Please let me know if you have any questions or if I may assist you further.

Warm Regards,
Robin Freiman, Addressing Official

Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701
(520) 724-7570
12/02/2021 ED ABRIGO PIMA COUNTY ASSESSOR Reqs Change FROM: Julieann Arechederra, GIS Cartographer
Pima County Assessor's Office
DATE: December 2, 2021

RE: Assessor's Review and Comments Regarding:
910 N RICHEY BOULEVARD S21-045

___X___ Plat does not meet Assessor's Office requirements.

COMMENTS:

" THE TITLE BLOCK MUST BE IN THE LOWER RIGHT HAND CORNER. IT MUST HAVE THE NUMBER OF LOTS OR UNITS OR BLOCKS OR ANY COMBINATION OF THESE. IT MUST HAVE THE COMMON AREAS LISTED, IF THERE ARE ANY. IT MUST HAVE THE SECTION, TOWNSHIP AND RANGE AND IF IT IS A RESUBDIVISION, IT MUST MENTION THE PLAT NAME AND THE MAP AND PLAT.

" THERE MUST BE A SECTION TIE, WITH A BEARING AND DIMENSION FROM THE SECTION CORNER OR QUARTER CORNER TO THE POINT OF TIE ON THE SUBDIVISION.
12/03/2021 JOSE ORTIZ COT NON-DSD TRAFFIC Approved Email from: David Stiffey
To: CDRC
Fri 12/3/2021 7:33 AM

No Comments