Plan Number: S21-010
Parcel: Unknown

Address:
1995 E AJO WY

Review Status: Completed

Review Details: MINOR SUBDIVISION REVIEW

Plan Number - S21-010
Review Name: MINOR SUBDIVISION REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2021 SBEASLE1 START PLANS SUBMITTED Completed
02/15/2021 SBEASLE1 UTILITIES SOUTHWEST GAS Passed
02/15/2021 SBEASLE1 PIMA COUNTY WASTEWATER Reqs Change To Applicant: Please contact Pima County Wastewater at email: Sewer@Pima.gov or phone (520) 724-6500 to request their approval for wastewater. Submit their approval document to the City of Tucson with your next submittal.
02/15/2021 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Reqs Change To Applicant: Please contact Tucson Water (or Ray Water Company, if applicable). Request a Water Availability letter. Include the Letter in your next submittal for this permit. Mayor and Council cannot grant final approval until water is assured and available.
02/15/2021 SBEASLE1 OTHER AGENCIES U. S. POST OFFICE Passed
02/15/2021 SBEASLE1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed
02/23/2021 ED ABRIGO PIMA COUNTY ASSESSOR Reqs Change FROM: Julieann Arechederra
GIS Cartographer
Pima County Assessor's Office
DATE: February 23, 2021
RE: Assessor's Review and Comments Regarding:
SOUTH GATE BLOCKS C & D S21-010

___X___ Plat does not meet Assessor's Office requirements.

COMMENTS:

" THE TITLE BLOCK MUST BE IN THE LOWER RIGHT HAND CORNER. IT MUST HAVE THE NUMBER OF LOTS OR UNITS OR BLOCKS OR ANY COMBINATION OF THESE. IT MUST HAVE THE COMMON AREAS LISTED, IF THERE ARE ANY. IT MUST HAVE THE SECTION, TOWNSHIP AND RANGE AND IF IT IS A RESUBDIVISION, IT MUST MENTION THE PLAT NAME AND THE MAP AND PLAT.(ADD NUMBER OF BLOCKS IS 2 & RESUB PLAT INFO 64/091 M&P)

" THE LOCATION MAP MUST BE IN THE UPPER RIGHT HAND CORNER AND MUST HAVE THE SECTION, TOWNSHIP AND RANGE. THE PROJECT AREA SHOULD BE OUTLINED OR HAVE AN ARROW POINT TO IT. (SECTION 29, TOWNSHIP 14, RANGE 14 EAST.)
03/08/2021 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
03/11/2021 SBEASLE1 UTILITIES TUCSON ELECTRIC POWER Approved 3/11/21 Tucson Electric Power Co., (TEP) has reviewed and approves the Block Plat submitted on February 15, 2021.
Removal or relocation of existing TEP facilities will be at the expense of the developer. If additional TEP easements are required for future development, they will be obtained by separate instrument.

Please note that the title block is missing the Book and Page reference for the original subdivision, Bk 64 Pg 91.

If there are any questions, please contact me at 520-401-9895.

Thank you,
Mary Burke, Senior Right of Way Agent

Tucson Electric Power Co.
Land Resources – RC 131
Tucson, AZ 85714-2114
Cell - 520-401-9895
mburke@tep.com
03/11/2021 JIM EGAN COT NON-DSD FIRE Approved
03/12/2021 KAY MARKS PIMA COUNTY ADDRESSING Reqs Change (The ATTACHED PDF mentioned below can be viewed online: www.TucsonAz.gov/Pro. See the Documents section.)

03/12/21 S21-010, Final Block Plat, South Gate, 1st submittal, is being Returned for Corrections by Pima County Addressing. The attached pdf contains Addressing’s comments.
Please let me know if you have any questions.
Thank you,
Robin Freiman, Addressing Official

Pima County Development Services Department
Tucson, AZ 85701
(520) 724-7570
03/15/2021 STEVE SHIELDS ZONING REVIEW Approv-Cond FROM: Development Services Department Zoning Review

PROJECT: South Gate – Blocks C and D
FINAL PLAT (1st Review)
S21-010

TRANSMITTAL DATE: March 15, 2021

The Zoning Review Section conditionally approves the development package for this project subject to the requirements below. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised development package to verify that those changes do not affect any zoning requirements.
2-07.5.0 CONTENT REQUIREMENTS
1. COMMENT: 2-07.5.1.H – Provide the subdivision case number, S21-010, in the lower right corner of the plat next to the title block on all sheets.

2. COMMENT: 2-07.5.3.D – The Approval block shall match what is shown within the standard.
If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
03/16/2021 ANDREW CONNOR LANDSCAPE REVIEW Approved
03/16/2021 ROBERT SHERRY PLUMBING-RESIDENTIAL REVIEW Completed
03/19/2021 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved 03/19/21 No existing or proposed Tucson Parks and Recreation facilities are affected by this Block Plat.

Howard B. Dutt, RLA, Landscape Architect
Tucson Parks and Recreation
(520) 837-8040
04/01/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Provide name of the beneficiary of the trust owning the property.
2. This plat includes the resubdivision of common area of the condominium. Provide consent to subdivide from all parties with an interest in the common area.
Loren Makus, EIT
Loren.makus@tucsonaz.gov
04/05/2021 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change DATE: April 5, 2021
Returned for Corrections

PERMIT/ACTIVITY: S21-010
DESCRIPTION: Final Block Plat - South Gate, blocks C and D. 1995 E AJO WY

FEE BALANCE: $0 (zero) Thank you for the payment.

RESUBMITTAL
Submit the following documents to:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
(Select "Existing Application", then the permit number)
1) Comment Response Letter
your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Title the documents for your 2nd submittal starting with the
submittal number, for example: 2_Plan_Set

SEE REVIEW COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab
- Reviews - click on Review Details
- Documents - click on View to the right of each document

Thank you.

City of Tucson
Attn: Sharon Beasley, Permit Specialist
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov