Plan Number: S20-045
Parcel: Unknown

Address:
930 S 8TH AV

Review Status: Completed

Review Details: MINOR SUBDIVISION REVIEW

Plan Number - S20-045
Review Name: MINOR SUBDIVISION REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2022 SBEASLE1 START PLANS SUBMITTED Completed
01/12/2022 SBEASLE1 UTILITIES SOUTHWEST GAS Passed
01/12/2022 SBEASLE1 PIMA COUNTY WASTEWATER Reqs Change To: Applicant
From: Planning & Development Services Dept.

Contact Pima County Wastewater at email: Sewer@Pima.gov or phone (520) 724-6500 to request their approval for wastewater. Submit the approval letter to the City of Tucson with your next submittal.
01/12/2022 SBEASLE1 OTHER AGENCIES U. S. POST OFFICE Passed
01/12/2022 SBEASLE1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed
01/19/2022 ED ABRIGO PIMA COUNTY ASSESSOR Reqs Change See letter in the "Documents" section of PRO: "Pima Co Assessor review comments, first submittal".
01/26/2022 SBEASLE1 UTILITIES TUCSON ELECTRIC POWER Approved Email from: TEPDEVREV@tep.com
To: CDRC
Tue 1/25/2022 10:10 AM

Tucson Electric Power Co., (TEP) has reviewed and has no objection to Minor Subdivision - Barrio House. 930 South 8th Avenue, submitted on January 12th, 2022.

There are existing TEP facilities within the boundaries of the plat. Costs for removing or relocating existing TEP facilities will be billable to the developer.

Please call the New Construction Department at 520-918-8300 to apply for service for new development. Submit a final set of approved plans, including electrical load and offsite improvement plans to determine how TEP will serve this development. If easements are required for new TEP facilities, they will be obtained by separate instrument.

If there are any questions, please contact Land Resources at tepdevrev@tep.com.

Tucson Electric Power Co.
Land Resources Department
01/26/2022 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved Email from: Howard Dutt
To: CDRC
Wed 1/26/2022 2:18 PM

No existing or proposed Tucson Parks and Recreation facilities are affected by this Minor Subdivision.

Howard B. Dutt, RLA
Landscape Architect
Tucson Parks and Recreation
(520) 631-2030
01/26/2022 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: 930 S 8th Ave – Final Plat
FINAL PLAT (1st Review)
S20-045

TRANSMITTAL DATE: January 26, 2022

DUE DATE: February 1, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

2-07.1.0 APPLICABILITY
Final plats, block plats, minor subdivisions, and condominium plats shall be prepared according to the requirements provided below. Hereafter referred to as “plat” or “plats.”
A final plat serves as a survey document suitable for recordation of all or part of an approved tentative plat, if applicable. The final plat must conform to the approved tentative plat or site plan in lot configuration, design, and required conditions of development. The final plat, once approved, is recorded in the Pima County Recorder’s Office. The final plat is kept on file and becomes part of the permanent record for the subject site.
2-07.5.0 CONTENT REQUIREMENTS
2-07.5.1 General
1. COMMENT: 2-07.5.1.A - A project-location map must be drawn in the upper right corner of the first sheet of the plat at a scale of three inches equals one mile and include the following information:

2. COMMENT: 2-07.5.1.A.1 - The project site approximately centered within a one square mile area;

3. COMMENT: 2-07.5.1.A.2 - Label the section, township, and range; section corners; north arrow; and the scale;

4. COMMENT: 2-07.5.1.A.3 - Subdivisions, arterial and collector streets, major watercourses, and railroads within the one-mile area; and,

5. COMMENT: 2-07.5.1.E.1- Provide the number of lots within the title block.

6. COMMENT: 2-07.5.1.H - The subdivision case number, S20-045, assigned to this plat must be placed in the lower right corner of the plat next to the title block on all sheets.
2-07.5.2 General Notes
The plat must include the following general notes. Additional notes specific to each project are required when pertinent. Fill in the blanks with the project-specific information.
7. COMMENT: 2-07.5.2.G - As a Board of Adjustment variance was granted for this project, provide the following note: “This plat is subject to Board of Adjustment variance C10-21-14, unless expired or superseded by a subsequent application.”

2-07.5.3 Standard Paragraphs
The plat must include the following statements, as applicable. All signatures must be in permanent, black, India ink and be accompanied by a notary signature and seal.
8. COMMENT: 2-07.5.3.D. Change the year to 2022 within the Approval Block.

9. COMMENT: Provide a supplemental residential plot plan for Parcel A that demonstrates how requirements such as lot coverage, perimeter yard setbacks, etc are met for the existing house. Reference the requirements for a Residential Plot Plan found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf, This plot plan shall be a provided on a separate sheet from the final plat.

10. COMMENT: Per UDC Article 6.6.2.B An accessory building shall be built only on a lot occupied by a principal building or use. That said based on current aerial photos there are two (2) detached accessory structure that appear to be located on Parcel “B”. The structures either need to be removed or relocated to Parcel “A”. If relocated to Parcel “A” the sheds are required to meet perimeter yard setbacks and be included in the lot coverage.
If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp
01/26/2022 ROBERT SHERRY PLUMBING-RESIDENTIAL REVIEW Completed
01/26/2022 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: 930 S 8th Ave – Final Plat
FINAL PLAT (1st Review)
S20-045

TRANSMITTAL DATE: January 26, 2022

DUE DATE: February 1, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

2-07.1.0 APPLICABILITY
Final plats, block plats, minor subdivisions, and condominium plats shall be prepared according to the requirements provided below. Hereafter referred to as “plat” or “plats.”
A final plat serves as a survey document suitable for recordation of all or part of an approved tentative plat, if applicable. The final plat must conform to the approved tentative plat or site plan in lot configuration, design, and required conditions of development. The final plat, once approved, is recorded in the Pima County Recorder’s Office. The final plat is kept on file and becomes part of the permanent record for the subject site.
2-07.5.0 CONTENT REQUIREMENTS
2-07.5.1 General
1. COMMENT: 2-07.5.1.A - A project-location map must be drawn in the upper right corner of the first sheet of the plat at a scale of three inches equals one mile and include the following information:

2. COMMENT: 2-07.5.1.A.1 - The project site approximately centered within a one square mile area;

3. COMMENT: 2-07.5.1.A.2 - Label the section, township, and range; section corners; north arrow; and the scale;

4. COMMENT: 2-07.5.1.A.3 - Subdivisions, arterial and collector streets, major watercourses, and railroads within the one-mile area; and,

5. COMMENT: 2-07.5.1.E.1- Provide the number of lots within the title block.

6. COMMENT: 2-07.5.1.H - The subdivision case number, S20-045, assigned to this plat must be placed in the lower right corner of the plat next to the title block on all sheets.
2-07.5.2 General Notes
The plat must include the following general notes. Additional notes specific to each project are required when pertinent. Fill in the blanks with the project-specific information.
7. COMMENT: 2-07.5.2.G - As a Board of Adjustment variance was granted for this project, provide the following note: “This plat is subject to Board of Adjustment variance C10-21-14, unless expired or superseded by a subsequent application.”

2-07.5.3 Standard Paragraphs
The plat must include the following statements, as applicable. All signatures must be in permanent, black, India ink and be accompanied by a notary signature and seal.
8. COMMENT: 2-07.5.3.D. Change the year to 2022 within the Approval Block.

9. COMMENT: Provide a supplemental residential plot plan for Parcel A that demonstrates how requirements such as lot coverage, perimeter yard setbacks, etc are met for the existing house. Reference the requirements for a Residential Plot Plan found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf, This plot plan shall be a provided on a separate sheet from the final plat.

10. COMMENT: Per UDC Article 6.6.2.B An accessory building shall be built only on a lot occupied by a principal building or use. That said based on current aerial photos there are two (2) detached accessory structure that appear to be located on Parcel “B”. The structures either need to be removed or relocated to Parcel “A”. If relocated to Parcel “A” the sheds are required to meet perimeter yard setbacks and be included in the lot coverage.
If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp
02/03/2022 JOSE ORTIZ COT NON-DSD TRAFFIC Approved Email from: David Stiffey
To: CDRC
Thu 2/3/2022 10:56 AM

No Comments
02/04/2022 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved The approval letter is viewable in the Documents section of PRO: "Tucson Water availability letter, 01.28.22"
02/11/2022 AWARNER1 LANDSCAPE REVIEW Passed
02/25/2022 JIM EGAN COT NON-DSD FIRE Approved
03/22/2022 LOREN MAKUS ENGINEERING REVIEW Needs Review 1. Update the name of the City Clerk to Suzanne Mesich.
2. Provide a supplemental site plan showing existing and proposed utility connections.
3. Provide appropriate easements if utilities services cross parcels.

Loren Makus
loren.makus@tucsonaz.gov
03/23/2022 KAY MARKS PIMA COUNTY ADDRESSING Approved Email from: <Addressing@pima.gov>
To: CDRC
Wed 3/23/2022 10:33 AM

Pima County Addressing approves Minor Subdivision - Barrio House, S20-045.

Thank you
Nicholas Jordan
Site Review Project Manager - Addressing Official

Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701
(520) 724-9623
03/23/2022 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change Email from: COTDSDPermits
To: Wesley Meeker
Wed 3/23/2022 3:34 PM

REVIEW NOTICE
Returned for Corrections: S20-045

DESCRIPTION: Minor Subdivision - Barrio House. 930 South 8th Avenue.

Fee Balance: $0 (zero) Thank you for the payment.

YOUR NEXT STEPS
1. SEE REVIEW COMMENTS and documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, Activity Search, enter the Activity/Permit Number
- Permits - click on blue tab to see different sections
- Reviews section - click on REVIEW DETAILS
- Documents section - click on VIEW

2. UPLOAD A RESUBMITTAL and include:
1) Comment Response Letter (your response to REQUIRES CHANGE comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

Please title your SECOND submittal documents accordingly, example: 2_Comment Response Letter

FILEDROP:
https://docs.tucsonaz.gov/Forms/tucsonpermitapp
- "Existing Application"
- In the "Permit Number" field, enter the number and, if applicable, any notes for our staff
- Select "PLANS" for all documents for quicker downloading on our end

Thank you.
Sharon Beasley, Building Permit Specialist

City of Tucson, Planning and Development Services
Email: COTDSDpermits@TucsonAz.gov