Plan Number: S20-014
Parcel: Unknown

Review Status: Completed

Review Details: MINOR SUBDIVISION REVIEW

Plan Number - S20-014
Review Name: MINOR SUBDIVISION REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2020 SBEASLE1 START PLANS SUBMITTED Completed
02/27/2020 SBEASLE1 UTILITIES SOUTHWEST GAS Passed Review not required. This agency was notified for their information only.
02/27/2020 SBEASLE1 PIMA COUNTY WASTEWATER Reqs Change To Applicant: Please provide an approval document in the next resubmittal. The Applicant is responsible for obtaining review and approval for wastewater from Pima County (email: Sewer@Pima.gov) prior to Mayor & Council approval of this final plat.
02/27/2020 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Reqs Change The Applicant is responsible for obtaining a Water Availability Letter from Tucson Water (or Ray Water Company, if applicable). Provide the Letter in the next resubmittal. Mayor & Council cannot approve until water is assured.
02/27/2020 SBEASLE1 OTHER AGENCIES U. S. POST OFFICE Passed Review not required. This agency was notified for their information only.
02/27/2020 SBEASLE1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed Review not required. This agency was notified for their information only.
03/05/2020 SBEASLE1 COT NON-DSD PARKS & RECREATION Approved No existing or proposed Tucson Parks and Recreation facilities are affected by this minor subdivision.

Howard B. Dutt, RLA, Landscape Architect
Tucson Parks and Recreation, (520) 837-8040
03/09/2020 KAY MARKS PIMA COUNTY ADDRESSING Approved (The "attached PDF" mentioned below can be viewed online: www.TucsonAz.gov/Pro. See the "Documents" section.)


S20-014 Final plat for Espinoza Lots 1-6, 1st submittal,is Approved by Pima County Addressing.

The attached pdf shows how the new lots will be addressed once the plat is recorded.
Thank you,
Robin Freiman, Addressing Official
Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701, (520) 724-7570
03/17/2020 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: David Rivera
PDSD Zoning Review Section

PROJECT: Espinoza Lots 1-6 Minor Subdivision
Final Plat (1st Review)
S20-014 - R-2 Zoning

TRANSMITTAL DATE: March 17, 2020

DUE DATE: March 26, 2020

COMMENTS: Please resubmit revised drawings along a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-07. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Final plats, block plats, minor subdivisions, and condominium plats shall be prepared according to the requirements provided below. Hereafter referred to as "plat" or "plats." A final plat serves as a survey document suitable for recordation of all or part of an approved tentative plat, if applicable. The final plat must conform to the approved tentative plat or site plan in lot configuration, design, and required conditions of development. The final plat, once approved, is recorded in the Pima County Recorder's Office. The final plat is kept on file and becomes part of the permanent record for the subject site. (Am. Admin. Directive, 5/14/2013)


2-07.3.0 SUBMITTAL TIMING
Review of final plats is normally initiated after the tentative plat has been approved, unless concurrent tentative and final plat submittal has been approved by the PDSD prior to submittal. Final plats may also be submitted for review prior to the approval of a tentative if a minimum of one review of the tentative plat have occurred. In any case, submittal of the final plat prior to approval of the tentative plat is done at the applicant's risk since changes could be required of the tentative that may affect the final plat.

2-07.4.0 FORMAT REQUIREMENTS



2-07.5.1.A.3 Subdivisions, arterial and collector streets, major watercourses, and railroads within the one-mile area; and,

1. COMMENT: 2-07.5.1.A.3 - List within the location map the subdivision map and plat numbers that are located within the one mile area represented in the location map.


2-07.5.1.H - The Subdivision Case number assigned to the final plat and the DP case number assigned to the approved tentative plat must be placed in the lower right corner of the plat next to the title block. If the property is subject to a rezoning case, the C9-__-__ rezoning case number is to be noted also.
2. COMMENT: 2-07.5.1.H - List the subdivision case number S20-014 next to the title block.


2-07.5.2.J If applicable, add the following note: "This subdivision is subject to Ordinance No. ____ which established zoning in the _____________________ Annexation Area."

3. COMMENT: 2-07.5.2.J Add the note as stated above and include the following in the blanks respectively; "2045" and "West To Silverbell Road and South To San Xavier Indian Reservation".


2-07.5.4.A. Indicate the name and width of each street, alley, easement (type), and drainage way within the subdivision boundary being created by this plat. Label each as public or private, along with the appropriate dedication notation;

4. COMMENT: 2-07.5.4.A Draw the center line for First Avenue and dimension the current right of way width.


5. COMMENT: Add the following two notes;
1. A note stating that "Separate permits will be required for development on each lot".
2. "This subdivision (Residential Development) will be designed to comply with the Inclusive Home Design Ordinance, City of Tucson Ordinance 104631"


If you have any questions about this transmittal, Contact David Rivera on Tuesday, Wednesday or Thursday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised final plat.
03/20/2020 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
03/23/2020 ANDREW CONNOR LANDSCAPE REVIEW Reqs Change ADMINISTRATIVE MANUAL

The Final Plat will contain the following identification in the lower right corner of each sheet:

Any relevant case numbers for reviews or modifications that affect the site.

Provide Case # S20-014 on each sheet.

Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.
03/25/2020 ROBERT SHERRY PLUMBING-RESIDENTIAL REVIEW Reqs Change How will lots 1, 3, and 5 connect to the public sewer? An 18" public sewer runs along on South 1st Av but will Pima County allow you to connect to it?
03/26/2020 LOREN MAKUS ENGINEERING REVIEW Approved
03/31/2020 SBEASLE1 UTILITIES TUCSON ELECTRIC POWER Approved Tucson Electric Power Company, (TEP) has reviewed and approves the final plat submitted on February 27, 2020.
Please be advised that specific TEP easements may be required within the lots in order for TEP to provide electrical service to this new subdivision. The 10’ PUE provided by the plat may not be adequate for our electrical design and future access to our facilities. Any additional easements that may be required will be obtained by separate instrument.

If there are any questions, please contact me at 520-917-8744.
Thank you,
Mary Burke, Senior Right of Way Agent
Tucson Electric Power Co., Land Resources – RC 131
3950 E. Irvington Road, Tucson, AZ 85714-2114
Office - 520-917-8744, mburke@tep.com
04/01/2020 JIM EGAN COT NON-DSD FIRE Approved
04/21/2020 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change RETURNED FOR CORRECTIONS NOTICE
Your Next Steps: Resubmittal with a Comment Response Letter

DESCRIPTION: Minor Subdivision, Final Plat - Espinoza Lots 1-6.
PERMIT: S20-014
FEE BALANCE: $0 (zero)

SEE REVIEWER'S COMMENTS and your submitted documents on PRO: www.tucsonaz.gov/pro
(If information is not available, check back later after data transfers to PRO.)
- Home page, left side, Activity Search, enter the Activity Number
- Permits section, click on blue tab
- Reviews section, click on Review Details
- Documents section, click on blue icon to the right of each document

YOUR NEXT STEPS: Submit the following items to the Filedrop - https://www.tucsonaz.gov/file-upload-pdsd
1) Comment Response Letter (your response to the reviewer's Requires Change comments)
2) Plan Set (all pages, full set, even if no changes were made)
3) Any other documents requested by review staff

- Name your 2nd submittal documents to start with the submittal number, for example: 2_Plan_Set

Thank you.
Sharon Beasley, Permit Specialist

City of Tucson
Planning and Development Services
email: COTDSDPermits@TucsonAz.gov

NOTE: The City of Tucson's Permit Counter at 201 N. Stone Avenue (the physical office) is closed to the public until further notice. In the meantime, our staff is working remotely from home. All communications are by telephone or email.

CONTACT US: To speak with a staff member on the telephone, please sign into the Virtual Zoning Counter: https://www.tucsonaz.gov/pdsd/virtual-walk-thru.
The queue is open from 8:00 am -12:00 noon, Monday-Friday.
It’s better to sign in closer to 8 than 12 noon.
This is similar to the City’s in-person counter.
The difference is after you sign up, we will give you a call.
04/21/2020 ED ABRIGO PIMA COUNTY ASSESSOR Reqs Change Assessor comments:
Dedication stated as " I Ana Maria Valenzuela, the undersigned " not the applicant or persons stated to be signing the dedication, Jesse Espinoza and Rosa Lucatero. Cannot find ownership documents to Ana Maria Valenzuela.
Rejected.
Thank you.
Joyce L Hays
Pima County Assessor’s Office
Program Manager, (Property Ownership and Mapping)
240 N. Stone Ave., Tucson AZ 85701
Phone: 520-724-8257

Final Status

Task End Date Reviewer's Name Type of Review Description
04/21/2020 SBEASLE1 OUT TO CUSTOMER Completed