Plan Number: S19-005
Parcel: Unknown

Address:
8211 E LEE ST

Review Status: Completed

Review Details: FINAL PLAT - REVIEW

Plan Number - S19-005
Review Name: FINAL PLAT - REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2019 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved November 14, 2018
Cypress Civil Development, LLC
2030 E. Speedway Blvd. #110
Tucson, AZ 85719
Attn: Theresa Hadley
SUBJECT: Water Availability for Project: 8211 E. Lee Street , APN: 13309007D,
Case #: WA2653 , T-14 R-15 S-04 , Lots: 9999 , Location Code: TUC , Total Area: 2.38 , Zoning: RX-1
WATER SUPPLY
Tucson Water will provide water service to this project based on the subject zoning of the above parcels. Tucson Water has an assured water supply (AWS) designated from the State of Arizona Department of Water Resources (ADWR). An AWS designation means Tucson Water has met the criteria established by ADWR for demonstration of a 100-year water supply - it does not mean that water service is currently available to the subject project.
WATER SERVICE
The approval of water meter applications is subject to the current availability of water service at the time an application is received. The developer shall be required to submit a water master plan identifying, but not limited to: 1) Water Use; 2) Fire Flow Requirements; 3) Offsite/Onsite Water Facilities; 4) Loops and Proposed Connection Points to Existing Water System; and 5) Easements/Common Areas.
Any specific area plan fees, protected main/facility fees and/or other needed facilities' cost, are to be paid by the developer. If the existing water system is not capable of meeting the requirements of the proposed development, the developer shall be financially responsible for modifying or enhancing the existing water system to meet those needs.
This letter shall be null and void two years from the date of issuance.
Issuance of this letter is not to be construed as agency approval of a water plan or as containing construction review comments relative to conflicts with existing water lines and the proposed development.
If you have any questions, please call New Development at 791-4718.
Sincerely,
Michael Mourreale, P.E.
Engineering Manager
Tucson Water Department
02/04/2019 SBEASLE1 START PLANS SUBMITTED Completed
02/04/2019 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Reqs Change Tucson Electric Power Co., (TEP) has reviewed the final plat submitted on February 4, 2019, and is unable to approve the plat at this time. An electrical design must be completed and easements for TEP facilities shown on the final plat before TEP can approve. In order for TEP to move forward with a preliminary design, please submit a copy of the Approved Development Package/Tentative Plat to jerlacher@tep.com.
If there are any questions, please contact me at 520-401-9895. Thank you,

Mary Burke, Right of Way Agent III
Tucson Electric Power Co., Land Resources - RC 131
3950 E. Irvington Road, Tucson, AZ 85714-2114
Office - 520-917-8744, Cell - 520-401-9895
mburke@tep.com
02/04/2019 SBEASLE1 UTILITIES SOUTHWEST GAS Passed This agency is being notified for their information only. A response is not required.
02/06/2019 ED ABRIGO PIMA COUNTY ASSESSOR Reqs Change DATE: February 6, 2019
FROM: Suzanne Gilpin, GIS Cartographer, Pima County Assessor's Office, (520)724-4387
RE: Assessor's Review and Comments Regarding Final Plat-S19-005-SHALOM SUBDIVISION (1st SUBMITTAL)
COMMENTS:
Ownership MUST match what we have of record. We show Lee St. LLC of record.
02/28/2019 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: David Rivera
PDSD Zoning Review Section

PROJECT: Shalom Subdivision - Lots 1- 12 and Common Area "A"
Final Plat (1st Review) Related to DP18-0274 - 8211 E. Lee Street
S19-005 - Current Zoning RX-1 Rezoning to R-1 per C9-18-19

TRANSMITTAL DATE: February 28, 2019

DUE DATE: March 4, 2019

COMMENTS: Please resubmit revised drawings along a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-07. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Final plats, block plats, minor subdivisions, and condominium plats shall be prepared according to the requirements provided below. Hereafter referred to as "plat" or "plats." A final plat serves as a survey document suitable for recordation of all or part of an approved tentative plat, if applicable. The final plat must conform to the approved tentative plat or site plan in lot configuration, design, and required conditions of development. The final plat, once approved, is recorded in the Pima County Recorder's Office. The final plat is kept on file and becomes part of the permanent record for the subject site. (Am. Admin. Directive, 5/14/2013)


2-07.3.0 SUBMITTAL TIMING
Review of final plats is normally initiated after the tentative plat has been approved, unless concurrent tentative and final plat submittal has been approved by the PDSD prior to submittal. Final plats may also be submitted for review prior to the approval of a tentative if a minimum of one review of the tentative plat have occurred. In any case, submittal of the final plat prior to approval of the tentative plat is done at the applicant's risk since changes could be required of the tentative that may affect the final plat.


2-07.5.1.H - The Subdivision Case number assigned to the final plat and the DP case number assigned to the approved tentative plat must be placed in the lower right corner of the plat next to the title block. If the property is subject to a rezoning case, the C9-__-__ rezoning case number is to be noted also.

1. COMMENT: List the assigned subdivision case number S19-005 next to the title block of both sheets.

Revise the reference case number listed as TP 18-0274 to DP18-0274 on both sheets.


2-07.5.6 Protective Covenants
Protective covenants or Covenants, Conditions, and Restrictions (CC&Rs) establishing responsibility for construction, maintenance, and ownership of any proposed common area, open space, private street, or similar joint use, when needed, will:
2-07.5.6.A. Provide for maintenance of and liability for any proposed commonly-owned areas; and

2. COMMENT: On Page 56 of the CC&Rs correct the year listed from 2017 to 2019.

2-07.5.6.B. Include the various conditions of rezoning or other special situations requiring permanent administration by an owners' association.
(Am. Admin. Directive, 5/14/2013)

3. COMMENT: Per rezoning condition t of the rezoning case C9-18-19, lots 2 and 12 are the only lots allowed to have a two story structure. I believe that this conditions falls within the purview of the standard above. Incorporate condition seven into the CC&R's.


If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised final plat.
03/04/2019 SBEASLE1 PIMA COUNTY ADDRESSING Reqs Change **The PDF attachment can be viewed on PRO in the "Documents" section**

The Addressing review of S19-005 Final Plat for Shalom Subdivision Lots 1-12 is being Returned for Corrections by Pima County Addressing.
The attached pdf contains Addressing's comments.
Please let me know if you have any questions. Thank you,
Robin Freiman, Addressing Official
Pima County Development Services Department
201 N Stone AV – 4th Floor
Tucson, AZ 85701, (520) 724-7570
03/07/2019 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change S19-005

1) Change "NEW PUBLIC DRAINAGE EASEMENT PER THIS PLAT" to NEW PRIVATE DRAINAGE AND MAINTENANCE ACCESS EASEMENT PER THIS PLAT"
2) Update the electrical and gas easements call outs by removing the word "PUBLIC"
3) Sheet 2. In all lots there appears to be door detail, please remove. In common area A there are 2 miscellaneous dots

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
03/11/2019 ALEXANDRA HINES PIMA COUNTY WASTEWATER Reqs Change Applicant is responsible for obtaining review and approval for wastewater from Pima County at sewer@pima.gov prior to sending to Mayor & Council for approval. Provide wastewater approval letter for P19WS00006 in resubmittal.
03/12/2019 SBEASLE1 ZONING-DECISION LETTER REVIEW Reqs Change PLAN RETURNED FOR CORRECTIONS NOTICE
The reviews have been completed and a resubmittal is required.
Activity Number: S19-005
Project Description: FINAL PLAT - Shalom Subdivision, Lots 1-12 and Common Area "A" (drainage basin).
To see review comments, visit PRO at www.tucsonaz.gov/PRO, then search by Activity Number. (If new comments aren't shown yet, check back later as data flows to PRO periodically throughout the day.)
Prepare a Comment Response Letter detailing changes to the plan and which review comments are being addressed. Name your documents in the following manner - a 2nd submittal document would be titled: 2_Plan_Set.
After the necessary corrections have been made, submit the following items to the PDSD Filedrop at https://www.tucsonaz.gov/file-upload-pdsd
In the Project Description field, enter the Activity Number.
After submittal, the plans will then re-enter a 20-working-day review cycle.
1) Comment Response Letter
2) Corrected plan set with all documents
3) Items requested by review staff
The fee balance is $0 (zero). Maria Gayosso, copied, is the Project Manager to contact with any questions, email: Maria.Gayosso@TucsonAz.gov or phone: (520) 837-6972.
Thank you.
City of Tucson
Planning and Development Services
Attn: Sharon Beasley
201 N. Stone Avenue, First Floor
Tucson, AZ 85701

Final Status

Task End Date Reviewer's Name Type of Review Description
03/12/2019 SBEASLE1 OUT TO CUSTOMER Completed