Plan Review Detail
Review Status: Completed
Review Details: MINOR SUBDIVISION REVIEW
Plan Number - S18-084
Review Name: MINOR SUBDIVISION REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/26/2018 | ALEXANDRA HINES | START | PLANS SUBMITTED | Completed | |
| 09/26/2018 | ALEXANDRA HINES | UTILITIES | SOUTHWEST GAS | Passed | Agency notified for information only. |
| 09/26/2018 | ALEXANDRA HINES | OTHER AGENCIES | U. S. POST OFFICE | Passed | Agency notified for information only. |
| 09/26/2018 | AHINES2 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Approved | Water available for area. |
| 09/26/2018 | ALEXANDRA HINES | OTHER AGENCIES | PIMA ASSN OF GOVTS | Passed | Agency notified for information only. |
| 10/09/2018 | JIM EGAN | COT NON-DSD | FIRE | Reqs Change | Lots 5 & 6 are deeper than 150' from the fire department access road, with no turnaround. Residential fire sprinklers could be considered as an alternative to access. |
| 10/09/2018 | ED ABRIGO | PIMA COUNTY | ASSESSOR | Approved | Office of the Pima County Assessor 240 N STONE AVENUE Tucson, Arizona 85701 BILL STAPLES ASSESSOR TO: CDRC Office Subdivision Review City of Tucson (FAX# 791-5559) FROM: Julieann Arechederra GIS Cartographer Pima County Assessor's Office DATE: October 8, 2018 RE: Assessor's Review and Comments Regarding: SAM HUGHES VILLAS FINAL PLAT * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * X Plat meets Assessor's Office requirements. COMMENTS: NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED. |
| 10/11/2018 | KAY MARKS | PIMA COUNTY | ADDRESSING | Reqs Change | S18-084 Sam Hughes Villas Lot 1-6 / 1st Submittal is being Returned for Corrections by Pima County Addressing. Please see the attached pdf for Addressing’s comments. Let me know if you have any questions or if I may assist you further. Thank you, Robin Freiman Addressing Official Pima County Development Services Department 201 N Stone AV – 1st Floor Tucson, AZ 85701 (520) 724-7570 |
| 10/12/2018 | ANDREW CONNOR | LANDSCAPE | REVIEW | Approved | |
| 10/12/2018 | ZELIN CANCHOLA | COT NON-DSD | TRAFFIC | Approved | |
| 10/17/2018 | LIZA CASTILLO | UTILITIES | TUCSON ELECTRIC POWER | Reqs Change | Tucson Electric Power Co., (TEP) has reviewed the final plat submitted on October 1, 2018, and is unable to approve the plat at this time. An electrical design must be completed and easements for TEP facilities shown on the final plat in order for TEP to approve. Also, the following revisions are requested: 1. Please revise the Ingress/Egress and Access Easements to be Ingress/Egress and Utility Easements. If you have any questions, please contact me at 520-917-8744. Thank you, Mary Burke Right of Way Agent III Tucson Electric Power Co. Land Resources – RC 131 3950 E. Irvington Road Tucson, AZ 85714-2114 Office - 520-917-8744 Cell - 520-401-9895 mburke@tep.com |
| 10/18/2018 | ROBERT SHERRY | PLUMBING-RESIDENTIAL | REVIEW | Reqs Change | 1. Revise the site drawing to include the location of the public sanitary sewer manholes, including the rim elevations of the upstream and downstream manholes along with the Pima County Wastewater Management Department (PCWMD) reference number. Reference: City of Tucson Administrative Manual, Section 2-06.4.8D and Section 107.2.1, IBC 2012. 2. Clarify how lots 5 and 6 connect to the public or private sewer systems. Reference: Section 701.2, IPC 2012. 3. Where the proposed finish floor elevation is less than 12 inches above the elevation of the next upstream manhole in the public sewer or private sewer collection system, a backwater valve shall be installed in the building drain or branch of the building drain serving that floor. Floors discharging from above that reference point shall not discharge through the backwater valve. Reference: Section 715.1, IPC 2012, as amended by the City of Tucson. |
| 10/19/2018 | EHAMBLI1 | ZONING HC | REVIEW | Passed | |
| 10/19/2018 | KELLY LEE | PIMA COUNTY | WASTEWATER | Passed | No review required. See email from Pima County wastewater in pRO. |
| 10/19/2018 | EHAMBLI1 | ZONING | REVIEW | Reqs Change | CDRC Transmittal TO: Planning and Development Services Department Plans Coordination Office FROM: Elisa Hamblin, AICP Lead Planner PDSD Zoning Review Section PROJECT: Sam Hughes Court, 2340 E 8th St Minor Subdivision (1st Review) S18-084 TRANSMITTAL DATE: October 19, 2018 DUE DATE: October 19, 2018 COMMENTS: Please resubmit revised drawings along a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-07. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). 1. 2-07.5.1.A.4. - The location map on sheet 1 should have the subject property approximately centered within the map. The map does not need to indicate every parcel, but should include subdivisions. 2. 2-07.5.1.E. - The title block must include the legal description of the subject parcel and if the final plat is a resubdivision of a previously recorded plat, indicate the title and the book and page/sequence number reference of the existing subdivision. 3. 2-07.5.1.G. - Line weights will reflect the nature of the line, e.g., right-of-way lines must be more prominent than lot lines or easements and drainageways must be shown in heavy solid lines except at street crossings. 4. 2-07.5.1.H. - The subdivision case number (S18-084) must be placed in the lower right corner of the plat next to the title block. 5. 2-07.5.2.J. - Add the following general note: "This subdivision is subject to Ordinance No. 939 which established zoning in the East Broadway Annexation Area." 6. 2-07.5.3.E. - Assurances. The following ASSURANCE block must be placed on the plat's first sheet. ASSURANCES "This is to certify that all improvements, such as streets, sidewalks, sewers, water and utility installation, drainage and flood control facilities, and monuments, required by the City of Tucson have been completed or the future completion of such improvements has been assured by a land trust financial assurance agreement, the posting of performance bonds, an escrow account, letter of credit, or other security as the City of Tucson deems necessary and proper. In the event that any such assurance expires, lapses or is otherwise inadequate to assure the completion of assurable infrastructure, the city may suspend the issuance of building permits or certificates of occupancy." ____________________________________________ City of Tucson Planning and Development Services Department Director ____________________________________________ City of Tucson City Engineer 7. 2-07.5.4. - Proposed Subdivision Information. Provide the following information on the plat: 8. 2-07.5.4.A. - Indicate the easement or other use for the 5' width and 3' width shown on the northern end of lot 5. Indicate the easement or use for the approximately 3' width shown on the southern boundary of lots 1, 2, and 3. 9. 2-07.5.4.E. - Show required setbacks, such as erosion hazard, drainage, etc.; 10. General comment - A supplementary site plan was submitted with this Minor Subdivision. As a courtesy, please be aware that several features do not meet development standards. Detached accessory structures are not permitted in the street perimeter yard as illustrated on Lot 6. The perimeter yard setbacks are 6' or 2/3 the height whichever is greater. The proposed 12' height would require a setback of 8'. If you have any questions about this transmittal, please contact me at Elisa.Hamblin@tucsonaz.gov or (520) 837-4966. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised final plat. |
| 10/24/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | 1. Add the complete assurances statement. 2. UDC 7.11.1 requires retention and detention basins to be outside of residential lots. Revise the plan to show common area ownership for the retention basins. 3. The title report lists an easement for telephone and telegraph lines and appurtenant facilities. Show the easement on the plat. 4. In the response letter describe the assurances mechanism for the subdivision. If necessary, add the applicable notes to the plat. |
| 10/25/2018 | KELLY LEE | ZONING-DECISION LETTER | REVIEW | Reqs Change | Chris: This review has been completed and resubmittal is required. Please resubmit the following items: Prepare a Comment Response Letter which tells the reviewer what changes have been made to the plan and what comments are addressed. When you have made the necessary corrections to the plans, please resubmit the following items to PDSD Filedrop: https://www.tucsonaz.gov/file-upload-pdsd 1) Corrected plan set 2) Items requested by review staff Please remember to name your files appropriately, for example: second (2nd) submittal, 2_plan_set.pdf 2_swppp_report.pdf and the plans will re-enter the review cycle. Thank you, Kelly Lee Lead Planner Planning & Development Services (520) 837-6999 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/21/2018 | SBEASLE1 | OUT TO CUSTOMER | Completed |