Plan Number: S18-004
Parcel: Unknown

Review Status: Completed

Review Details: FINAL PLAT - REVIEW

Plan Number - S18-004
Review Name: FINAL PLAT - REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2018 QJONES1 START PLANS SUBMITTED Completed
01/18/2018 KELLY LEE UTILITIES SOUTHWEST GAS Passed
01/31/2018 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Reqs Change Tucson Electric Power Co., (TEP) has reviewed the final plat submitted on January 18, 2018, and is unable to approve the plat at this time. An electrical design must be completed and any required easements for TEP facilities need to be shown on the final plat in order for TEP to approve.

To initiate design, please submit the Approved Tentative Plat and water plans to mburke@tep.com.

If you have any questions, please contact me at 520-917-8744.

Thank you,

Mary Burke
Right of Way Agent III
Tucson Electric Power Co.
Land Resources – RC 131
3950 E. Irvington Road
Tucson, AZ 85714-2114
Office - 520-917-8744
Cell - 520-401-9895
mburke@tep.com
02/05/2018 ALEXANDRA HINES OTHER AGENCIES TUCSON AIRPORT AUTHORITY Approv-Cond February 2, 2018

Kelly Lee
Lead Planner
City of Tucson
Public Works Buildings - 201 North Stone Avenue
Tucson, AZ. 85701

RE: S18-004 Final Plat La Estancia de Tucson, Lots 665-828 / 1st Submittal, Received January 18, 2018

Dear Ms. Lee,

Thank you for the opportunity to comment on DP18-004, Final Plat La Estancia de Tucson, Lots 665-828; 1st Submittal, a final plat application for an approximately 21 acre site, the project area is located northeast of the intersection of Los Reales Road and South Wilmot Road. The proposed land use is residential; establishing single family homes.

This site is within the Tucson International Airport avigation easement requirements and public disclosure area and FAA traffic pattern airspace.

The Tucson Airport Authority provided comments on a previous submittal, DP17-0254, comment letter dated 11/20/17, which is identified as being associated with S18-004.

The Tucson Airport Authority conditionally approves the subject request contingent upon the following conditions of approval, as noted below. These conditions should be identified in the general notes of the approved development plan.

Conditions of approval:

"That prior to the City's approval of any construction permit for a permanent building, the property owner shall record the Avigation Easement prior to the subdivision process which discloses the existence, and operational characteristics of the Tucson International Airport to future owners or tenants of the property and further conveys the right to the public to lawfully use the airspace above the property. The content of such documents shall be according to the form and instructions provided."

The current property owner or person authorized to sign on behalf of the current property owner shall complete, sign, and record the Avigation Easement. Please record the Avigation Easement with the Pima County Recorder's Office. Once the Avigation Easement is recorded please send a copy of the recorded easement to Tucson Airport Authority by either email (send to srobidoux@flytucson.com) or to the mailing address provided below.

Scott Robidoux
Senior Airport Planner
Tucson Airport Authority
7250 South Tucson Boulevard
Suite 300
Tucson, AZ 85756

"The developer shall provide the Airport Disclosure Statement form, at time of sale, to the new property owners with new unit purchases. In the event this proposed project does not involve the sale of new units, but is instead offering rental residential units to the public, the new tenant of the rental unit shall be provided a copy of the Airport Disclosure Statement form. The intent of the Airport Disclosure Statement form is to educate and notify the new residents that they are living near an airport."

The new property owner or new tenant shall forward a signed copy of the Airport Disclosure Statement form to:

Scott Robidoux
Senior Airport Planner
Tucson Airport Authority
7250 South Tucson Boulevard
Suite 300
Tucson, AZ 85756

Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811.

Respectfully,


Scott Robidoux,
Senior Airport Planner

cc file
02/07/2018 ED ABRIGO PIMA COUNTY ASSESSOR Reqs Change Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson


FROM: Ada Griffin
GIS Cartographer
Pima County Assessor's Office


DATE: February 6, 2018


RE: Assessor's Review and Comments Regarding:

S18-004 Final Plat La Estancia de Tucson, Lots 665-828 /
1st Submittal

_

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Plat meets Assessor's Office requirements.
___X___ Plat does not meet Assessor's Office requirements.

COMMENTS:


" THERE MUST BE A SECTION TIE, WITH A BEARING AND DIMENSION FROM THE SECTION CORNER OR QUARTER CORNER TO THE POINT OF TIE ON THE SUBDIVISION.

" THE PERIMETER LINE MUST BE SOLID AND HEAVIEST LINE WEIGHT ON THE PLAT. THE LOT LINES AND COMMON AREA LINES MUST BE SOLID AND THE NEXT HEAVIEST.

NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.
02/08/2018 ALEXANDRA HINES PIMA COUNTY ADDRESSING Reqs Change ***Attachment in Documents folder on PRO.***

S18-004 Final Plat La Estancia de Tucson, Lots 665-828 / 1st Submittal is being Returned for Corrections by Pima County Addressing.

The attached pdf contains Addressing’s comments.

Please let me know if you have any questions.

Thank you,

Robin Freiman
Addressing Official
Pima County Development Services Department
201 N Stone AV – 1st Floor
Tucson, AZ 85701
(520) 724-7570
02/09/2018 KELLY LEE ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Kelly Lee, Lead Planner
PDSD Zoning Review Section

PROJECT: S18-004 La Estancia de Tucson
Final Plat (1st Review)

TRANSMITTAL DATE: February 6, 2018

DUE DATE: February 9, 2018

COMMENTS: Please resubmit revised drawings along a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-07. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

The review comments include the actual standard first with the applicable Administrative Manual section number and the following paragraph is the actual comment related to the specific item that must be addressed. If you need to review the sections listed below click on the link or copy it in the address bar of your internet program. http://www.amlegal.com/nxt/gateway.dll/Arizona/tucson_az_udc/administrativemanual?f=templates$fn=default.htm$3.0$vid=amlegal:tucson_udc_az

The following documents and information shall be submitted upon application:

2.1 Application Form- Please revise application to include property owner and contact information.

2-07.5.1.A A project-location map must be drawn in the upper right corner of the first sheet of the plat at a scale of three inches equals one mile and include the following information:

2-07.5.1.A.3 Subdivisions, arterial and collector streets, major watercourses, and railroads within the one-mile area; and,

1. COMMENT: Label the Julian Wash (major watercourse) on the project location map.

2-07.5.1.C If the project is located within the boundaries of a Planned Area Development (PAD) zone, include a reduced-scale map of the entire PAD on the first sheet, indicating the location of the portion being developed.

2. COMMENT: The reduced scale map does not show the entire PAD. Please correct.

2-07.5.1.E. Provide a title block in the lower right corner of each sheet

3. COMMENT: Please make the tentative plat and block plat title block consistent with eachother.

2-07.5.1.H The DP case number for assigned to the approved tentative plat must be placed in the lower right corner of the plat next to the title block. If the property is subject to a rezoning case, the C9-__-__ rezoning case number is to be noted also.

4. COMMENT: What is the SP number? Please confirm this is for PAD-7.

2-07.5.1.I A legend which shows and describes all symbols used on the drawing must be placed on either the first sheet of the plat or the first sheet which contains all or part of the subdivision drawing.

5. COMMENT: Please identify the meaning of the asterisks next to lot number: 828

2-07.5.2.D If the property is subject to conditions of rezoning, add the following note: "This plat is subject to the conditions of rezoning case number C9-__-__, unless superseded by a subsequent rezoning ordinance."

6. COMMENT: Add the ordinance number to note 6 and remove reference to City of Tucson Land Use Code and replace with Unified Development Code.

7. COMMENT: please identify reference to Development Regulations III.A.1Se2. I could not find that section in the Planned Area Development.

8. COMMENT: Please remove reference to rezoning for Van Horne Elementary C9-16-03.

9. COMMENT: Please remove reference to Land use Code in note 10. Replace with Unified Development Code.

2-07.5.4.C. If the project has common areas, label each common area individually with a separate letter designation. Enclose with a solid line each common area, private street, etc., that will have separate restrictions, a separate homeowners' association, or any common area that is separated by a public right-of-way;

10. COMMENT: Please add label to sheet 3 identifying the CA?

If you have any questions about this transmittal, Contact Kelly Lee at (520) 837-6999 or by email Kelly.Lee@tucsonaz.gov or contact Steve Shields at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised final plat.
02/09/2018 ALEXANDRA HINES PIMA COUNTY WASTEWATER Reqs Change The applicant is responsible for obtaining review and approval for wastewater from Pima County at sewer@pima.gov.
02/14/2018 KLEE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved Water Availability Letter found in Sire under documents.
02/22/2018 JOHN VAN WINKLE ENGINEERING REVIEW Approv-Cond 1) Sheet 1, Note 10 indicates that maximum building height is 2845 feet. This is probably meant to say, maximum building elevation since height is measured from grade. Verify and update note
2) Remove site visibility triangles (SVT) from all sheets. SVT's are not required for a final plat and as shown cannot be surveyed
3: Sheet 1, remove notes 12 and 16, they are not required to be shown

Updates can be reviewed on final mylar plat

John Van Winkle, P.E.
john.van-winkle@tucsonaz.gov
520-537-5007
02/23/2018 KELLY LEE ZONING-DECISION LETTER REVIEW Reqs Change This review has been completed and resubmittal is required. Please resubmit the following items:
1) Two rolled sets of the plans
2) All approved documents submitted previously
3) A disk containing all items submitted
4) All items requested by review staff
5) All items needed to approve these plans

Final Status

Task End Date Reviewer's Name Type of Review Description
03/23/2018 KROBLES1 OUT TO CUSTOMER Completed