Plan Number: S17-076
Parcel: Unknown

Review Status: Completed

Review Details: SUBPLAT- OK TO SUBMIT

Plan Number - S17-076
Review Name: SUBPLAT- OK TO SUBMIT
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/08/2017 QJONES1 START PLANS SUBMITTED Completed
12/08/2017 ALEXANDRA HINES ZONING REVIEW Needs Review
12/08/2017 LOREN MAKUS ENGINEERING REVIEW Needs Review 1. Revise the signature line for the assurances block to read "City of Tucson City Engineer."
2. Revise or remove the note dedicating the channels to the Flood Control District.
3. Provide a flowage easement for all regulatory watercourses with a discharge greater than 100 cfs.
4. Clarify the assurances mechanism to be used and add appropriate notes.
5. Ensure the CC&Rs provide for maintenance of drainage facilities.