Plan Review Detail
Review Status: Completed
Review Details: MINOR SUBDIVISION REVIEW
Plan Number - S17-058
Review Name: MINOR SUBDIVISION REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/04/2017 | ARUIZ1 | START | PLANS SUBMITTED | Completed | |
| 10/05/2017 | ROBERT SHERRY | PLUMBING-RESIDENTIAL | REVIEW | Completed | |
| 10/06/2017 | ALEXANDRA HINES | UTILITIES | SOUTHWEST GAS | Passed | Agency notified for information only. |
| 10/06/2017 | ALEXANDRA HINES | OTHER AGENCIES | U. S. POST OFFICE | Passed | Agency notified for information only. |
| 10/06/2017 | AHINES2 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Passed | Water assured for less than 6 lots. |
| 10/06/2017 | ALEXANDRA HINES | OTHER AGENCIES | PIMA ASSN OF GOVTS | Passed | Agency notified for information only. |
| 10/10/2017 | ED ABRIGO | PIMA COUNTY | ASSESSOR | Reqs Change | Office of the Pima County Assessor 240 N STONE AVENUE Tucson, Arizona 85701 BILL STAPLES ASSESSOR TO: CDRC Office Subdivision Review City of Tucson (FAX# 791-5559) FROM: Janice Wagner GIS Cartographer Pima County Assessor's Office DATE: October 10, 2017 RE: Assessor's Review and Comments Regarding: S17-058 NWC ORACEL ROAD & LIMBERLOST DRIVE / 1ST FINAL REVIEW * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * Plat meets Assessor's Office requirements. ____X___ Plat does not meet Assessor's Office requirements. COMMENTS: " THE TITLE BLOCK MUST BE IN THE LOWER RIGHT HAND CORNER. IT MUST HAVE THE NUMBER OF LOTS OR UNITS OR BLOCKS OR ANY COMBINATION OF THESE. IT MUST HAVE THE COMMON AREAS LISTED, IF THERE ARE ANY. IT MUST HAVE THE SECTION, TOWNSHIP AND RANGE AND IF IT IS A RESUBDIVISION, IT MUST MENTION THE PLAT NAME AND THE MAP AND PLAT. " ALL ADJACENT SUBDIVISIONS SHOULD BE NAMED, WITH MAP AND PLAT IN THE APPROPRIATE AREAS AROUND THE SUBDIVISION. " CHECK OWNERSHIP TO MAKE SURE IT MATCHES WHAT WE HAVE. OUR RECORDS HAVE LAST DEED SHOWN IN EVT TUCSON FIESTA RECORDED IN SQ20172640711. NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED. |
| 10/19/2017 | ZELIN CANCHOLA | COT NON-DSD | TRAFFIC | Approved | |
| 10/20/2017 | KAY MARKS | PIMA COUNTY | ADDRESSING | Reqs Change | S17-058 NWC Oracle Road & Limberlost Drive / 1st Submittal is being Returned for Corrections by Pima County Addressing. The attached pdf contains Addressing’s comments. Please let me know if you have any questions. Thank you, Robin Freiman Addressing Official Pima County Development Services Department 201 N Stone AV – 1st Floor Tucson, AZ 85701 (520) 724-7570 |
| 10/25/2017 | JIM EGAN | COT NON-DSD | FIRE | Approved | |
| 10/25/2017 | JOHN BEALL | COT NON-DSD | COMMUNITY PLANNING | Approved | PLANNING AND DEVELOPMENT SERVICES DEPARTMENT COMMENTS Regarding SUBJECT: Community Design Review Committee Application CASE NUMBER: CASE NAME: DATE SENT S17-058 NWC Oracle Road & Limberlost Drive 10/25/2017 (X) Final Plat () Development Plan () Landscape Plan () Revised Plan/Plat () Board of Adjustment () Other - Elevations SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS: (X) Approval () Denied () Rezoning history on site () Annexation history on site () Tentative Plat () Development Plan () Landscape Plan () Other REVIEWER: MM DATE: 10/25/2017 COMMENTS Site is addressed 4215 N Oracle Rd and currently being reviewed for S17-058 Final Plat. Site is zoned C-3, and is in compliance with Plan Tucson. |
| 10/27/2017 | LIZA CASTILLO | UTILITIES | TUCSON ELECTRIC POWER | Reqs Change | Tucson Electric Power Co., (TEP) has reviewed the final plat submitted on 10-6-17, and is unable to approve the plat at this time. Please add the following: 1. Identify the plat as a resubdivision of Lot 31 and a portion of Lot 32 of Rillito Park subdivision recorded in Book 3 of Maps, Page 17 2. Add the following TEP easements to the plat: Docket 9699 Page 2888 and Book 4203 Page 176 3. Correct the label for the 10’ Public Utility Easement along the western boundary of Lot 31 to read Doc 10049 (not 1049) Pg 477 If you have any questions regarding these comments, please contact me at 520-917-8744. Thank you, Mary Burke Right of Way Agent III Tucson Electric Power Co. Land Resources – RC 131 3950 E. Irvington Road Tucson, AZ 85714-2114 Office - 520-917-8744 Cell - 520-401-9895 mburke@tep.com |
| 10/30/2017 | SSHIELD1 | ZONING HC | REVIEW | Approved | |
| 10/30/2017 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Principal Planner PROJECT: NWC Oracle Road & Limberlost Drive Final Plat (1st Review) S17-058 TRANSMITTAL DATE: October 30, 2017 DUE DATE: November 01, 2017 COMMENTS: Please resubmit revised drawings along a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-07. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). The review comments include the actual standard first with the applicable Administrative Manual section number and the following paragraph is the actual comment related to the specific item that must be addressed. If you need to review the sections listed below click on the link or copy it in the address bar of your internet program. http://www.amlegal.com/nxt/gateway.dll/Arizona/tucson_az_udc/administrativemanual?f=templates$fn=default.htm$3.0$vid=amlegal:tucson_udc_az This link will take you directly to the section used for the standards review. The UDC & TSM requirements are in the Unified Development Code and can be viewed at the same web link as above 5.1 General 1. 2-07.5.1.D Place the words "SEQ#________" in both the upper and lower right corners outside the margin line. 2-07.5.1.E Provide a title block in the lower right corner of each sheet with the following information: 2-07.5.1.E.1 Subdivision name; number of blocks, lots, and/or units; and common area; 2. 2-07.5.1.E.1 Provide the following within the title block, subdivision name & number of lots. 2-07.5.1.E.2 Legal description by section, township, and range; and, 3. 2-07.5.1.E.2 Provide the following within the title block, Legal description by section, township, and range. 4. 2-07.5.1.E.3 If the final plat is a resubdivision of a previously recorded plat, indicate the title and the book and page/sequence number reference of the existing subdivision. 5. 2-07.5.1.H Place the subdivision case number, S17-058, in the lower right corner of the plat next to the title block. 6. 2-07.5.2.J Add the following note: "This subdivision is subject to Ordinance No. 5651 which established zoning in the Oracle Road/Wetmore Road II Annexation Area." 2-07.5.3 Standard Paragraphs The plat must include the following statements, as applicable. All signatures must be in permanent, black, India ink and be accompanied by a notary signature and seal. 7. 2-07.5.3.D The approval block should match verbatim what is shown in AM 2-07.5.3.D. If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised final plat. |
| 10/31/2017 | TOM MARTINEZ | OTHER AGENCIES | AZ DEPT TRANSPORTATION | Approved | The Arizona Department of Transportation (ADOT) has reviewed the referenced 1st Submittal, and the following comments are provided: ADOT has reviewed and accepted the September 25, 2017 Traffic Impact Analysis (TIA) for the proposed Limber Restaurants to be located on the northwest corner of the State Route 77 (Oracle Road)/Limberlost Drive intersection (Project Address: 4215 N. Oracle Road). Copy of ADOT’s “Letter of Acceptance” is attached. In general, we concur with the findings and recommendations in the report. At the present time, access to the site is provided by three existing driveways, two driveways on Oracle Road and one driveway on Limberlost Drive. With the project, these three access points will continue to provide access to the site. The south driveway on Oracle Road (identified as South Sports Driveway in the TIA) will be shifted approximately 75 feet to the north as part of the development. In addition, as shown in the TIA, a southbound right-turn lane will be required on Oracle Road at the South Sports Driveway to serve this development. The specific geometry of the southbound right-turn lane on Oracle Road will be addressed during design. As per Intergovernmental Agreement between the State of Arizona and the City of Tucson, the City will issue the “State Highway Right-of-Way Encroachment Use Permit” for work in State right-of-way at this location. ADOT will assist the City with reviewing and approving the “Off-Site Improvement Plans”. We appreciate the opportunity to review the development package. Thank you. Maria Deal Transportation Engineering Specialist ADOT Southern Regional Traffic Engineering 1221 S. 2nd Ave. Tucson, AZ 85713 520.388.4235 mdeal@azdot.gov |
| 10/31/2017 | ALEXANDRA HINES | COT NON-DSD | PARKS & RECREATION | Approved | No existing or proposed Tucson Parks and Recreation facilities are affected by this development. Howard B. Dutt, RLA Landscape Architect Tucson Parks & Recreation (520) 837-8040 Howard.Dutt@tucsonaz.gov |
| 11/01/2017 | ANDREW CONNOR | LANDSCAPE | REVIEW | Reqs Change | Ensure that all Zoning comments are addressed. |
| 11/02/2017 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | 1. Revise the signature line for the PDSD Engineering Administrator to read "City of Tucson City Engineer." |
| 11/02/2017 | ANDREW CONNOR | NPPO | REVIEW | Approved | |
| 11/03/2017 | ALEXANDRA HINES | ZONING-DECISION LETTER | REVIEW | Reqs Change | This review has been completed and resubmittal is required. Please resubmit the following items: 1) Two rolled sets of the plans 2) All approved documents submitted previously 3) A disk containing all items submitted 4) All items requested by review staff 5) All items needed to approve these plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/03/2017 | KROBLES1 | OUT TO CUSTOMER | Completed |