Plan Review Detail
Review Status: Completed
Review Details: MINOR SUBDIVISION REVIEW
Plan Number - S16-074
Review Name: MINOR SUBDIVISION REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/21/2016 | AHINES2 | START | PLANS SUBMITTED | Completed | |
| 09/21/2016 | AHINES2 | UTILITIES | SOUTHWEST GAS | Passed | For notification purposes only. |
| 09/21/2016 | AHINES2 | PIMA COUNTY | WASTEWATER | Reqs Change | September 19, 2016 To: Kevin Hall Cypress Civil Development c/o Lisa Bowers Tucson Expediting & Development Thru: Patricia Gehlen, CDRC Manager City of Tucson Development Services Department From: _______________________________________________ Debbie Ketchem, Civil Engineer Assistant - Sr. Development Liaison Unit Subject: Review Letter - sewer elements only Final Plat - 1st Submittal, P16WS00081 (S16-074) City Park Block 1 ____________________________________________________________________________ Pima County Regional Wastewater Reclamation Department (PCRWRD) received this Final Plat on September 15, 2016. The following revisions are requested: 1. Sheet 1: Dedication paragraph two (2), revise the Dedication to remove reference to easements. If the Dedication is correct then easements must be shown. 2. The Final Plat may not be approved until a RWRD Capacity Availability Type II letter is obtained. The next submittal will be the 2nd submittal for this Final Plat. The RWRD review fee for the 2nd submittal will be $0.00 (Per PC Code, Title 13.20.030.A.2). It is acceptable to send your corrected plans electronically to RWRDFP@pima.gov or Debbie.Ketchem@pima.gov. Do not hesitate to contact me if you have any questions at (520) 724-6481. Cc: Lorenzo Hernandez, P.E., C.E. Manager., RWRD Francisco Galindo, P.E., RWRD |
| 09/21/2016 | AHINES2 | OTHER AGENCIES | U. S. POST OFFICE | Passed | For notification purposes only. |
| 09/21/2016 | AHINES2 | OTHER AGENCIES | PIMA ASSN OF GOVTS | Passed | For notification purposes only. |
| 09/22/2016 | ED ABRIGO | PIMA COUNTY | ASSESSOR | Approved | Office of the Pima County Assessor 240 N. Stone Ave. Tucson, Arizona 85701 BILL STAPLES ASSESSOR TO: City of Tucson Development Services Department FROM: Suzanne Gilpin GIS Cartographer Pima County Assessor's Office (520)724-4387 DATE: September 22, 2016 RE: Assessor's Review and Comments Regarding Final Plat- S16-074 CITY PARK - 1ST SUBMITTAL * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * X Plat meets Assessor's Office requirements. ______ Plat does not meet Assessor's Office requirements. COMMENTS: NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED. |
| 09/23/2016 | KAY MARKS | PIMA COUNTY | ADDRESSING | Approv-Cond | S16-074 City Park / 1st Submittal is Approved by Pima County Addressing subject to correcting the reference for parcel 2 of the Post Condominiums to Bk 62 Pg 61. Please let me know if you have any questions. Thank you, Robin Freiman Addressing Specialist Pima County Development Services Department 201 N Stone AV – 1st Floor Tucson, AZ 85701 (520) 724-7570 |
| 09/27/2016 | ROBERT SHERRY | PLUMBING-RESIDENTIAL | REVIEW | Passed | |
| 09/28/2016 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: David Rivera for Steve Shields - Principal Planner PDSD Zoning Review Section PROJECT: City Park Block 1 - 56 E Congress Street Final Plat (1st Review) S16-074 TRANSMITTAL DATE: September 28, 2016 DUE DATE: October 12, 2016 COMMENTS: Please resubmit revised drawings along a detailed response letter, which states how all Zoning Review Section comments were addressed. This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-07. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). 2-07.5.0 CONTENT REQUIREMENTS 5.1 General 2-07.5.1.A.2 Label the section, township, and range; section corners; north arrow; and the scale; 1. COMMENT: Label the on the location map the section corners 7 and 18. 2-07.5.1.A.3 Subdivisions, arterial and collector streets, major watercourses, and railroads within the one-mile area; and, 2. COMMENT: Label the SSPRR and Broadway Blvd. on the location map. 2-07.5.1.E Provide a title block in the lower right corner of each sheet with the following information: 2-07.5.1.H The S(Year)-___ subdivision case number assigned to the approved tentative plat must be placed in the lower right corner of the plat next to the title block. If the property is subject to a rezoning case, the C9-__-__ rezoning case number is to be noted also. 3. COMMENT: This plat has been assigned the PDSD case number S16-074. List the case number next to the title block. 2-07.5.2 General Notes The plat must include the following general notes. Additional notes specific to each project are required when pertinent. Fill in the blanks with the project-specific information. 2-07.5.2.D If the property is subject to conditions of rezoning, add the following note: "This plat is subject to the conditions of rezoning case number C9-__-__, unless superseded by a subsequent rezoning ordinance." 4. COMMENT: Just a caveat, if it has not yet been done, check with Rezoning staff to ensure that the proposal is not considered a change major change of PDP. Contact John Beall at 837-6966. 2-07.5.3.E Assurances The following ASSURANCE block must be placed on the plat's first sheet. ASSURANCES "This is to certify that all improvements, such as streets, sidewalks, sewers, water and utility installation, drainage and flood control facilities, and monuments, required by the City of Tucson have been completed or the future completion of such improvements has been assured by a land trust financial assurance agreement, the posting of performance bonds, an escrow account, letter of credit, or other security as the City of Tucson deems necessary and proper. In the event that any such assurance expires, lapses or is otherwise inadequate to assure the completion of assurable infrastructure, the city may suspend the issuance of building permits or certificates of occupancy." City of Tucson Planning and Development Services Department Director City of Tucson PDSD Engineering Administrator 5. COMMENT: Change the words "City of Tucson PDSD Engineering Administrator" to City Engineer. 2-07.5.6 Protective Covenants Protective covenants or Covenants, Conditions, and Restrictions (CC&Rs) establishing responsibility for construction, maintenance, and ownership of any proposed common area, open space, private street, or similar joint use, when needed, will: 2-07.5.6.A. Provide for maintenance of and liability for any proposed commonly-owned areas; and 6. COMMENT: Clarify if the recorded CC&Rs will be revised based on the new development. If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised final plat. |
| 09/28/2016 | DAVID RIVERA | ZONING HC | REVIEW | Approved | |
| 09/29/2016 | PGEHLEN1 | ENV SVCS | REVIEW | Passed | Review will be done by PSDS Engineering. |
| 09/29/2016 | PGEHLEN1 | UTILITIES | CENTURYLINK | Passed | No longer a review agency |
| 10/03/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Reqs Change | DATE: October 3, 2016 DUE DATE: October 12, 2016 SUBJECT: Block Plat TO: Kevin Hall, PE LOCATION: 56 E Congress Street REVIEWERS: Paul Baughman, PE, CFM ACTIVITY: S16-074 SUMMARY: Engineering Division of Planning and Development Services Department has received and reviewed the proposed Development Plan Package. The following items need to be addressed: 1) The legend shows a (C) for Calculated and (M) for measured dimension. Per AM 2-07.5.5C5 all distances and bearings between all monuments need to be indicated whether they are measured or calculated. Please update line work accordingly. 2) Per AM 2-07.5.1H please add the S16-074 to the title block areas on each sheet. 3) There is no PDSD Engineering Administrator at this time. Please change the signature line to read City Engineer under the assurance section. 4) Per AM 2-07.5.1A3 please show the railroad and Aviation Parkway on the location map. 5) There are two bearings and distances called out at the intersection of Scott Avenue and Congress Street that do not show a survey monument as a connection point. Is there a survey monument that should be called out or should a single bearing and distance be used instead? Please clarify per AM 2-07.5.5C6 6) There is extraneous line work shown just above the OCR-2 zoning designation east of the Scott Avenue right-of-way callout. Please add designator or remove extraneous callout. If you have any comments questions or wish to discuss new information, please call or email me at 520-837-5007 or paul.baughman@tucsonaz.gov. |
| 10/04/2016 | AHINES2 | OTHER AGENCIES | TUCSON AIRPORT AUTHORITY | Approv-Cond | October 4, 2016 Thank you for the opportunity to comment on S16-074, City Park; 1st Submittal, a final plat (block plat) application for an approximately 0.47 acre site located immediate south of East Congress Street and between South Stone Avenue and South Scott Avenue. The proposed land use is commercial. This site is within the Tucson International Airport avigation easement requirements and public disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace. The applicant shall file Form 7460 with the FAA. Any cranes used for the project must also be identified with Form 7460. Please file Form 7460 at https://oeaaa.faa.gov/oeaaa/external/portal.jsp. The Tucson Airport Authority conditionally approves the subject request contingent upon the following condition of approval, as noted below. This condition should be identified in the general notes of the approved development plan. Conditions of approval: "That prior to the City's approval of any construction permit for a permanent building, the property owner shall record the Avigation Easement prior to the subdivision process which discloses the existence, and operational characteristics of the Tucson International Airport to future owners or tenants of the property and further conveys the right to the public to lawfully use the airspace above the property. The content of such documents shall be according to the form and instructions provided." The current property owner or person authorized to sign on behalf of the current property owner shall complete, sign, and record the Avigation Easement. Once the Avigation Easement is recorded please send a copy of the recorded easement to Tucson Airport Authority by either email (send to srobidoux@flytucson.com) or to the mailing address provided below. Scott Robidoux Airport Planner Tucson Airport Authority 7250 South Tucson Boulevard Suite 300 Tucson, AZ 85756 Please do not hesitate to contact me if you have any questions or concerns regarding this comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-573-4811. Respectfully, Scott Robidoux, Airport Planner cc file |
| 10/04/2016 | LIZA CASTILLO | UTILITIES | TUCSON ELECTRIC POWER | Approved | Tucson Electric Power Co., (TEP) approves the Final Plat for City Park submitted on September 21, 2016. Please call the New Construction Department at 520-918-8300 to apply for service. Submit a final set of approved plans including electrical load and offsite improvement plans to determine how TEP will serve this development. If easements are required, they will be obtained by separate instrument. Contact me at 520-917-8744 should you have any questions. Thanks, Mary Burke Right of Way Agent II Tucson Electric Power Co. Mail Stop HQE613 PO Box 711, Tucson, AZ 85702 Office - 520-917-8744 Cell - 520-401-9895 mburke@tep.com |
| 10/06/2016 | JOHN BEALL | COT NON-DSD | COMMUNITY PLANNING | Approved | |
| 10/10/2016 | JOE LINVILLE | LANDSCAPE | REVIEW | Approved | |
| 10/11/2016 | TOM MARTINEZ | OTHER AGENCIES | AZ DEPT TRANSPORTATION | Approved | Regional Traffic Engineering has no comments on this submittal and supports its acceptance. The location will have no affect to any ADOT facilities because of the proposed location. Tom Martinez |
| 10/12/2016 | JIM EGAN | COT NON-DSD | FIRE | Approved | |
| 10/14/2016 | AHINES2 | ZONING-DECISION LETTER | REVIEW | Reqs Change | This review has been completed and resubmittal is required. Please resubmit the following items: 1) Two rolled sets of the plans 2) All approved documents submitted previously 3) A disk containing all items submitted 4) All items requested by review staff 5) All items needed to approve these plans |
| 10/14/2016 | ZELIN CANCHOLA | COT NON-DSD | TRAFFIC | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/17/2016 | ARUIZ1 | OUT TO CUSTOMER | Completed |