Plan Review Detail
Review Status: Completed
Review Details: MINOR SUBDIVISION REVIEW
Plan Number - S16-001
Review Name: MINOR SUBDIVISION REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2016 | AROMERO4 | START | PLANS SUBMITTED | Completed | |
| 01/12/2016 | KAY MARKS | PIMA COUNTY | ADDRESSING | Approved | The above project has been approved by Pima County Addressing 01/12/16 |
| 01/12/2016 | DAVID RIVERA | ZONING HC | REVIEW | Approved | |
| 01/12/2016 | DAVID RIVERA | ZONING | REVIEW | Approv-Cond | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: David Rivera Principal Planner PROJECT: S16-001 3700 S Calle Polar Final Plat TRANSMITTAL DATE: January 12, 2016 DUE DATE: February 2, 2016 COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Unified Development Code and Development Standards were addressed. This plan has been reviewed for compliance with the Administrative Manual Standards listed in section 2-07 of the City of Tucson Administrative Manual. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC). The review comments include the actual standard first with the applicable Administrative Manual section number and the following paragraph is the actual comment related to the specific item that must be addressed. 01. COMMENT. Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site Final Plat that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A Final Plat application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is January 6, 2017. *************************************************************** 2-07.5.1.H - The S(Year)-___ subdivision case number assigned to the approved tentative plat must be placed in the lower right corner of the plat next to the title block. If the property is subject to a rezoning case, the C9-__-__ rezoning case number is to be noted also. 02. COMMENT: The PDSD subdivision case number S16-001 has been assigned to this project. List the case number in the lower right corner of the plan sheet. 2-07.5.4.H - Show no-vehicular access easements where applicable; 03. COMMENT: If applicable draw and label the No-Vehicular Access location(s). 04. COMMENT: Approval of the tentative plat is required before final approval of the final plat can be given by zoning. If you have any questions about this transmittal, please call David Rivera, (520) 791-5608. |
| 01/12/2016 | BVIESTE1 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Approved | See additional documents in PRO. Response for S16-001 Kellie Anderson Tucson Water/New Development Administrative Assistant 520-837-2165 520-791-4718 520-791-2501 (fax) Kellie.Anderson@tucsonaz.gov |
| 01/14/2016 | BVIESTE1 | PIMA COUNTY | WASTEWATER | Reqs Change | REGIONAL WASTEWATER RECLAMATION DEPARTMENT 201 NORTH STONE AVENUE TUCSON, ARIZONA 85701-1207 JACKSON JENKINS PH: (520) 724-6500 DIRECTOR FAX: (520) 724-9365 January 14, 2016 To: Jeff Hunt, P.E. Cypress Civil Development Thru: Patricia Gehlen, CDRC Manager City of Tucson Development Services Department From: ________________________________________________ Debbie Ketchem, Civil Engineer Assistant - Sr. Development Liaison Unit Subject: Esperanza en Escalante Veterans Housing, Lots 1 and 2 Final Plat - 1st Submittal, P16WS00002 (S16-001) Response Letter Pima County Regional Wastewater Reclamation Department (RWRD) received this Final Plat and RWRD is requesting additional information for the above referenced submittal received on January 8, 2016. The following revisions are requested: 1. Provide a pdf or plans of DP15-0188 for reference. RWRD needs to confirm the point of connection for the private sewer is acceptable. 2. Final Plat must be signed by engineer of record and registered land surveyor before the Final Plat can be approved. 3. Remove from the Dedication reference to "public sewer" since the existing sewer is private and no public sewers are proposed. 4. Show the distance of 306.40' from the NE property line to the location of the existing 20' x 20' public sewer utility easement. 5. Consider adding an easement for the existing private sewer for Lot 2 because the existing private sewer will be crossing lot lines. The next submittal will be the second submittal for this Final Plat. The RWRD review fee for the second submittal will be $50.00 (Per PC Code, Title 13.20.030.A.2). Do not hesitate to contact me if you have any questions at (520) 724-6481. Cc: Lorenzo Hernandez, P.E., C.E. Manager., RWRD Francisco Galindo, P.E., RWRD |
| 01/19/2016 | ED ABRIGO | PIMA COUNTY | ASSESSOR | Reqs Change | Office of the Pima County Assessor 240 N STONE AVENUE Tucson, Arizona 85701 BILL STAPLES ASSESSOR TO: CDRC Office Subdivision Review City of Tucson (FAX# 791-5559) FROM: Julieann Arechederra GIS Cartographer Pima County Assessor's Office DATE: January 19, 2016 RE: Assessor's Review and Comments Regarding: S16-001 FINAL PLAT FOR ESPERANZA EN ESCALANTE VETERANS HOUSING * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * Plat meets Assessor's Office requirements. ___X___ Plat does not meet Assessor's Office requirements. COMMENTS: " THERE MUST BE A SECTION TIE, WITH A BEARING AND DIMENSION FROM THE SECTION CORNER OR QUARTER CORNER TO THE POINT OF TIE ON THE SUBDIVISION. NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED. |
| 01/21/2016 | JIM EGAN | COT NON-DSD | FIRE | Approved | |
| 01/21/2016 | TOM MARTINEZ | OTHER AGENCIES | AZ DEPT TRANSPORTATION | Approved | Regional Traffic Engineering has no comments on this submittal and supports its acceptance. The development will have no affects on any ADOT facilities due to its location. Thank you. |
| 01/22/2016 | ROBERT SHERRY | PLUMBING-RESIDENTIAL | REVIEW | Passed | |
| 01/28/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 01/28/2016 | JOE LINVILLE | LANDSCAPE | REVIEW | Approved | |
| 01/29/2016 | PGEHLEN1 | UTILITIES | SOUTHWEST GAS | Approved | see informational comments in PRO/SIRE |
| 02/02/2016 | LIZA CASTILLO | UTILITIES | TUCSON ELECTRIC POWER | Reqs Change | SUBJECT: ESPERANZA EN ESCALANTE – MINOR SUBDIVISION S16-001 Tucson Electric Power Co., (TEP) has reviewed the final plat for Esperanza En Escalante submitted January 11, 2016, and is unable to approve the plat at this time. The plat indicates that a portion of an existing 15’ Public Electric Easement per Dkt 10104, Pg 1504 will be released per the plat. There are existing TEP facilities within the portion of the easement shown for abandonment. These facilities serve the development on Lot 1. Developer must provide new easements for existing equipment in order for TEP to release the old easement. In the event that the equipment is to removed or relocated, all costs will be borne by the developer. Please note that a utility easement may not be released by the platting process, it must be released or quit claimed by the utiltity(ies) occupying the easement. If you have any questions, please contact me at 520-917-8744. Thank you, Mary Burke Right of Way Agent Tucson Electric Power Co. Mail Stop HQE613 PO Box 711, Tucson, AZ 85702 Office - 520-917-8744 Cell - 520-401-9895 mburke@tep.com |
| 02/03/2016 | PGEHLEN1 | COT NON-DSD | TUCSON POLICE DEPARTMENT | Approved | I have no issues with this review. Thank you, Kara Curtis Community Service Officer Tucson Police Department Operations Division Midtown 1100 S. Alvernon Tucson, AZ 85711 kara.curtis@tucsonaz.gov (520) 837-7428 |
| 02/03/2016 | PGEHLEN1 | OTHER AGENCIES | PIMA ASSN OF GOVTS | Approved | See additional documents in PRO/SIRE No objections/adverse comments. See attached. -------------------------------------------------------------------------------- Disclaimer: This report and/or data was funded in part through grant[s] from the Federal Highway Administration and/or Federal Transit Administration, U.S. Department of Transportation. The contents of this report and/or data reflect the views and opinions of the author(s) who is responsible for the facts and accuracy of the data presented herein. The contents do not necessarily state or reflect the official views or policies of the U.S. Department of Transportation, the Arizona Department of Transportation, or any other State or Federal Agency. This report and/or data does not constitute a standard, specification or regulation. The information in this publication is provided on an “as is” basis, and there are no warranties, express or implied, including, but not limited to, any warranties of merchantability or fitness for a particular purpose. In no event shall PAG be liable for any damages resulting from the use of the information. PAG provides the information in good faith and has endeavored to create and maintain accurate data. The users of this report and/or data are advised to use the information with caution and to independently verify accuracy. ____________________________ Eric W. Kramer, Ph.D., AICP Senior Land-Use Modeler |
| 02/05/2016 | PGEHLEN1 | UTILITIES | EL PASO NATURAL GAS | Passed | |
| 02/05/2016 | JOSE ORTIZ | COT NON-DSD | TRAFFIC | Approved | |
| 02/05/2016 | PGEHLEN1 | UTILITIES | CENTURYLINK | Passed | |
| 02/05/2016 | ROBERT YOUNG | PIMA COUNTY | PIMA CTY - DEV REVIEW | Passed | |
| 02/05/2016 | PGEHLEN1 | OTHER AGENCIES | TUCSON AIRPORT AUTHORITY | Passed | |
| 02/05/2016 | PGEHLEN1 | OTHER AGENCIES | U. S. POST OFFICE | Passed | |
| 02/08/2016 | JANE DUARTE | COT NON-DSD | PARKS & RECREATION | Approved | No planned or existing Tucson Parks and Recreation facilities are affected by this Minor Subdivision. Howard B. Dutt, RLA Landscape Architect Tucson Parks & Recreation (520) 837-8040 Howard.Dutt@tucsonaz.gov >>> DSD_CDRC 2/5/2016 3:49 PM >>> Comments were due yesterday. Thanks Trish >>> DSD_CDRC 01/11/2016 1:51 PM >>> Dear Reviewers: This is an electronic distribution for a CDRC Final Plat (Minor Subdivisoin) review. If you normally receive paper copies of the review documents, you will receive them soon. The applicable case numbers are: CDRC Development Plan: S16-001 Existing and Proposed Zoning: RX-1 |
| 02/09/2016 | JOHN BEALL | COT NON-DSD | COMMUNITY PLANNING | Approved | COMMENTS Site in compliance with Plan Tucson and South Pantano Area Plan, as outlined below: The proposed residential development is located within an "Existing Neighborhoods," area as identified by Plan Tucson. An Existing Neighborhoods category is primarily developed and largely built-out neighborhoods and commercial districts in which minimal new development and redevelopment is expected. The goal is to maintain the character of these neighborhoods, while accommodating some new development and redevelopment and encouraging reinvestment and new services and amenities that contribute further to neighborhood stability. In particular to housing, Plan Tucson provides direction and support in Chapter 3 - The Social Environment, under housing policies H8 and H9 which state housing facilities to promote safe, decent, and affordable housing and neighborhoods that support aging in place and is to address the housing needs of the most vulnerable populations in the community, including those at risk of homelessness. Providing a variety of housing for all segments of the population is the key. The South Pantano Area Plan (SPAP) encourages the development of a variety of housing types and the compatibly of new development with existing land uses. The SPAP residential sub-goal directs new development to encourage the development of a variety of housing types including single-family detached units, duplexes, apartments, condominiums, townhouses, and mobile homes. This development should preserve the integrity of established neighborhoods, promote infill of vacant land where adequate streets and utilities are available, and ensure the compatibility of new residential development with existing land uses. Site is in compliance with Plan Tucson and South Pantano Area Plan. A Minor Change of Conditions to SE-03-08 Esperanza en Escalante Veteran's Housing special exception on November 2, 2015. The formal request is to remove condition #10, which states, a southbound right turn lane shall be constructed at the access point to the site, from the development conditions. |
| 02/10/2016 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Reqs Change | This review has been completed and resubmittal is required. Please resubmit the following items: 1) 4 rolled sets of the plans 2) a disk containing all items submitted 3) All items requested by review staff 4) All items needed to approve these plans |
| 02/10/2016 | PGEHLEN1 | ENV SVCS | REVIEW | Approved | Trish, I am sorry about putting the wrong Activity Number on my review comments for the Esperanza En Escalante plat review. The correct Activity Number for this project is "S16-001". This e-mail is to confirm that the City of Tucson - Environmental Services Department approves Activity Number S16-001. Thomas G. Ryan, P.E. Environmental Services Department |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/08/2016 | AROMERO4 | OUT TO CUSTOMER | Completed |