Plan Number: S15-012
Parcel: Unknown

Review Status: Completed

Review Details: FINAL PLAT - REVIEW

Plan Number - S15-012
Review Name: FINAL PLAT - REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2015 AROMERO4 START PLANS SUBMITTED Completed
04/03/2015 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved letter provided for Tentative plat still valid
04/07/2015 PGEHLEN1 UTILITIES SOUTHWEST GAS Approved See additional documents in PRO

April 7, 2015


City of Tucson CDRC
Attn: Patricia Gehlen, Manager
201 N. Stone Avenue
Tucson, AZ 85701

RE: SWG Plan Review for Iskra Fields, Lots 1 - 4 / Final Plat
CDRC No. S15-012

Southwest Gas Corporation (SWG) has no objection to the development of the above-mentioned project. Existing natural gas facilities are located within the area of development and may be affected by construction of this project; specifically, a gas service is located near the south east corner of the proposed development serving the existing address of 2225 East Fort Lowell Road. Additionally, a gas main is located within the right-of-way of Fort Lowell Road for future extension into the proposed development.

Blue Stake and potholing are suggested for best accuracy when locating SWG facilities. Please be aware that SWG requires a minimum one-foot separation from distribution facilities and any proposed structures and two-foot separation from high pressure gas facilities. SWG requests the contractor use caution when working in the vicinity of gas facilities and protect and support gas facilities per Blue Stake requirements.

All information is provided for reference use only. Please note that it is the responsibility of excavators or those developers planning excavation to verify actual field conditions in advance of construction so that requests for gas service or any potential issues can be addressed in a timely manner.

Please include SWG in all future plat and development plan submittals of this project. If you have any questions or require any additional information, please contact me at (520) 794-6218 or TUCSWGDevReview@swgas.com.


Sincerely,



Arthur Lason
Engineering Technician /Southern Arizona Division
Enc: SWG Contact Information (pdf)
04/07/2015 ED ABRIGO PIMA COUNTY ASSESSOR Reqs Change Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)


FROM: Ada Griffin
GIS Cartographer
Pima County Assessor's Office


DATE: April 7, 2015


RE: Assessor's Review and Comments Regarding:

S15-012 FINAL-PLAT-FOR-ISKRA-FIELDS

_

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Plat meets Assessor's Office requirements.
___X____ Plat does not meet Assessor's Office requirements.

COMMENTS:



" THERE MUST BE A SECTION TIE, WITH A BEARING AND DIMENSION FROM THE SECTION CORNER OR QUARTER CORNER TO THE POINT OF TIE ON THE SUBDIVISION.

" ALL ADJACENT SUBDIVISIONS SHOULD BE NAMED, WITH MAP AND PLAT IN THE APPROPRIATE AREAS AROUND THE SUBDIVISION.



NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.
04/09/2015 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved From: MBurke@tep.com [MBurke@tep.com]
Sent: Thursday, April 09, 2015 3:27 PM
To: DSD_CDRC.DSPO2.CHDOM2@tucsonaz.gov
Cc: kperry@perryengineering.net
Subject: S15-012 - Iskra Fields Final Plat


SUBJECT: ISKRA FIELDS LOTS 1-4 FINAL PLAT
S15-012


Tucson Electric Power Co. (TEP) has reviewed and approves the final plat for Iskra Fields, Lots 1-4. Electric service will be provided to this subdivision in accordance with the rules and regulations approved by the Arizona Corporation Commission.


Please contact me at (520) 917-8744 if you have any questions.


Thank you,


Mary Burke
Right of Way Agent
Tucson Electric Power Co.
Mail Stop HQW603
PO Box 711, Tucson, AZ 85702
Office - 520-917-8744
Cell - 520-401-9895
mburke@tep.com
04/09/2015 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Approv-Cond 201 N. STONE AV, 1ST FL
TUCSON, AZ 85701-1207


ROBIN FREIMAN
ADDRESSING REVIEW
PH #: 721-9512



TO: CITY PLANNING
FROM: ROBIN FREIMAN, ADDRESSING REVIEW
SUBJECT: S15-012 FINAL PLAT FOR ISKRA FIELDS, LOTS 1-4
DATE: April 9, 2015



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.


1.) Please label with project number S15-012
2.) Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar of approved Final Plat to City Planning

***PIMA COUNTY ADDRESSING MUST RECEIVE A COPY OF THE RECORDED FINAL PLAT PRIOR TO THE ASSIGNMENT OF ANY ADDRESSES. PLEASE COORDINATE THE DELIVERY AND RECORDATION OF THE MYLAR WITH THE CITY OF TUCSON PLANNING***

3.) All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.


***The Pima County Addressing Section can use digital CAD drawing files.
These CAD files can be e-mailed to: CADsubmittals@pima.gov
The digital CAD drawing files expedite the addressing and permitting processes when we are able to insert this digital data into the County's Geographic Information System. Your support is greatly appreciated.***
04/10/2015 PGEHLEN1 PIMA COUNTY WASTEWATER Reqs Change REGIONAL WASTEWATER RECLAMATION DEPARTMENT
201 NORTH STONE AVENUE
TUCSON, ARIZONA 85701-1207
JACKSON JENKINS PH: (520) 724-6500
DIRECTOR FAX: (520) 724-9365
April 10, 2015


To: Ken Perry, P.E.

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department
From: Francisco Galindo, P.E.
Civil Engineer, Development Liaison Unit
Subject: Iskra Fields, Lots 1-4
Final Plat - 1st Submittal, S15-012, Review Comment Letter

The Final Plat for the proposed project has been reviewed on behalf of Pima County Regional Wastewater Reclamation Department (PCRWRD).
RWRD is requesting additional information for the above referenced submittal of the Final Plat as received on April 4, 2015. The following revisions are requested:

1. Will the sewer serving the property be public or private within the right-of-way? If it is public, where will the upstream manhole from the point of connection be, within the right- of-way or inside the property? If inside the property a public sewer easement is required.

2. The Plat Dedication shall include language regarding the grantees and purpose of the easement.

The next submittal will be the second submittal for this Final Plat. The RWRD review fee for the second submittal will be $50.00 (Per PC Code, Title 13.20.030.A.2). Do not hesitate to contact me at (520) 724-6733 if you have any questions.
Do not hesitate to contact me if you have any questions at (520) 724-6733.



Francisco Galindo, P.E. Civil Engineer
Development Liaison Unit


Cc: Lorenzo Hernandez, P.E., C.E. Manager., RWRD
Chad Amateau, P.E., RWRD
Debbie Ketchem, CEA - Sr., RWRD
Project file
04/21/2015 MICHAEL ST. PAUL ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Michael St Paul
Planning Technician

PROJECT: S15-012
2225 East Fort Lowell Road
Final Plat (R-1 zone)

TRANSMITTAL DATE: April 22, 2015

DUE DATE: May 1, 2015


COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Unified Development Code, The Administrative and Technical Manuals were addressed.

This plan has been reviewed for compliance with the Subdivision Plat standards listed in section 2-07 of the City of Tucson Administrative Manual. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC).

The review comments include the actual standard first with the applicable Administrative Manual section number and the following paragraph is the actual comment related to the specific item that must be addressed. If you need to review the sections listed below click on the link or copy it in the address bar of your internet program. http://www.amlegal.com/nxt/gateway.dll/Arizona/tucson_az_udc/technicalstandardsmanual?f=templates$fn=default.htm$3.0$vid=amlegal:tucson_udc_az


SECTION 2-07.0.0: FINAL PLAT, BLOCK PLAT, MINOR SUBDIVISION, AND CONDOMINIUM PLAT APPLICATIONS
Section

2-07.1.0 APPLICABILITY

2-07.2.0 APPLICATION SUBMITTAL REQUIREMENTS

2-07.3.0 SUBMITTAL TIMING

2-07.4.0 FORMAT REQUIREMENTS

2-07.5.0 CONTENT REQUIREMENTS

2-07.6.0 APPROVAL DOCUMENTS AND PROCEDURE


2-07.1.0 APPLICABILITY

Final plats, block plats, minor subdivisions, and condominium plats shall be prepared according to the requirements provided below. Hereafter referred to as "plat" or "plats."

A final plat serves as a survey document suitable for recordation of all or part of an approved tentative plat, if applicable. The final plat must conform to the approved tentative plat or site plan in lot configuration, design, and required conditions of development. The final plat, once approved, is recorded in the Pima County Recorder's Office. The final plat is kept on file and becomes part of the permanent record for the subject site.

(Am. Admin. Directive, 5/14/2013)


2-07.2.0 APPLICATION SUBMITTAL REQUIREMENTS

Plat application packets are available from the PDSD Department. Completed applications and accompanying materials are submitted to the PDSD. Incomplete or inaccurate applications will not be accepted, nor will any application in which the pre-application conference or neighborhood meeting requirements have not been met. Should an incomplete submittal be accepted for review, the applicant should be aware that, because of a lack of information, the review will take longer since comments cannot be finalized until after the resubmittal when the required information is provided. The types of documents and the specific number of copies required of each of the documents are on the PDSD website or may be obtained from the CDRC office.

The following documents and information shall be submitted upon application:

2.1 Application Form

A completed application signed by the property owner or authorized designee;

2.2 Plat

A plat must be prepared to the format and content requirements described herein; and,

2.3 Fees

Fees in accordance with Section 4-01.0.0, Development Review Fee Schedule.


2-07.3.0 SUBITTAL TIMING

Review of final plats is normally initiated after the tentative plat has been approved, unless concurrent tentative and final plat submittal has been approved by the PDSD prior to submittal. Final plats may also be submitted for review prior to the approval of a tentative if a minimum of one review of the tentative plat have occurred. In any case, submittal of the final plat prior to approval of the tentative plat is done at the applicant's risk since changes could be required of the tentative that may affect the final plat.


2-07.4.0 FORMAT REQUIREMENTS


H. The S(Year)-___ subdivision case number assigned to the approved tentative plat must be placed in the lower right corner of the plat next to the title block. If the property is subject to a rezoning case, the C9-__-__ rezoning case number is to be noted also.

COMMENT: Place the subdivision number (S15-012) on all sheet of the tentative and final plat.
04/22/2015 JASON GREEN ENGINEERING REVIEW Reqs Change DATE: April 22, 2015
DUE SATE: May 01, 2015
SUBJECT: Iskra Fields Final Plat Submittal- Engineering Review
TO: Patricia Gehlen, CDRC Manager
LOCATION: 2225 E Fort Lowell Rd, T13S R14E Sec29
REVIEWER: Jason Green, CFM
ACTIVITY: S15-012

SUMMARY: Engineering Division of Planning and Development Services Department has received and reviewed the proposed Final Plat, Title Report and Declaration of Easements. Engineering Division has reviewed the submitted Final Plat and does not recommend approval at this time. Refer to this link for further clarification:
http://www.amlegal.com/nxt/gateway.dll/Arizona/tucson_az_udc/administrativemanual?f=templates$fn=default.htm$3.0$vid=amlegal:tucson_udc_az

The following items need to be addressed:

FINAL PLAT COMMENTS:

1) AM Sec.2-07.5.1.H: Revise the Final Plat to place the assigned subdivision case number "S15-012" in the lower right corner of the plat next to the Title Block on all sheets.

2) AM Sec.2-07.5.3.B.2: Revise the Final Plat to include all Dedication paragraphs that are applicable to the final plat. Refer to the referenced section and provide one of the following four statements as may be appropriate foe the plat.

3) AM Sec.2-07.5.6: A signed and original notarized copy of the Declaration of Easements will be required prior to Final Plat Mylar approval. The easement needs to be recorded and the recordation information provided along with the list of Exhibits as called out on Sheet 10.

4) AM Sec.2-07.6.1.B: The final plat cannot be scheduled for Mayor and Council consideration until either Financial Assurances are submitted or a copy of a performance bond for the project is submitted and approved.

5) AM Sec.2-07.6.1.E: Submit two copies of an updated title report (current within 30 days) at Mylar submittal. A statement from the title company certifying the title report previously submitted is still valid is acceptable in place of an additional title report. The Title Report submitted has an effective date of July 1, 2014 which does not meet the 30 day requirement.


GENERAL COMMENTS:

Provide a revised Final Plat, recorded easement, and Financial Assurances at re-submittal addressing the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

For questions or to schedule a meeting I can be reached at 837-4929.

Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Planning & Development Services
04/23/2015 PGEHLEN1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Passed
04/23/2015 PGEHLEN1 UTILITIES CENTURYLINK Passed
04/23/2015 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Reqs Change This review has been completed and resubmittal is required. Please resubmit the following items:

) Twor rolled sets of the plans
2) A disk containing all items submitted
3) All items requested by review staff
4) All items needed to approve this plan

Final Status

Task End Date Reviewer's Name Type of Review Description
07/09/2015 KROBLES1 OUT TO CUSTOMER Completed