Plan Number: S14-040
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - FINAL PLAT - CONDO CONVERSION

Plan Number - S14-040
Review Name: RESUBMITTAL - FINAL PLAT - CONDO CONVERSION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2014 PGEHLEN1 START PLANS SUBMITTED Completed
09/17/2014 PGEHLEN1 UTILITIES SOUTHWEST GAS Approv-Cond See letters in PRO
09/17/2014 PGEHLEN1 OTHER AGENCIES PIMA ASSN OF GOVTS Passed
09/17/2014 PGEHLEN1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Reqs Change September 16, 2014

Ms. Gehlen:

Thank you for the opportunity to comment on S14-040. As I understand, this project involves parcel subdivision for the purpose of providing office condominiums. The property is located on the north side of Valencia Road and west of I-19.

This site is within the Tucson International Airport public disclosure area and traffic pattern airspace. The site is not within the City of Tucson Airport Environs Zone.

The Tucson Airport Authority requests that the following condition be placed upon the permit prior to issuance of any construction permits:

"That prior to the City's approval of any construction permit for the property owner shall record the Airport Disclosure Statement form that discloses the existence, and operational characteristics of the Tucson International Airport to future owners or tenants of the property and further conveys the right to the public to lawfully use the airspace above the property. The content of such documents shall be according to the form and instructions provided."

The intent of this condition is for the Airport Disclosure Statement form to be recorded for the properties within the final plat boundaries.

The Tucson Airport Authority asks that the property owner forward a copy of the recorded Airport Disclosure Statement form prior to issuance of a Certificate of Occupancy (C of O) to:

Tom Coyle, AICP
Director of Planning
Tucson Airport Authority
7005 S. Plumer
Tucson, AZ 85756

Thank you for the opportunity to comment on the subject application and the City of Tucson's recognition of the regional importance in ensuring continuing safety and viability of Tucson International Airport.

Best,



Tom Coyle, AICP
Director of Planning

See additional documents in PRO
09/18/2014 PGEHLEN1 PIMA COUNTY ADDRESSING Reqs Change 201 N. STONE AV, 1ST FL
TUCSON, AZ 85701-1207

ROBIN FREIMAN
ADDRESSING REVIEW
PH #: 724-9512

TO: CITY PLANNING
FROM: ROBIN FREIMAN, ADDRESSING REVIEW
SUBJECT: S14-040 FINAL PLAT FOR MIDVALE PARK II MEDICAL-DENTAL PLAZA TOWNOFFICES, 1ST REVIEW
DATE: 09/18/2014



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

1. Label Project Number S14-040 on sheets 1 and 2.

2. Sheet 1, General Notes #15C, Please reference first page of the right of way acquisition document, Docket 13009 Page 1627.

3. Sheet 1, Map References (R2), MIDVALE PARK HEALTH SERVICE CAMPUS LOT 1 THROUGH 6 AND BLOCK A, BOOK 38 MAPS AND PLATS, PAGE 35. The number of lots shown on the reference is incorrect.

4. Sheet 2, Please reference first page of the right of way acquisition document, Docket 13009 Page 1627.

5. Please show COMMERCE COURT as (PUBLIC).
09/22/2014 ED ABRIGO PIMA COUNTY ASSESSOR Reqs Change Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)


FROM: Julieann Arechederra
GIS Cartographer
Pima County Assessor's Office


DATE: September 19, 2014


RE: Assessor's Review and Comments Regarding:


* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Plat meets Assessor's Office requirements.
___X____ Plat does not meet Assessor's Office requirements.

COMMENTS:




" ALL HATCHING, STIPPLING, STRIPING ETC., MUST BE REMOVED IN THE FINAL PLAT, UNLESS ANOTHER AGENCY REQUIRES IT. IF SO ALL LETTERING MUST HAVE THE HATCHING, ETC., CUT AWAY SO THEY ARE LEGIBLE.



NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.
09/24/2014 DAVID RIVERA ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: David Rivera
Principal Planner

PROJECT: S14-040
Midvale Park II Medical Dental Offices TownOffices - Condominiums - Units one and Two and Common Elements "A" and "B" Final Plat

TRANSMITTAL DATE: September 26, 2014

DUE DATE: October 10, 2014

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Unified Development Code and Development Standards were addressed.

This plan has been reviewed for compliance with the Administrative Manual Standards listed in section 2-07 of the City of Tucson Administrative Manual. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC).

The review comments include the actual standard first with the applicable Administrative Manual section number and the following paragraph is the actual comment related to the specific item that must be addressed.

1. Section 3.3.3.G.5.c UDC, An applicant has one year from the date of application to obtain approval of a site Final Plat that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A Final Plat application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One year Expiration date is .

SECTION 2-07: FINAL PLAT / MNOR SUBDIVISION
Section

2-07.5.1.A.3 - Subdivisions, arterial and collector streets, major watercourses, and railroads within the one-mile area; and,
01. COMMENT: Correct the street name Calle Cruz River to Calle Santa Cruz on the location.

******************************************************************************************
2-07.5.1.F - Orient the subdivision drawing with north toward the top of the page, when possible. Place a north arrow on each sheet in the upper right corner with the scale of the drawing beneath the arrow. All lettering, dimensions, etc., must be oriented to the north. If it is not practical to orient north to the top of the sheet, the plan drawing shall be oriented with north to the left side of the sheet.
02. COMMENT: Rotate the drawing so that the north is pointed towards the left hand side of the sheet as noted by the last sentence of the standard above.

******************************************************************************************

2-07.5.1.H - The S(Year)-___ subdivision case number assigned to the approved tentative plat must be placed in the lower right corner of the plat next to the title block. If the property is subject to a rezoning case, the C9-__-__ rezoning case number is to be noted also.
03. COMMENT: This Project has been assigned the PDSD Case number S14-040. List the case number in the lower right corner of all plan sheets.

******************************************************************************************

2-07.5.4.B - Identify each block or lot within the subdivision boundary by number, and include the square footage of each;
04. COMMENT: Remove the line work that represents the old lot lines pre the previous plat. Clarify what the label Sequence # within the footprint of Unit 1 is for.

******************************************************************************************

2-07.5.4.H - Show no-vehicular access easements where applicable;
05. COMMENT: If there is requirement for no-vehicular access easements along the boundary of the subdivision draw, label and dimension the locations.

******************************************************************************************

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package site plan and any requested documents.
09/24/2014 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
PO Box 711, Tucson, AZ 85702


WR#282711 September 24, 2014


Dowl HKM
Attn: M. York
406 N. Church Ave
Tucson, AZ 85701

Dear Mr. York:

SUBJECT: Midvale Plaza Park II Condos
S14-040

Tucson Electric Power Company has reviewed and has approved the development plan submitted September 19, 2014. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development.


Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans.

If easements are required, they will be secured by separate instrument. Your final plans should be sent to:
Tucson Electric Power Company
Attn: Mr. Richard Harrington
New Business Project Manager
P. O. Box 711 (OH204)
Tucson, AZ 85702
520-917-8726

Should you have any technical questions, please call the area Designer Jennifer Necas at (520) 918-8295.

Sincerely,

Jeffery Shea
Admin Support Specialist
Design/Build


cc: DSD_CDRC@tucsonaz.gov, City of Tucson (email)
J. Necas, Tucson Electric Power
09/30/2014 PGEHLEN1 PIMA COUNTY WASTEWATER Reqs Change Review and approval by RWRD is required prior to Mayor and Council approval.
10/07/2014 MARTIN BROWN COT NON-DSD FIRE Approved
10/13/2014 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved See letter in SIRE
10/13/2014 LOREN MAKUS ENGINEERING REVIEW Denied Clarify the ownership of the common areas under the existing plat. It seems that owners of all the property in the underlying subdivision must consent to the change in status from common area to common elements.
10/13/2014 PGEHLEN1 UTILITIES CENTURYLINK Passed
10/14/2014 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Reqs Change This review has been completed and resubmittal is required. Please resubmit the following items:

1) Two rolled sets of the plans
2) A disk containing all items submitted
3) All items requested by review staff
4) All items needed to approve this plan
10/14/2014 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/28/2016 KROBLES1 OUT TO CUSTOMER Completed