Review Status: Completed

Review Details: MINOR SUBDIVISION REVIEW

Plan Number - S14-001
Review Name: MINOR SUBDIVISION REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2014 CPIERCE1 START PLANS SUBMITTED Completed
01/15/2014 ROBERT SHERRY PLUMBING-RESIDENTIAL REVIEW Passed
01/16/2014 PGEHLEN1 UTILITIES SOUTHWEST GAS Approved See letters in SIRE for informational letter.
01/16/2014 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved See letter in SIRE
01/16/2014 STEVE SHIELDS ZONING REVIEW Reqs Change CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: 4056 East Glenn
Final Plat (1st Review)
S14-001

TRANSMITTAL DATE: January 17, 2014

DUE DATE: January 29, 2014

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

The review comments include the actual standard first with the applicable Administrative Manual section number and the following paragraph is the actual comment related to the specific item that must be addressed. If you need to review the sections listed below click on the link or copy it in the address bar of your internet program. http://www.amlegal.com/nxt/gateway.dll/Arizona/tucson_az_udc/administrativemanual?f=templates$fn=default.htm$3.0$vid=amlegal:tucson_udc_az

This link will take you directly to the section used for the standards review. The UDC & TSM requirements are in the Unified Development Code and can be viewed at the same web link as above

1. UDC Section 8.5.2.A, Final Plat Approval Period. A final plat shall be approved and recorded within three years of the tentative plat approval date. A final plat is subject only to the ordinances in effect at the time of the tentative plat application except where an ordinance specifically states that it applies to pending applications.

SECTION 2-07.0.0: FINAL PLAT, BLOCK PLAT, MINOR SUBDIVISION, AND CONDOMINIUM PLAT APPLICATIONS

2-07.5.1.H The S(Year)-___ subdivision case number assigned to the approved tentative plat must be placed in the lower right corner of the plat next to the title block. If the property is subject to a rezoning case, the C9-__-__ rezoning case number is to be noted also.

1. COMMENT: Place the subdivision case number, S14-001. in the lower right corner of the plat next to the title block.

2-07.5.3.D Approval and Recording Data Blocks. The APPROVAL paragraph, where the City Clerk certifies that the plat has been approved by Mayor and Council, and the RECORDING DATA paragraph, which provides space for the recording information, must be placed on the first sheet of the plat adjacent to each other. The paragraphs are as follows.

2. COMMENT: Review AM 2-07.5.3.D Approval and Recording Data Blocks and provide the correct approval and recording block.

2-07.5.4.D Provide location, dimensions, areas in square footage, and purposes of lots proposed for dedication (such as open spaces, recreation areas, and natural areas) or for reservation for a public use (such as public parks, water facilities, and school sites);

3. COMMENT: There is a dedication proposed of future right-of-way (ROW) along Glenn Street shown on the plan. For your information this dedication is not required at this time.

4. COMMENT: The future ROW shown on the plat is not correct. Future ROW for Glenn is 64' not 62' as shown on the plan.

ADDITIONAL COMMENTS

5. COMMENT: Individual plot plans will be required for all lots at the time of development.

6. COMMENT: Zoning recommends that you contact Tucson Water and show them the proposed subdivision. It appears you may have issues with water service for lots 3 & 4.

These comments are for the provided 'SITE PLAN EXHIBIT":

1. COMMENT: Provide a lot coverage calculation for lot 1 as it is the only lot with existing development.

2. COMMENT: Based on the most current aerial photos there appears to be detached accessory structures on the existing parcel that appear to conflict with propose lot lines. Demo permits for these structures will be required prior to approval of the plat.

3. COMMENT: Once addresses have been assigned for each individual lot a residential plot plan for lot 1 will be required to be submitted for approval.

4. COMMENT: As Glenn is an MS&R lots 1 & 2 vehicle maneuvering must be accomplished on site. Vehicles will not be allowed to back out into Glenn.

If you have any questions about this transmittal, please Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised final plat and site plan exhibit.

.
01/21/2014 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: 4056 E. GLENN FINAL PLAT
S14-001

Tucson Electric Power Co. (TEP) has reviewed and approves the Final Plat submitted for review on January 15, 2014. Additional easements that TEP may require in order to provide electrical service to Lots 1-5 must be secured by separate instrument before facilities will be installed.

If you have any questions, please feel free to contact me at 917-8744.

Thank you,

Mary Burke
Right of Way Agent
Tucson Electric Power Co.
Mail Stop HQW603
PO Box 711, Tucson, AZ 85702
Office - 520-917-8744
Cell - 520-401-9895
mburke@tep.com<mailto:mburke@tep.com>
01/21/2014 RONALD BROWN ZONING HC REVIEW Approved
01/21/2014 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved Regional Traffic Engineering has no comments on this submittal and supports its acceptance. Thank you.

________________________________
01/21/2014 PGEHLEN1 OTHER AGENCIES PIMA ASSN OF GOVTS Approved No objections/adverse comments. See attached.



____________________________

Eric W. Kramer, Ph.D., AICP

Senior Land-Use Modeler



PAG40MPOhoriz3.png



177 N. Church Ave, Suite 405

Tucson, AZ 85701

(520) 792-1093 x506 (tel)

(520) 620-6981 (fax)

www.pagnet.org

<mailto:ekramer@pagnet.org> ekramer@pagnet.org






See documents in SIRE
01/22/2014 JASON GREEN ENGINEERING REVIEW Reqs Change DATE: January 23, 2014
SUBJECT: 4056 E Glenn Minor Subdivision Final Plat Submittal- Engineering Review
TO: Patricia Gehlen, CDRC Manager
LOCATION: 4056 E Glenn Street, T13S R14E Sec34 Ward 6
REVIEWER: Jason Green, CFM
ACTIVITY: S14-001


SUMMARY: Engineering Division of Planning and Development Services Department has received the proposed Final Plat. Engineering Division has reviewed the submitted Final Plat and does not recommend approval at this time. Refer to this link for further clarification:
http://www.amlegal.com/nxt/gateway.dll/Arizona/tucson_az_udc/administrativemanual?f=templates$fn=default.htm$3.0$vid=amlegal:tucson_udc_az

The following items need to be addressed:


FINAL PLAT COMMENTS:

1) AM Sec.2-07.5.1.H: Revise the Final Plat to place the assigned subdivision case number "S14-001" in the lower right corner of the plat next to the Title Block.

2) AM Sec.2-07.5.2.E: Revise the Final Plat to include the following note per the referenced standard; "Prior to issuance of any building permit, a Floodplain Use Permit and Elevation Certificates are required for all Lots. The minimum FFE Elevations for each Lot is 1.07 feet from highest adjacent grade per the submitted Drainage Statement prepared by Cypress Civil Development dated 21DEC13."

3) AM Sec.2-07.5.3.D: Revise the Final Plat and Approval/Recording Data paragraphs to read per the referenced section;

"I, (fill in name of current City Clerk), Clerk of the City of Tucson, Arizona, hereby certify that this plat was approved by the Mayor and Council of the City of Tucson, Arizona, on this ____ day of __________, 20__."
_________________________ ______________
Clerk, City of Tucson Date

Sequence________________
Fee_____________________
State of Arizona
County of Pima
I hereby certify that the instrument
was filed for record at the request
Of__________________________
Date________________________
Time_________________________
Witness my hand and Official Seal
day and year above written.
F. ANN RODRIGUEZ, County Recorder
BY___________________________
Deputy

4) AM Sec.2-07.5.4.D: Revise the Minor Subdivision Final Plat to correctly show the future right-of-way area as 64-feet or at a minimum the future half right-of-way as 32-feet due to the proposed dedication. Verify with TDOT Permits and Codes if future street dedication is required at this time along Glenn Street as shown on the plan.

5) AM Sec.2-07.5.5.C.5: Revise the Final Plat to clearly indicate whether the distance and bearings between monuments were measured or calculated for all property line boundary information. This can be labeled in plan view are as a note within the General Note Section or Legend.

6) AM Sec.2-07.6.1.B: The final plat cannot be scheduled for Mayor and Council consideration until either Financial Assurances are submitted or a copy of a performance bond for the project is submitted. The final plat cannot be scheduled for Mayor and Council consideration until Financial Assurances are submitted and approved. Specifically for the required improvements within the right-of-way.

7) AM Sec.2-07.6.1.E: Submit two copies of an updated title report (current within 30 days) at Mylar submittal. A statement from the title company certifying the title report previously submitted is still valid is acceptable in place of an additional title report. The Title Report submitted has an effective date of December 9, 2013 which does not meet the 30 day requirement.

8) UDC Sec.8.4.3.B.4: The development will be required to install sidewalk along the entire street frontage of both public roadways since both streets are fully constructed and have existing curbing. A Financial Assurance Package will be required to ensure that the construction of the sidewalk has been completed and the burden is not placed upon each future individual lot owners. Provide written approval from City of Tucson Transportation Permits and Codes Section if they will allow the sidewalk to be constructed at a later date or if Glenn Street already has a future road widening plan in place to avoid conflicts.


SITE PLAN EXHIBIT:

1) AM Sec.2-06.4.9.H.1: Label and dimension the vehicle maneuvering for both Lots 1 and 2 that must be accomplished on site since Glenn Street is a MS&R Street. Vehicles will not be allowed to back out into Glenn Street, verify.

2) AM Sec.2-06.4.9.H.1: Label and dimension the existing and/or new driveway access points and curb cuts to ensure compliance with Chapter 25 of the Tucson Code, the Tucson Access Management Guidelines for MS&R Streets and TSM Sec.10-01 for construction purposes. Verify minimum/maximum curb cut widths and minimum curb return radii for all driveway locations.

3) AM Sec.2-06.4.9.H.2: Label and dimension the existing and/or future sight visibility triangles for the street intersection and for the proposed driveway access points onto each street.

4) AM Sec.2-06.4.9.N.6: Revise the site plan exhibit to label the minimum FFE Elevations for all proposed buildings on site and for any buildings that are to be constructed in the future. Or provide a note stating the requirements of the Final Plat as stated above.

5) AM Sec.2-06.4.9.S: Fully label and dimension the sidewalk within the public right-of-way of both roadways. Verify that the existing and/or future right-of-way and sidewalk area are correctly dimensioned for Glenn Street.

6) AM Sec.2-06.4.9.T: Verify or provide approval from Environmental Services for future refuse pick up. Specifically for the use of roll outs along both street frontages.


GENERAL COMMENTS:

Provide a revised Final Plat, Assurances, and Site Plan Exhibit at re-submittal addressing the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

For questions or to schedule a meeting I can be reached at 837-4929.

Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Planning & Development Services
01/22/2014 KAY MARKS PIMA COUNTY ADDRESSING Reqs Change 201 N. STONE AV, 1ST FL
TUCSON, AZ 85701-1207

[Description: Pcseal]


MICHELENE NOWAK
ADDRESSING REVIEW
PH #: 724-9512

TO:

CITY PLANNING

FROM:

MICHELENE NOWAK, ADDRESSING REVIEW

SUBJECT:

S14-001/FINAL PLAT FOR 4056 EAST GLENN LOTS 1-5-1ST REVIEW

DATE:

JANUARY 22, 2014




The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

1. Label project # S14-001 on all Sheets

2. Correct Title Block to read: Catalina Farms Addition . . .

3. Verify if access to the existing residence on Lot 1 will remain on Glenn Street or change to Calle De Romy.
01/23/2014 JIM EGAN COT NON-DSD FIRE Approved
01/29/2014 PGEHLEN1 ENV SVCS REVIEW Approv-Cond ESD has reviewed the Minor Subdivision submittal. Please add the following general note to the Site Plan Exhibit: Refuse service is to be individual curbside service. Plastic containers (APCs) shall be placed and removed from the curbside collection area on the day of service.
01/29/2014 JANE DUARTE COT NON-DSD PARKS & RECREATION Approved
01/29/2014 JOE LINVILLE LANDSCAPE REVIEW Approved
01/29/2014 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Passed
01/29/2014 ZELIN CANCHOLA COT NON-DSD TRAFFIC Denied From Zelin Canchola
TDOT
Date: 1-28-14

Subject 4056 E Glenn Street Lots 1 through 5

Plan needs further modification.

1. In reference to PDSD engineering commnet Number 8, TDOT concurs with the requirement to install sidewalks. "Will be required to install sidewalk along the entire street frontage of both public roadways. Glenn Street will require 6 foot wide sidwalk. Glenn is not scheduled for widening at this time. A right of way permit will ber required for work in the Right of Way. Contact permits and codes 791-4259 for additional information.

2. Site Plan Exibit:

No backing out onto Glenn Street will be permitted.

Access points must meet city code/access management guidlines.

No additinal future street dedications required.
01/29/2014 ZELIN CANCHOLA COT NON-DSD TUCSON POLICE DEPARTMENT Approved I have no issues with this proposal.

CSO Becky Noel #37968
Tucson Police Dept
837-7428
01/30/2014 PGEHLEN1 UTILITIES EL PASO NATURAL GAS Passed
01/30/2014 PGEHLEN1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Passed
01/30/2014 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Reqs Change This review has been completed and resubmittal is required. Please resubmit the following items:

1) 2 rolled sets of the drawings
2) A disk containing all items submitted
3) All items requested by review staff
4) All items needed to approved this plan.
01/30/2014 ROBERT YOUNG PIMA COUNTY PIMA CTY - DEV REVIEW Passed
01/30/2014 PGEHLEN1 UTILITIES CENTURYLINK Passed
01/30/2014 PGEHLEN1 OTHER AGENCIES U. S. POST OFFICE Passed
01/30/2014 PGEHLEN1 PIMA COUNTY WASTEWATER Approved REGIONAL WASTEWATER RECLAMATION DEPARTMENT
201 NORTH STONE AVENUE
TUCSON, ARIZONA 85701-1207
JACKSON JENKINS PH: (520) 724-6500
DIRECTOR FAX: (520) 724-9365

January 30, 2014


To: Kevin M. Hall, P.E., Project Manager
Cypress Civil Dwvelopment, LLC

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

From: Francisco Galindo, P.E., Civil Engineer
Planning and Engineering - DLU

Subject: 4056 East Glenn, Lots
Final Plat - 1st Submittal, S14-001, Review Comments

The drawings of the Final Plat for the proposed project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWRD). This review letter may contain comments pertaining to the concerns of either Department.
PCRWRD hereby approves the above referenced submittal of the Final Plat received by us on January 14, 2014.
Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) will need to be obtained. Cypress Civil Development indicated that the development will not include any public sewers.

If you have any questions regarding the above comments, please contact me.




Francisco Galindo, P.E.
Planning and Engineering - Development Liaison Unit


Cc: Chad Amateau, P.E., RWRD
Lorenzo Hernandez, P.E., RWRD
Project file: S-14-001; T13S, R14E, Section 34
01/30/2014 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)


FROM: Julieann Arechederra
GIS Cartographer
Pima County Assessor's Office


DATE: January 17, 2014


RE: Assessor's Review and Comments Regarding: S14-001
4056 EAST GLENN


* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

X Plat meets Assessor's Office requirements.
_______ Plat does not meet Assessor's Office requirements.

COMMENTS:



" THANK YOU! THIS PLAT MEETS ASSESSOR'S REQUIREMENTS.TCHES WHAT WE HAVE.












NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/08/2014 GERARDO BONILLA REJECT SHELF Completed