Plan Number: S13-021
Parcel: Unknown

Address:
633 W 18TH ST

Review Status: Completed

Review Details: MINOR SUBDIVISION REVIEW

Plan Number - S13-021
Review Name: MINOR SUBDIVISION REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2013 PGEHLEN1 START PLANS SUBMITTED Completed
08/02/2013 KAY MARKS PIMA COUNTY ADDRESSING Passed per addressing form
08/05/2013 PGEHLEN1 ENV SVCS REVIEW Passed ES has no comments at this point.

Jeff
08/05/2013 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved See letter in SIRE
08/06/2013 ROBERT SHERRY PLUMBING-RESIDENTIAL REVIEW Passed
08/07/2013 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved Regional Traffic Engineering has no objections to the proposed development and supports its acceptance. Thank you.

________________________________

Confidentiality and Nondisclosure Notice: This email transmission and any attachments are intended for use by the person(s)/entity(ies) named above and may contain confidential/privileged information. Any unauthorized use, disclosure or distribution is strictly prohibited. If you are not the intended recipient, please contact the sender by email, and delete or destroy all copies plus attachments.
.
08/09/2013 MICHAEL ST. PAUL ZONING REVIEW Approv-Cond Place the subdivision number (S13-021) in the lower right corner of each sheet.
08/13/2013 PGEHLEN1 OTHER AGENCIES PIMA ASSN OF GOVTS Approved No objections/adverse comments



____________________________

Eric W. Kramer, Ph.D., AICP

Senior Land-Use Modeler



PAG40MPOhoriz3.png



177 N. Church Ave, Suite 405

Tucson, AZ 85701

(520) 792-1093 x506 (tel)

(520) 620-6981 (fax)

www.pagnet.org

<mailto:ekramer@pagnet.org> ekramer@pagnet.org
08/19/2013 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 08/23/2013,
SUBJECT: South Yard Drill Track, Blocks 1-5 and Public Recreation Areas
S13-021, T14S, R13E, SECTIONS 13 and 14

RECEIVED: Final Plat and Drainage Report on July 31, 2013

The subject submittal has been reviewed. The submittal can not be approved at this time. Address the following comments before review can continue. Prepare a detailed response that explains the revisions that were made and references the exact location on the Drainage submittal and the Block Plate where the revisions were made:

Drainage Report:

1. The submitted a drainage report is approximately 20 years old. Verify that the information presented in the report still valid and submit, if necessary, a master drainage statement for this project that includes all drainage related information relevant to this subdivision.
2. Submit a drainage exhibit, for the subject subdivision, that shows all 100-year floodplain limits for all flows of 100 cfs or more. Additionally, include the regulatory floodplain water surface elevations.
3. Based on the results of the floodplain study, then proposed drainage easement dimensions shall be determined.
4. In order to ensure that the created parcels are developable, verify that all parcels will have all weather access. Additionally, verify that encroachment will not be an issue.
5. The master drainage statement shall determine the guideline under which the individual lot drainage report shall be prepared.
6. The master drainage statement must address how the lot to lot drainage will be managed regardless of which parcel will be developed first and the following parcels development sequence. It should be clearly stated that lot to lot drainage pattern shall be accommodated and maintained for post development conditions and shall not be blocked.
7. The master drainage report shall clearly state that a separate drainage report shall be submitted for every individual parcel at the time of its development.
8. The master drainage report shall address future drainage facilities maintenance responsibilities.

Final Plat

1. The plat shall be stamped by a registered civil engineer and registered surveyor (A.M. 2-07.5.3.A).
2. Since this submittal does not have a tentative plat associated with it, submit a site plan that show all existing culture, existing grades or contour lines, and the 100-year floodplain limits and water surface elevations (UDC 8.4.1.A).
3. The parcels developability and suitability for development shall be determined during the block plat submittal. The City's regulations do not allow creating new lots/parcels that are not developable. Revise General Note #7 accordingly.
4. Provide the complete S13-021 case number on every sheet (A.M. 2-07.5.1.H).
5. Add a general note, which requires the submittal of a separate drainage report for each parcel, to address the proposed parcel drainage for pre and post development conditions (A.M. 2-07.5.2).
6. Determine if the owner(s) is an individual or more than one person and revise all "Certification" and "Dedication" accordingly.
7. If some or all parcels are subject to the floodplain requirements, add the following note: "Prior to issuance of any building permit, a Floodplain Use Permit is required for Lots/Parcels________".
8. Clarify if assurances are required to assure that all relevant assurable items (i.e. monuments, etc..) that need to be installed, shall be completed with this plat (A.M. 2-07.5.3.E).
9. If assurances are required and are submitted in the form of a third party land trust, a "Beneficiary" block need to be provided on the first sheet of the plat (A.M. 2-07.5.3.C).
10. Show, if applicable, all erosion hazard setback lines as required by A.M. 2-07.5.4.E.
11. Show the limits of all 100-year flood prone areas in a surveyable and readily retraceable manner with frequent ties to intersecting lot lines for all flows of 100 cfs or more (A.M. 2-07.5.4.F).
12. The dimensions of the proposed drainage easements may need to be revised based on the floodplain limits information (A.M. 2-07.5.5.B).
13. Do Blocks 1, 2 and 3 need no-vehicular access easements (A.M. 2-07.5.4.H)?
14. Are cross access easements required among the different parcels (A.M. 2-07.5.4.A) and (A.M. 2-07.5.5.B)?
15. In order to expedite the plat review and approval, provide the boundary survey and closure calculations report in accordance with A.M. 2-07.5.5.C.3.
16. Submit, if applicable, a copy of the assurances for review.
08/19/2013 PGEHLEN1 PIMA COUNTY WASTEWATER Denied PIMA COUNTY
REGIONAL WASTEWATER RECLAMATION DEPARTMENT
201 NORTH STONE AVENUE
TUCSON, ARIZONA 85701-1207
JACKSON JENKINS PH: (520) 724-6500
DIRECTOR FAX: (520) 620-0135

August 15, 2013

To: John A. Cahill, Property Agent
City of Tucson Real Estate Program

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

From: Francisco Galindo, P.E., Civil Engineer
Development Liaison Unit

Subject: FINAL BLOCK PLAT for South Yard Drill Track, Block 1-5
Final Plat - 1st Submittal, S13-021, Review Comments

The drawings of the Final Plat for the proposed project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWRD). This review letter may contain comments pertaining to the concerns of either Department.
The PDEQ and PCRWRD hereby reject the above referenced submittal of the Final Plat received by us on August 1, 2013, for the following reasons:
1. All Public Sewer Easements, access to public sewers and landscaping within public sewer easements shall be in accordance to the Pima County RWRD "Engineering Design Standards, 2012", Section 7.
2. Cover Sheet: The second paragraph of the Dedication shall read (I/We) herby grant to the public, Pima County, and all utility companies…
3. Add Township and Range to General Note No. 11.
4. Sheet 2: Revise the proposed "30' Unrecorded Sewer Easement" to 40' Public Sewer Easement Dedicated by this Plat. Easement widths must be in accordance to the Engineering Design Standards, 2012, Subsection 7.1.1.
5. Sheet 3: Revise the "Unrecorded License Agreement" to XX' Public Sewer Easement Dedicated by this Plat. The existing 36" sewer interceptor shall be in its entirety within a public sewer easement, public right-of-way or combination of both. The easement shall extend as a minimum 15 ft. southerly of the existing sewer interceptor and northerly to the proposed right-of-way line of 18th Street.
Please note the following: An approval of the above referenced submittal does not authorize the construction of public or private sewer collection, or water distribution lines. Prior to the construction of such features, a Construction Authorization (approval to construct) will need to be obtained from PDEQ.

If you have any questions regarding the above comments, please contact me at (520) 724-6733, Francisco.Galindo@pima.gov or Michael.Harrington@wwm.pima.gov at (520) 724-6305.






Francisco Galindo, P.E.
Planning and Engineering - Development Liaison Unit


Cc: Michael J. Harrington, Sr. CEA
Kurt Stemm, RWRD
Chad Amateau, P.E., RWRD
Project file, T14S, R13E, Sections, 13 and 14
08/22/2013 PGEHLEN1 COT NON-DSD TUCSON POLICE DEPARTMENT Approved I have no issues with this request.

CSO Becky Noel #37968
Tucson Police Dept
837-7428
08/23/2013 RONALD BROWN ZONING HC REVIEW Passed
08/27/2013 JIM EGAN COT NON-DSD FIRE Approved
08/29/2013 PGEHLEN1 UTILITIES SOUTHWEST GAS Denied August 26, 2013

City of Tucson
Attn: Patricia Gehlen
201 N. Stone Avenue, 6th Floor
Tucson, Arizona 85701

RE: S13-021/SOUTH YARD DRILL TRACK
Final Block Plat for South Yard Drill Track

Southwest Gas Corporation (SWG) has existing natural gas facilities located in Block 5 and the Public Recreation Areas of the proposed "Final Block Plat for South Yard Drill Track". SWG objects to the plat as presented. The plat does not indicate the prior rights for these facilities pursuant to a license agreement granted by the City's predecessor in interest to the property.This should be corrected on the plat. Additionally, in order to protect these facilities, SWG requests a perpetual easement be saved and reserved to SWG, without cost to SWG, as a condition of the recordation of the proposed Plat.

The Applicant may request that the existing natural gas facilities be relocated. Said relocation shall be at the Applicant's expense, in accordance with SWG's approved Arizona Gas Tariff, and to a location satisfactory to SWG.

Further information regarding natural gas facilities on or near this project may be acquired by contacting me at (520) 794-6265.

Respectfully,



Francisco Castro
Engineering Supervisor
Southern Arizona Division
08/29/2013 JANE DUARTE COT NON-DSD PARKS & RECREATION Approved
08/29/2013 JOE LINVILLE LANDSCAPE REVIEW Approved
08/29/2013 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
09/03/2013 PGEHLEN1 UTILITIES CENTURYLINK Passed
09/03/2013 PGEHLEN1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Passed
09/03/2013 PGEHLEN1 UTILITIES EL PASO NATURAL GAS Passed
09/03/2013 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Passed
09/03/2013 ROBERT YOUNG PIMA COUNTY PIMA CTY - DEV REVIEW Passed
09/03/2013 PGEHLEN1 OTHER AGENCIES U. S. POST OFFICE Passed
09/04/2013 ED ABRIGO PIMA COUNTY ASSESSOR Denied Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)


FROM: Ada Griffin
GIS Cartographer
Pima County Assessor's Office


DATE: August 16, 2013


RE: Assessor's Review and Comments Regarding:

S13-021/SOUTH YARD DRILL TRACK

_

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Plat meets Assessor's Office requirements.
___X___ Plat does not meet Assessor's Office requirements.

COMMENTS:


" ALL ADJACENT SUBDIVISIONS SHOULD BE NAMED, WITH MAP AND PLAT IN THE APPROPRIATE AREAS AROUND THE SUBDIVISION.



NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.
09/05/2013 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Reqs Change This review has been completed and resubmittal is required.

Please resubmit the following items:

1) 4 rolled sets of the plans
2) 1 folded set for RWRD and fees(applicant is responible for submitting to RWRD).
3) a disk containing all items submitted to the city
4) all items requested by review staff
5) all items needed to approve the plans.
09/05/2013 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Denied Tucson Electric Power (TEP) has reviewed the final plat and does not approve.

As you aware TEP has facilities within the proposed subdivision. An easement for these facilities will need to be granted by this plat in order for TEP's approval.

Please contact me at 917-8744 if there are any questions.

Thank you,
Mary Burke
Tucson Electric Power

Sent from my iPhone

Final Status

Task End Date Reviewer's Name Type of Review Description
09/09/2013 CPIERCE1 REJECT SHELF Completed