Plan Number: S13-012
Parcel: Unknown

Review Status: Completed

Review Details: FINAL PLAT - REVIEW

Plan Number - S13-012
Review Name: FINAL PLAT - REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2013 CPIERCE1 START PLANS SUBMITTED Completed
05/14/2013 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved See letter in SIRE
05/14/2013 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Approv-Cond MICHELENE NOWAK
ADDRESSING REVIEW
PH #: 721-9512



TO: CITY PLANNING
FROM: MICHELENE NOWAK, ADDRESSING REVIEW
SUBJECT: S13-0012/FINAL PLAT FOR MARANA MARKETPLACE PHASE III LOT 1
DATE: May 14, 2013



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

On Final Plat include Project #S13-0012 on all Sheets.


1.) Submit a 24 x 36 Reverse Reading Double Matte Photo Mylar or bond paper of approved Development Plan to City Planning. Signed and dated Mylar will be forwarded to Pima County Addressing prior to assignment of addresses.

2.) All addresses will need to be displayed per Pima County Address Standards at the time of final inspection.




***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through Pima
County Addressing. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County’s
Geographic Information System. Your support is greatly appreciated.***
05/15/2013 JASON GREEN ENGINEERING REVIEW Reqs Change DATE: May 17, 2013
SUBJECT: Marana Market Place Phase III Block Plat Submittal- Engineering Review
TO: Patricia Gehlen, CDRC Manager
LOCATION: 6080 N Thornydale Rd, T13S R13E Sec08 Ward 3
REVIEWER: Jason Green, CFM
ACTIVITY: S13-012

SUMMARY: Engineering Division of Planning and Development Services Department has received and reviewed the proposed Final Plat and Title Report. Engineering Division has reviewed the submitted Final Plat and does not recommend approval at this time. Refer to this link for further clarification:
http://cms3.tucsonaz.gov/files/planning/Admin_Manual_ADOPTED_100912.pdf

The following items need to be addressed:

FINAL PLAT COMMENTS:
1) AM Sec.2-07.5.1.A.2: Revise the Location Map to label the Section Corners.

2) AM Sec.2-07.5.1.A.4: Revise the Location Map to label the major watercourses (Rillito Creek) within the 1-mile area.

3) AM Sec.2-07.5.1.A.5: Revise the Location Map to label the City's jurisdictional limits within the mapped area.

4) AM Sec.2-07.5.1.H: Revise the Final Plat to place the assigned subdivision case number "S13-012" in the lower right corner of the plat next to the Title Block on all sheets.

5) AM Sec.2-07.5.3.B.2: Revise the Final Plat and the Dedication paragraph to read per the referenced standard. Use one of the 4 statements within the standard that is appropriate for the plat. Since the plat is a Block Final Plat the dedication should be specific to the public easements that are located onsite, revise the statement to reflect as such.

6) AM Sec.2-07.5.3.D: Revise the Final Plat and Recording Data paragraph to read per the referenced section;

Sequence________________
Fee_____________________
State of Arizona
County of Pima
I hereby certify that the instrument
was filed for record at the request
Of__________________________
Date________________________
Time_________________________
Witness my hand and Official Seal
day and year above written.
F. ANN RODRIGUEZ, County Recorder
BY___________________________
Deputy

7) AM Sec.2-07.5.5.C.4: Revise the Final Plat to label all boundary monuments as either found or set. Specifically the monument along the west property line that is tied to the 1/16 corner of Section 8. Clearly label the monument as found or set.

GENERAL COMMENTS:

Provide a revised Final Plat at re-submittal addressing the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

For questions or to schedule a meeting I can be reached at 837-4929.

Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Planning & Development Services
05/15/2013 PGEHLEN1 UTILITIES SOUTHWEST GAS Approved see letter in SIRE
05/16/2013 STEVE SHIELDS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Marana Marketplace Phase III
S13-012 (1st Review)
Final Plat

TRANSMITTAL DATE: May 16, 2013


COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The Zoning Review Section conditionally approves the final plat for this subdivision, subject to the following changes on the executed tentative plat. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised tentative plat to verify that those changes do not affect any zoning requirements.

2. A.M. 2-07.5.1.A.2 Label the sections corners on the location map.

3. A.M. 2-07.5.1.H Provide the S13-012 subdivision case number in the lower right corner of the plat next to the title block on all sheets.

4. A.M. 2-07.5.3.D Revise the "RECORDING DATA: block to reflect the following;

SEQUENCE________________
FEE_______________________
STATE OF ARIZONA
COUNTY OF PIMA
HEREBY CERTIFY THAT THE INSTRUMENT WAS FILED FOR RECORD AT THE REQUEST
OF________________________
DATE_____________________
TIME_____________________
WITNESS MY HAND AND OFFICIAL SEAL DAY AND YEAR ABOVE WRITTEN.
F. ANN RODRIGUEZ, COUNTY RECORDER
BY________________________
i. DEPUTY

5. Zoning cannot approve the final plat on until the tentative plat, DP13-0081 has been approved.


If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised final plat.
05/20/2013 ED ABRIGO PIMA COUNTY ASSESSOR Denied Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)


FROM: Ada Griffin
GIS Cartographer
Pima County Assessor's Office


DATE: 05/20/13


RE: Assessor's Review and Comments Regarding

-


* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Plat meets Assessor's Office requirements.
___X___ Plat does not meet Assessor's Office requirements.

COMMENTS:


THE TITLE BLOCK IN THE LOWER RIGHT HAND CORNER OF THE PLAT; MUST HAVE THE SECTION, TOWNSHIP AND RANGE.




NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.
05/29/2013 PGEHLEN1 UTILITIES CENTURYLINK Approv-Cond Hi,



I have reviewed the final plans for the above mentioned development. Centurylink has a buried cable in the public utility easement that runs east and west and is located south of Cantaloupe Drive. Centurylink also has a cable in the public utility easement that runs east and varies north west located north of Cantaloupe Drive. Also we have cable and conduit along the east side of Riber road, which is on the west side of this development. The cables would have to be located to validate their exact location. Also, if the cables mentioned need to be relocated billing to the developer would be required.



Thank you,



Tom Whittaker

Centurylink Field Engineer

For Jihad Farhat
05/29/2013 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: Marana Marketplace Phase III Final Plat
S13-012

Tucson Electric Power Co. has reviewed and approves the final plat submitted for review May 14, 2013.

If you have any questions, please feel free to contact me.

Thank you,

Mary Burke
Right of Way Agent
Tucson Electric Power Co.
Mail Stop HQW603
PO Box 711, Tucson, AZ 85702
Office - 520-917-8744
Cell - 520-401-9895
mburke@tep.com<mailto:mburke@tep.com>
05/30/2013 PGEHLEN1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Passed
05/31/2013 PGEHLEN1 PIMA COUNTY WASTEWATER Denied PIMA COUNTY
REGIONAL WASTEWATER RECLAMATION DEPARTMENT
201 NORTH STONE AVENUE
TUCSON, ARIZONA 85701-1207
JACKSON JENKINS PH: (520) 724-6500
DIRECTOR FAX: (520) 620-0135

May 28, 2013

To: Kevin Hall, P.E., Project Manager
Cypress Civil Development, L.L.C.

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

From: Michael J. Harrington, Sr. Civil Engineering Assistant
Development Liaison Unit

Subject: FINAL BLOCK PLAT for MARANA MARKETPLACE PHASE III, LOT 1
Final Plat – 1st Submittal, S13-0012, Review Comments

The drawings of the Final Plat for the proposed project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWRD). This review letter may contain comments pertaining to the concerns of either Department.
PCRWRD hereby approves the above referenced submittal of the Final Plat received by us on February 27, 2013, subject to the following conditions:
All sheets, Title Block: Show the project case number adjacent to the Title block. Also show the tentative plat cross-reference case number DP13-0081 with the site plan case number.
Sheet 2 of 2: Revise the plat so that it shows the jurisdictional boundaries shared by the City of Tucson and Pima County and the Town of Marana and Pima County.
If you have any questions regarding the above comments, please do not hesitate to contact me.


Michael J. Harrington, Sr. CEA
Planning and Engineering - Development Liaison Unit


Cc: Francisco Galindo, P.E., RWRD
Chad Amateau, P.E., RWRD
Kristin L. Greene, P.E., RWRD
Project file, T13S, R13E, Section 8
05/31/2013 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied This review has been completed. Resubmittal is required.

Please resubmit the following items:

1) Three rolled sets of the plans
2) a disk containing all items submitted
3) All items requested by review staff
4) All items needed to approve the plans.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/03/2013 CPIERCE1 REJECT SHELF Completed
06/03/2013 PGEHLEN1 OUT TO CUSTOMER Completed