Plan Number: S12-017
Parcel: Unknown

Review Status: Completed

Review Details: MINOR SUBDIVISION REVIEW

Plan Number - S12-017
Review Name: MINOR SUBDIVISION REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2012 GBONILL1 START PLANS SUBMITTED Completed
04/02/2012 GBONILL1 COT NON-DSD REAL ESTATE Passed
04/02/2012 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Passed Halycon Acres Water Company provides the water. An assured water supply letter is needed when a subdivision is 6 or more parcels. No letter is needed.
04/03/2012 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved Regional Traffic Engineering has no comments on this submittal. The development is not adjacent to any ADOT facilities and should continue for approval.
04/03/2012 JIM EGAN COT NON-DSD FIRE Approved
04/04/2012 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: S12-017
The Place at Presidio Trail Block 1

Tucson Electric Power Co. (TEP) approves the final plat submitted for review on April 2, 2012.
Existing overhead electrical facilities are located within the platted area. All costs associated with the removal or relocation of the facilities will be billable to the developer.
Please forward any resubmittals of the final plat to this office.

Please contact me at 520-917-8744 if you have any questions.

Thank you,

Mary Burke
Right of Way Agent
Tucson Electric Power Company
Mail Stop HQW603
PO Box 711
Tucson, AZ 85702
520-917-8744 Office
520-401-9895 Cell
mburke@tep.com
04/04/2012 JWILLIA4 OTHER AGENCIES PIMA ASSN OF GOVTS Denied We need the number of dwelling units to comment on this development.



Thanks,

-Eric



____________________________

Eric W. Kramer, Ph.D., AICP

Senior Land-Use Modeler

PAG_logotype

177 N. Church Ave, Suite 405

Tucson, AZ 85701

(520) 792-1093 x506 (tel)

(520) 620-6981 (fax)
04/05/2012 ED ABRIGO PIMA COUNTY ASSESSOR Denied Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)

FROM: Sherry Hyde
Senior Property Technician
Pima County Assessor’s Office


DATE: 4/5/12


RE: Assessor’s Review and Comments Regarding
S12-017 THE PLACE AT PRESIDIO TRAIL- FINAL


* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

X Plat meets Assessor’s Office requirements.
_______ Plat does not meet Assessor’s Office requirements.

COMMENTS:

• THE BLOCK NEEDS TO BE NUMBERED & HAVE THE SQUARE FOOTAGE LISTED ON SHEET 2 OF THE PLAT.
• OUR RECORDS SHOW OWNERSHIP TO BE FIRST AMERICAN TITLE TR 9168 WITH THE BENEFICIARY OF THE TRUST TO BE PEPPER VINER AT PRESIDIO TRAIL LLC.

NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.
04/10/2012 LOREN MAKUS ENGINEERING REVIEW Approv-Cond April 10, 2012

The Engineering Division recommends approval of this plat once the ownership information is completed.

Loren Makus, EIT
Senior Engineering Associate
04/13/2012 JWILLIA4 PIMA COUNTY WASTEWATER Approved PIMA COUNTY
REGIONAL WASTEWATER RECLAMATION DEPARTMENT
201 NORTH STONE AVENUE
TUCSON, ARIZONA 85701-1207
JACKSON JENKINS PH: (520) 740-6500
DIRECTOR FAX: (520) 620-0135
April 11, 2012

To: Dan Castro, Project Manager
RICK Engineering Company

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

From: Kristin L. Greene, P.E., CE Manager
RWRD, Development Review Manager

Subject: The Place at Presidio Trail
Final Plat - 1st Submittal, S12-017, review comments

The drawings of the Final Plat for the proposed project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWRD). This review letter may contain comments pertaining to the concerns of either Department.
The PCRWRD hereby approves the above referenced submittal of the Final Plat received by us on April 2, 2012.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) will need to be obtained from PDEQ.

Also, air quality activity permits must be secured by the developer or prime contractor from PDEQ before constructing, operating or engaging in an activity which may cause or contribute to air pollution.

If you have any questions regarding the above comments, please do not hesitate to contact me.



Kristin L. Greene, P.E.
Civil Engineering Manager, Development Liaison Unit



Cc: Chad Amateau, P.E., RWRD
Project file
04/16/2012 TERRY STEVENS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: S12-017
The Place at Presidio Trail
Final Plat

TRANSMITTAL: 04/16/2012

DUE DATE: 05/01/12

COMMENTS:

1. The Zoning Review Section approves the final plat for this subdivision, subject to the following changes on the executed final plat. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised final plat to verify that those changes do not affect any zoning requirements.

2. DS 2-03.6.1.K 2 Case number S12-017 has been assigned to this final plat Please place this number in the right corner of all sheets of the final plat.

Remove the DP12- from all sheets.

Place the previous final plat case number, S05-135, and the annexation case number, C9-84-65 near the lower right corner of all sheets.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

TLS C:\planning\cdrc\finalplat\S12-017fpca.doc
04/17/2012 ZELIN CANCHOLA COT NON-DSD TRAFFIC Approved
04/23/2012 JWILLIA4 ENV SVCS REVIEW Approved Environmental Services Department
Development Plan Review
Reviewer: Jeff Drumm
Office Phone (520) 837-3713
E-mail: Jeffrey.Drumm @tucsonaz.gov


Date Case Number Project Address
April 23, 2012 S12-017 The Place at Presidio Trails

Comments: No comments.
04/26/2012 JOHN BEALL COT NON-DSD COMMUNITY PLANNING Passed No Comments.
04/30/2012 RONALD BROWN ZONING HC REVIEW Approved
05/01/2012 JOE LINVILLE LANDSCAPE REVIEW Denied Revise the plat to include any easements requested by Parks and Recreation.
05/02/2012 ROBERT YOUNG PIMA COUNTY PIMA CTY - DEV REVIEW Passed
05/02/2012 JANE DUARTE COT NON-DSD PARKS & RECREATION Denied
05/02/2012 PGEHLEN1 OTHER AGENCIES TUCSON AIRPORT AUTHORITY Passed
05/02/2012 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 2ND FL
TUCSON, AZ 85701-1207


AUDREY FARENGA
ADDRESSING REVIEW
PH #: 740-6800
FAX #: 623-5411


TO: CITY PLANNING
FROM: AUDREY FARENGA, ADDRESSING REVIEW
SUBJECT: S12-017 THE PLACE AT PRESIDIO TRAIL/FINAL PLAT
DATE: April 18, 2012



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

On the Final Plat label Block 1 on sheet 2.

***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through Pima
County Addressing. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County’s
Geographic Information System. Your support is greatly appreciated.***
05/03/2012 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

May 3, 2012

Rick Engineering
Dan Castro
3945 East Fort Lowell Road Suite 111
Tucson, Arizona 85712

Subject: S12-017 The Place at Presidio Trails Final Plat

Dear Dan:

Your submittal of April 2, 2012 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and two sets of the DETAILED cover letters explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

2 rolled copies Revised Final Plat (PAG, Assessors, Engineering, Zoning, Landscape, Parks and Recreation, Addressing, PDSD)

1 disk with all documents submitted


Should you have any questions, please call me at 837-4919.

Sincerely,



Patricia Gehlen
Project Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: sent via e-mail.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/16/2012 GERARDO BONILLA OUT TO CUSTOMER Completed