Plan Number: S12-013
Parcel: Unknown

Address:
2350 N 1ST AV

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - FINAL PLAT REVIEW

Plan Number - S12-013
Review Name: RESUBMITTAL - CDRC - FINAL PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2012 CPIERCE1 START PLANS SUBMITTED Completed
04/20/2012 TERRY STEVENS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: S12-013
Walgreens & Pad A
Final Plat

TRANSMITTAL: 04/20/2012

DUE DATE: 05/02/2012

COMMENTS:


1. The Zoning Review Section approves the final plat for this subdivision, subject to the following changes on the executed final plat. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised final plat to verify that those changes do not affect any zoning requirements.


2. DS 2-06.6 Per the conditional approval of the tentative plat, provide at the time of final plat, vehicle access for the two residential parcels (123-13-0750 and 123-13-0760). These documents have not been provided at the time of this review.

Per discussion with Jeff Beharana a separate agreement has been reached with the residential owners in regards to access. Provide copies of the agreements for review.

Provide a note on the final plat indicating that this access agreement has been recorded and provide recording sequence numbers for each agreement.

Provide sequence recording information for the abandonment of the alley and for the dedication of right of way.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

TLS C:\planning\cdrc\finalplat\S12-013fp-ca.doc
04/20/2012 LOREN MAKUS ENGINEERING REVIEW Approv-Cond April 20, 2012
S12-0013

The Final Plat is approved with the following conditions:

1. Include the name of the City Clerk in the blank space within the approvals section. The current City Clerk is Roger Randolph.
2. Include the recordation data for right-of-way dedication and for the alley abandonment.

Loren Makus, EIT
Senior Engineering Associate
05/01/2012 PGEHLEN1 CC&R CC&R's Passed
05/01/2012 PGEHLEN1 PIMA COUNTY WASTEWATER Approved PIMA COUNTY
REGIONAL WASTEWATER RECLAMATION DEPARTMENT
201 NORTH STONE AVENUE
TUCSON, ARIZONA 85701-1207
JACKSON JENKINS PH: (520) 740-6500
DIRECTOR FAX: (520) 620-0135
April 30, 2012

To: Katie Rounds, Project Manager
Evergreen Devco, Inc.

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

From: Kristin L. Greene, P.E., Civil Eng. Manager
RWRD, Development Review Manager

Subject: Amigos De Alpert, Lots 1 and 2
Final Plat - 2nd Submittal, S12-013, review comments

The drawings of the Final Plat for the proposed project have been reviewed on behalf of Pima County Department of Environmental Quality (PDEQ) and Pima County Regional Wastewater Reclamation Department (PCRWRD).This review letter may contain comments pertaining to either Department. The following comments are offered.
The PCRWRD hereby approves the above referenced submittal of the Final Plat received by us on April 18, 2012.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval to Construct) will need to be obtained from PDEQ.

Also, air quality activity permits must be secured by the developer or prime contractor from PDEQ before constructing, operating or engaging in an activity which may cause or contribute to air pollution.

If you have any questions regarding the above comments, please do not hesitate to contact me.




Kristin L. Greene, P.E.
Civil Engineering Manager, Development Liaison Unit





Cc: Chad Amateau, P.E., RWRD
Chandubhai Patel, P.E., RWRD
Project file
05/02/2012 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approved COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

May 2, 2012


Jeff D. Behrana
4650 E. Cotton Center Blvd.
Suite 200
Phoenxi, Arizona 85040

Subject: S12-013 Walgreens and Pad A Final Plat

Dear Jeff:

The above referenced project has been CONDITIONALLY APPROVED by the Community Design Review Committee. Please make any necessary corrections and submit the following documents:

1 Executed Final Plat Double Matte Océ or Photo Mylar.

2 Title reports current within the last thirty (30) days.

1 Check made payable to "Pima County Recorder" in the amount of $20.00 per plat page plus a $4.00 handling fee, along with CC&R fees if applicable. CC&R fees are $9.00 for the first 5 pages and $1.00 for each additional page and fees for consent(s) to dedicate, if applicable.

1 Original Set of Executed and notarized CC&R's document (if applicable) and Assurance Package (if applicable).

1 Copied Set of Executed and notarized CC&R's document (if applicable) and Assurance Package (if applicable).

1 CD with Digital Copy in PDF Format of Plat, CC&R's (if applicable) and Assurances (if applicable).

Assurances (if applicable) must be reviewed by the City Attorney's Office prior to being presented to the Mayor and Council. Plats, CC&R's and assurances must be approved at the same Mayor and Council Meeting. Please expect 5-6 weeks from the date submitted to the date scheduled for Mayor and Council approval.

Should you have any questions, please call me at (520) 837-4919.

Sincerely,

Patricia Gehlen
Project Manager


All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: (520)
05/02/2012 PGEHLEN1 UTILITIES TUCSON ELECTRIC POWER Approved From: Burke, Mary
Sent: Thursday, April 26, 2012 3:02 PM
To: DSD_CDRC@tucsonaz.gov
Subject: S12-013 Walgreens & Pad A Final Plat Review

SUBJECT: WALGREENS & PAD A FINAL PLAT REVIEW
S12-013

Tucson Electric Power (TEP) has reviewed and approves the final plat submitted April 19, 2012.

Please contact me at 917-8744 if you have any questions.

Thank you,

Mary Burke
Right of Way Agent
Tucson Electric Power Company
Mail Stop HQW603
PO Box 711
Tucson, AZ 85702
520-917-8744 Office
520-401-9895 Cell
mburke@tep.com

Final Status

Task End Date Reviewer's Name Type of Review Description
07/02/2012 JWILLIA4 APPROVAL SHELF Completed
07/02/2012 JWILLIA4 REJECT SHELF Completed
07/02/2012 JWILLIA4 OUT TO CUSTOMER Completed