Plan Review Detail
Review Status: Completed
Review Details: FINAL PLAT REVIEW
Plan Number - S09-057
Review Name: FINAL PLAT REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/21/2009 | FERNE RODRIGUEZ | START | PLANS SUBMITTED | Completed | |
| 09/21/2009 | FERNE RODRIGUEZ | COT NON-DSD | REAL ESTATE | Passed | |
| 09/24/2009 | LAITH ALSHAMI | ENGINEERING | REVIEW | Denied | Laith Alshami, Engineering and Floodplain Review, 09/29/2009, TO: Patricia Gehlen FROM: Laith Alshami, P.E. CDRC Engineering SUBJECT: Tucson Hotel and Convention Center S09-057, T14S, R13E, SECTION 13 Reference: D09-0025 and D09-0029 RECEIVED: Final Plat on September 21, 2009 The subject submittal has been reviewed and it can not be approved at this time. Address the following comments before review can continue. Prepare a detailed response that explains the revisions that were made and references the exact location on the Plat where the revisions were made: Final Plat: 1. Provide the complete S09-XXX case number as required by D.S. 2-03.6.1.K. 2. The development plan and drainage report for the hotel are still in review. The floodplain limits that might impact the proposed improvements have not been completely determined. If the proposed improvements are impacted by the regulatory floodplain, The standard general note concerning the floodplain use permit requirement, must be added (D.S. 2-03.6.2.E.). Please be advised that if the regulatory floodplain impacts the subject project, an engineer certification is required. 3. Show the limits of the 100-year flood prone areas in a surveyable and readily retraceable manner with frequent ties to intersecting lot lines for all flows of 100 cfs or more if applicable (D.S. 2-03.6.2.E.). 4. Demonstrate that the proposed improvements will not conflict with the existing easements. 5. Provide the proper tie between the basis of bearing and one of the subject parcel corner monuments (D.S. 2-03.6.5.A). 6. Verify that assurances are not required for this project. RESUBMITTAL REQUIRED: Revised Final Plat |
| 09/25/2009 | LIZA CASTILLO | UTILITIES | TUCSON ELECTRIC POWER | Approved | SUBJECT: TUCSON HOTEL AND CONVENTION CENTER S09-057 Tucson Electric Power Co. (TEP) approves the final plat submitted for review September 21, 2009. If easements are required, they will be secured by separate instrument. Please forward any resubmittals of the final plat to this office. Please contact me at (520) 917-8745 if you have any questions. Liza Castillo, Right of Way Agent II Tucson Electric Power Co. Unisource Energy Services offc-(520) 917-8745 fax-(520) 545-1416 lcastillo@tep.com |
| 09/25/2009 | JENNIFER STEPHENS | PIMA COUNTY | ADDRESSING | Denied | 201 N. STONE AV., 1ST FL TUCSON, AZ 85701-1207 AUDREY FARENGA ADDRESSING REVIEW PH: 740-6480 FAX #: 740-6370 TO: CITY PLANNING FROM: AUDREY FARENGA, ADDRESSING REVIEW SUBJECT: S09-057 TUCSON HOTEL AND CONVENTION CENTER/FINAL PLAT DATE: 09/25/09 The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval: 1 – Shade in only the area to be resubdivided on the Location Map. 2 – Change Lot 1 (northwestern most) to Lot 5 on pg. 2. |
| 10/01/2009 | PGEHLEN1 | CC&R | CC&R's | Approv-Cond | see engineering comments |
| 10/01/2009 | STEVE SHIELDS | ZONING | REVIEW | Denied | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Lead Planner PROJECT: Tucson Hotel and Convention Center S09-057 Final Plat TRANSMITTAL DATE: September 30, 2009 DUE DATE: October 05, 2009 COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a plat. If, at the end of that time, the plat has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this tentative plat is September 20, 2010. 2. D.S. 2-03.6.1.D.2 Show conditions within the square mile area, subdivisions (by book and page numbers) and railroads. 3. D.S. 2-03.6.1.F Provide a reduced-scale map of the entire Planned Area Development (PAD) district on the first sheet and indicate the location of the portion being developed. 4. D.S. 2-03.6.1.K Place the S09-057 subdivision case number assigned to the plat in the lower right hand corner of the plat next to the title block. 5. Based on the Development Plan D09-0029 it appears that there are proposed structure that will be built over existing easements. Please clarify what easements will be abandoned. 6. There is a 1'-0" VEHICULAR ACCESS EASEMENT that runs along Cushing Street property line. There is a proposed vehicle access point along Cushing Street. The 1'-0" vehicular access easement will need to be abandoned. 7. There are several easements shown on the plan with a letter designator but no description of what type of easement it is. Please clarify what type of easements these are. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C\planning\cdrc\finaplat\S09-057fp.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised final plat, and additional requested documents. |
| 10/06/2009 | FERNE RODRIGUEZ | COT NON-DSD | TUCSON AIRPORT AUTHORITY | Approved | The Tucson Airport Authority does not oppose this application. thank you Jordan D. Feld, AICP Director of Planning Tucson Airport Authority 7005 S. Plumer Ave. Tucson, AZ 85756 jfeld@tucsonairport.org www.tucsonairport.org (520) 573-5115 office (520) 573-8006 fax |
| 10/06/2009 | FERNE RODRIGUEZ | PIMA COUNTY | WASTEWATER | Denied | October 6, 2009 To: Dan Castro Rick Engineering Company, Inc. Thru: Patricia Gehlen, CDRC Manager City of Tucson Development Services Department From: Chandubhai C. Patel, P.E., Civil Eng. Manager Development Review Division ( Wastewater) Subject: Tucson Convention Center Final Plat – 1st Submittal S09-057 The drawings of the proposed Final Plat for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWRD). This review letter may contain comments pertaining to the concerns of either Department. The following comment is offered for your use. 1. The Development Plan for this project was reviewed on August 19, 2009 and NOT APPROVED because of the lack of required sewer capacity letter from the PCRWRD. Until the Development Plan gets approved, this Final Plat cannot be approved. We will revise this letter upon approval of the development plan. No additional fee will be charged. If you have any questions regarding the above-mentioned comments, please do not hesitate to contact me. |
| 10/06/2009 | ED ABRIGO | PIMA COUNTY | ASSESSOR | Approv-Cond | Office of the Pima County Assessor 115 N. Church Ave. Tucson, Arizona 85701 BILL STAPLES ASSESSOR TO: CDRC Office Subdivision Review City of Tucson (FAX# 791-5559) FROM: Joyce Hays, Section Supervisor Pima County Assessor’s Office Mapping Department DATE: September 30, 2009 RE: Assessor’s Review and Comments Regarding Final Plat S-09-057 TUCSON HOTEL AND CONVENTION * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * X Plat meets Assessor’s Office requirements. COMMENTS: PAGE 1 OF THE PLAT IS NUMBERED WITH ALL 6 LOTS, BUT PAGE 2 HAS TWO LOT 1’S & NO LOT 5. ALL ADJACENT SUBDIVISIONS SHOULD BE NAMED, WITH MAP AND PLAT, IN THE APPROPRIATE AREAS AROUND THE SUBDIVISION. NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED. |
| 10/07/2009 | PGEHLEN1 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Approved | |
| 10/08/2009 | JOHN WILLIAMS | ZONING-DECISION LETTER | REVIEW | Denied | COMMUNITY DESIGN REVIEW COMMITTEE PLANNING & DEVELOPMENT SERVICES October 8, 2009 Dan Castro Rick Engineering Company 3945 E. Fort Lowell Road, #111 Tucson, Arizona 85712 Subject: S09-057 Tucson Hotel and Convention Center Final Plat Dear Dan: Your submittal of September 21, 2009 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a set of 6 DETAILED cover letters explaining how each outstanding requirement has been addressed: ALL BLACKLINES MUST BE FOLDED 6 Copies Revised Final Plat (Engineering, Addressing, Assessors, Zoning, Wastewater, PDSD) Should you have any questions, please call me at 837-4919. Sincerely, John Williams Planning Technician All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/ Via fax: (520) 322-6956 |