Plan Number: S09-036
Parcel: Unknown

Review Status: Completed

Review Details: FINAL PLAT - CONDO CONVERSION

Plan Number - S09-036
Review Name: FINAL PLAT - CONDO CONVERSION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2009 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
06/05/2009 ANDY STEUART COT NON-DSD REAL ESTATE Approv-Cond Request "S09-036" be annotated in space provided at the lowr right hand corner.
06/05/2009 DAVID MANN COT NON-DSD FIRE Denied Additional fire hydrant required. Refer to C.O.T. amendments to the 2006 IFC (Section 503) for spacing requirements.
06/11/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied Redo parking as per originally approved site developement plan. Reference H/C comments.
06/11/2009 RONALD BROWN ZONING HC SITE REVIEW Denied The following items need to be physically completed on site and completion verified by DSD by on site inspection prior to final plat approval:
1. Repaint the two accessible parking spaces shown on the originally approved site developemnt plan.
2. Reestablish the marked crossing between the triplex buildings.
3. Add detectable warnings at both existing ramps of the marked crossing in compliance with 2006 IBC, ICC/ANSI 117.1, Section 406.12.

END OF REVIEW
06/15/2009 ED ABRIGO PIMA COUNTY ASSESSOR Approv-Cond Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)

FROM: Joyce Hays, Section Supervisor
Pima County Assessor’s Office
Mapping Department

DATE: 6/12/09


RE: Assessor’s Review and Comments Regarding Final Plat S09-036, Fairmount Villa Condominiums


* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

x Plat meets Assessor’s Office requirements.
_______ Plat does not meet Assessor’s Office requirements.

COMMENTS: Per my conversation with Lou at Baker & Assoc. the Basis of Bearing will be added to the General Notes and a section tie with distance and bearings will be added to the final plat.
Brian Sloan
Pima County Assessor’s Office
Mapping Dept.
740-4395

NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.
06/22/2009 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Denied SUBJECT: FAIRMOUNT VILLA CONDOMINIUMS
S09-036
Tucson Electric Power Company (TEP) has reviewed the final plat
submitted June 4, 2009. TEP is unable to approve the plat at this time.
In order for TEP to approve the final plat, the following dedication
will be required:
* "AN EASEMENT IS GRANTED FOR THE PURPOSE OF ACCESS, INSTALLATION,
REPLACING, REPAIRING AND MAINTENANCE OF ELECTRICAL METERS, CABLE AND
CONDUITS, WHIGH GROUPED ELECTRICAL METERS ARE ATTACHED TO THE EXTERIOR
WALLS."
Show the requested dedication on the resubmittal of the final plat.
Submit a copy to the City of Tucson for TEP's final approval.
Please contact me at (520) 917-8745 if you have any questions.


Liza Castillo, Right of Way Agent II
Tucson Electric Power Co.
Unisource Energy Services
offc-(520) 917-8745
fax-(520) 545-1416
lcastillo@tep.com
06/23/2009 TERRY STEVENS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: S09-036
Fairmount Villa Condominiums
Final Plat - Condo Conversion

TRANSMITTAL: 06/23/2009

DUE DATE: 07/02/09

COMMENTS:

1. An applicant has one (1) year from the date of application to obtain approval and recordation of a final condominium plat that complies with zoning and other development requirements in effect at the time of application. This final condominium plat must be approved and recorded on or before 06/03/10.

2. DS 2-03.6.1.K Case number S09-036 has been assigned to this final plat. Please place this number in the right corner of all sheets of the final plat.

3. Provide a letter stating that the owner/developer is aware of and will comply with all aspects of LUC 4.1.9.1 and LUC Sec. 4.1.9.2.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961


TLS C:\planning\cdrc\finalplat\ S09-036fp.doc
06/29/2009 JASON GREEN ENGINEERING REVIEW Denied DATE: June 29, 2009
SUBJECT: Fairmount Villa Condominium Conversion Final Plat Submittal- Engineering Review
TO: Patricia Gehlen, CDRC Manager
LOCATION: 6145 & 6147 E Fairmount Street, T14S R14E Sec01 Ward 6
REVIEWERS: Jason Green, CFM
ACTIVITY: S09-036

SUMMARY: Engineering Division of Development Services Department has received, Sheet 1 thru 3 of the proposed Final Plat, a copy of the CC&Rs and a copy of the Title Report. Engineering Division has reviewed the submitted Final Plat, CC&Rs and Title Report and does not recommend approval of the Final Plat at this time. The following items need to be addressed:

FINAL PLAT COMMENTS:

1) DS Sec.2-03.6.1.H.1: Revise the title block on the proposed Final Plat and/or all applicable wording in the CC&Rs to match each other. All names, common elements, limited common elements, and descriptions must have the same wording in the CC&Rs as in the Title Block. Provide a clear definition for "Other Common Elements" as stated in the Common Elements "A" description within the Title Block. Verify if this is to include private/public sewers, utilities, water, etc.

2) DS Sec.2-03.6.1.H: Revise the Title Block to add "A Condominium Conversion Project" in the lower right corner of each Sheet.

3) DS Sec.2-03.6.1.K: Revise the Final Plat to indicate the subdivision cases number assigned (S09-036) where indicated by "# _____", it must be added to the lower right hand corner of the plans on all sheets.

4) DS Sec.2-03.6.4.A: Revise the Final Plat to label all streets as "Public." Specifically Lee Street and Alamo Avenue as shown on Sheet 2.

5) DS Sec.2-03.6.3.B.1: Revise the Dedication paragraph to include signature lines for all property owners per the Title Report. Per the submitted Title Report both Martin J Weil and Deirdre McGuire Weil are the trustees of the McGuire Weil Family Trust therefore both must sign the Final Plat Dedication Paragraph. Verify that the signature lines are updated to read per the Title Report.

6) DS Sec.2-03.6.6.A: Revise the CC&R Title, cover page and all references within the CC&Rs to accurately reflect the proposed Final Plat. Revise the following information within the CC&Rs:

a) Revise the Title Section to accurately label all proposed common elements and limited common elements, with descriptions per the Title Block. Either the CC&Rs or the Title Block must be revised and must match with exact wording for the descriptions of all elements.

b) A final signed original notarized copy of the CC&Rs will be required prior to approval of the Final Plat.

c) Provide an accurate legal description as called out in Exhibit A, but not shown.

7) DS Sec.2-03.7.1.G: The final plat cannot be scheduled for Mayor and Council consideration until one of the following has been provided:

a) Provide a copy of Certificate of Occupancy (CofO) paperwork accepted by the City of Tucson for the final construction of all buildings; or

b) If there is any remaining construction, financial assurances shall be submitted and approved.

GENERAL COMMENTS:

Provide a revised Final Plat, a revised original CC&R package and either a CofO or a Financial Assurance Package at re-submittal.

The revised Final Plat, CC&Rs and CofO/Assurance Package must address the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

Further comments may be generated upon resubmittal of the Final Plat and CC&Rs.

For questions or to schedule a meeting I can be reached at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
06/29/2009 JGREEN2 CC&R CC&R's Denied DATE: June 29, 2009
SUBJECT: Fairmount Villa Condominium Conversion Final Plat Submittal- Engineering Review
TO: Patricia Gehlen, CDRC Manager
LOCATION: 6145 & 6147 E Fairmount Street, T14S R14E Sec01 Ward 6
REVIEWERS: Jason Green, CFM
ACTIVITY: S09-036

SUMMARY: Engineering Division of Development Services Department has received, Sheet 1 thru 3 of the proposed Final Plat, a copy of the CC&Rs and a copy of the Title Report. Engineering Division has reviewed the submitted Final Plat, CC&Rs and Title Report and does not recommend approval of the Final Plat at this time. The following items need to be addressed:

FINAL PLAT COMMENTS:

1) DS Sec.2-03.6.1.H.1: Revise the title block on the proposed Final Plat and/or all applicable wording in the CC&Rs to match each other. All names, common elements, limited common elements, and descriptions must have the same wording in the CC&Rs as in the Title Block. Provide a clear definition for "Other Common Elements" as stated in the Common Elements "A" description within the Title Block. Verify if this is to include private/public sewers, utilities, water, etc.

2) DS Sec.2-03.6.1.H: Revise the Title Block to add "A Condominium Conversion Project" in the lower right corner of each Sheet.

3) DS Sec.2-03.6.1.K: Revise the Final Plat to indicate the subdivision cases number assigned (S09-036) where indicated by "# _____", it must be added to the lower right hand corner of the plans on all sheets.

4) DS Sec.2-03.6.4.A: Revise the Final Plat to label all streets as "Public." Specifically Lee Street and Alamo Avenue as shown on Sheet 2.

5) DS Sec.2-03.6.3.B.1: Revise the Dedication paragraph to include signature lines for all property owners per the Title Report. Per the submitted Title Report both Martin J Weil and Deirdre McGuire Weil are the trustees of the McGuire Weil Family Trust therefore both must sign the Final Plat Dedication Paragraph. Verify that the signature lines are updated to read per the Title Report.

6) DS Sec.2-03.6.6.A: Revise the CC&R Title, cover page and all references within the CC&Rs to accurately reflect the proposed Final Plat. Revise the following information within the CC&Rs:

a) Revise the Title Section to accurately label all proposed common elements and limited common elements, with descriptions per the Title Block. Either the CC&Rs or the Title Block must be revised and must match with exact wording for the descriptions of all elements.

b) A final signed original notarized copy of the CC&Rs will be required prior to approval of the Final Plat.

c) Provide an accurate legal description as called out in Exhibit A, but not shown.

7) DS Sec.2-03.7.1.G: The final plat cannot be scheduled for Mayor and Council consideration until one of the following has been provided:

a) Provide a copy of Certificate of Occupancy (CofO) paperwork accepted by the City of Tucson for the final construction of all buildings; or

b) If there is any remaining construction, financial assurances shall be submitted and approved.

GENERAL COMMENTS:

Provide a revised Final Plat, a revised original CC&R package and either a CofO or a Financial Assurance Package at re-submittal.

The revised Final Plat, CC&Rs and CofO/Assurance Package must address the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments.

Further comments may be generated upon resubmittal of the Final Plat and CC&Rs.

For questions or to schedule a meeting I can be reached at 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
07/01/2009 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved
07/02/2009 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

JENNIFER STEPHENS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: JENNIFER STEPHENS, ADDRESSING OFFICIAL
SUBJECT: S09-036 FAIRMOUNT VILLA CONDOMINIUMS/FINAL PLAT
DATE: 7/02/09



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Delete 13-09 on Location Plan.
Shade in only the portion to be resubdivided on Location Plan.
Correct scale on page 3.
07/09/2009 FERNE RODRIGUEZ PIMA COUNTY WASTEWATER Approv-Cond July 8, 2009

To: Lou Catallini, P.E.
BAKER & ASSOCIATES ENGINEERING

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

From: Chandubhai C. Patel, P.E., Civil Eng. Manager
Development Review Division (Wastewater)

Subject: FAIRMOUNT VILLA CONDOMINIUMS, UNITS 1-6
And Common Elements “A”-“C” and Limited Common Elements “D” & “E”
A Condominium Conversion Project
Final Plat -1st Submittal, S09-036



The drawings for the proposed Final Plat for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWRD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

GENERAL: It is understood by talking to the Engineer that this is a Condominium Conversion Project.

ALL SHEETS: Indicate in the Title Block that this is a Condominium Conversion Project.

SHEET 1: Add a General Note that states:

THIS IS A CONDOMINIUM CONVERSION PROJECT. ALL SEWERS ARE EXISTING AND PRIVATE. NO NEW SEWERS ARE PROPOSED.

SHEET 1: add A General Note that states:

THE ON-SITE SANITARY SEWERS, EXCEPT PUBLIC SEWERS WITHIN PUBLIC SEWER EASEMENTS OR RIGHTS-OF-WAY, ARE PRIVATE AND WILL BE OPERATED AND MAINTAINED ON A PRIVATE BASIS BY THE DULY FORMED ASSOCIATION OF THE HOME OWNERS.

5. SHEET 1: DEDICATION: Second Paragraph, Last but one line: Following the words FOR THE, add WORDS SANITARY SEWERS AND



6. The corrections may be shown on the mylars. A fee of $50.00 will be charged to certify that the corrections have been made.

SUBJECT TO THE ABOVE, the Pima County Department of Environmental Quality and the Regional Wastewater Reclamation Department CONDITIONALLY approve the above referenced submittal of the Final Plat as received by us on June 04, 2009.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization will need to be obtained from the PDEQ.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.

If you have any questions regarding the above comments, please do not hesitate to contact me.
07/13/2009 JWILLIA4 ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

July 13, 2009

Lou Catallini, P.E.
Baker & Associates Engineering, Inc.
3561 E. Sunrise Dr. Suite 225
Tucson, Arizona 85718

Subject: S09-036 Fairmount Villa Condominiums Final Plat

Dear Mr. Catallini:

Your submittal of June 4, 2009 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a set of 9 DETAILED cover letters explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

9 Copies Revised Final Plat (Fire, HC Site, Building-Com, Assessor, TEP, Zoning, Engineering, Addressing, DSD)

2 Copies CC&R's (Engineering, DSD)

2 Copies C of O / Assurance Package (Engineering, DSD)

Should you have any questions, please call me at 837-4919.


Sincerely,




John Williams
Planning Technician

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: (520) 318-1930