Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Plan Number: S09-026
Parcel: Unknown

Review Status: Completed

Review Details: FINAL PLAT REVIEW

Plan Number - S09-026
Review Name: FINAL PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/19/2009 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
06/26/2009 TERRY STEVENS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: S09-026
Alvernon and Lee Offices
Final Plat

TRANSMITTAL: 06/26/2009

DUE DATE: 07/08/09

COMMENTS:


1. The Zoning Review Section approves the final plat for this subdivision, subject to the following changes on the executed final plat. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised final plat to verify that those changes do not affect any zoning requirements.

2. Remove the sight visibility triangle lines indicated along the north property line.

3. Add the number of lots and the common areas to the title on page one of the CC&Rs.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961


TLS C:\planning\cdrc\finalplat\S09-026fpca.doc
06/26/2009 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)
FROM: Joyce Hays, Section Supervisor
Pima County Assessor’s Office
Mapping Department

DATE: 06/26/09


RE: Assessor’s Review and Comments Regarding Final Plat S09-026, Alvernon and Lee Offices


* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

X Plat meets Assessor’s Office requirements.
_______ Plat does not meet Assessor’s Office requirements.

COMMENTS: Thank you for your submittal.

NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.
07/02/2009 FERNE RODRIGUEZ COT NON-DSD REAL ESTATE Approved Per 5/19/04 (Michale Grasser) and 5/21/04 (Tanya Grahn/Presideo Eng.) confirmations, a "cross-access easement" Dkt/Pg. 13562/975, is established for offsite access to APN 122-13-211B.
07/02/2009 FERNE RODRIGUEZ COT NON-DSD TUCSON AIRPORT AUTHORITY Approved To Whom It May Concern:



Thank you for the opportunity to comment on S09-026, a request for final
plat review on a site located at the northeast corner of Alvernon and
Lee. The proposed use is professional offices.



This site is not within the Tucson International Airport or Ryan
Airfield public disclosure areas or traffic pattern airspace.



The Tucson Airport Authority does not oppose this application.



Please contact me if you have any questions or concerns.



Respectfully,



Jordan D. Feld, AICP

Director of Planning

Tucson Airport Authority

7005 S. Plumer Ave.

Tucson, AZ 85756

jfeld@tucsonairport.org

www.tucsonairport.org

(520) 573-5115 office

(520) 573-8006 fax
07/08/2009 PAUL MACHADO ENGINEERING REVIEW Denied To: Patricia Gehlen DATE: July 8, 2009
CDRC/Zoning Manager

SUBJECT: Alvernon & Lee Offices, 1602 N. Alvernon Way
Final Plat S09-026 (First Review)
T14S, R14E, Section 03

RESUBMITTAL REQUIRED: Final Plat.

The Final Plat (FP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Final Plat:

1. Please include a response letter to the comments along with the corrected copies of the FP.
2. Submit the Subdivision Improvement Assurances for review. The following items are required in the assurance package if a Third Party Trust Agreement will be used:
" Title Report
The title report was not included in the FP package.
3. Submit the above documents containing original signatures, copies of the documents and signatures will not be forwarded to the City of Tucson attorney for review.
4. Show dimensions between the future and existing r-o-w on detail 1. Also show more dimensions on detail 1 to tie down the detail with the survey.
5. Show detention/retention areas in a surveyable and readily retraceable manner. The detention/retention areas are not directly adjacent to the bldgs, this should be reflected on the survey.
6. All boundary monumentation must be labeled as "found" or "set." The monument at the intersection of Lee St. and Sycamore Blvd. is showing a monument that is found but calls out a monument to be "set" per the legend. Revise as required.
7. Please submit a copy of the subdivision boundary closure calculations.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax,
C:/1602 N. Alvernon Way_FP
07/09/2009 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207


JENNIFER STEPHENS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: JENNIFER STEPHENS, ADDRESSING OFFICIAL
SUBJECT: S09-026 ALVERNON AND LEE OFFICES/FINAL PLAT
DATE: 7/06/09



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.






***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through Pima
County Addressing. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County’s
Geographic Information System. Your support is greatly appreciated.***
07/13/2009 PGEHLEN1 CC&R CC&R's Approv-Cond see zoning and engineering comments.
07/14/2009 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved >>> <LCastillo@tep.com> 07/15/2009 7:12 AM >>>
TEP approves the final plat submitted June 19, 2009.
07/14/2009 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved
07/20/2009 FERNE RODRIGUEZ PIMA COUNTY WASTEWATER Approv-Cond July 20, 2009

To: JOHN WOOD
PRESIDIO ENGINEERING, INC

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

From: Chandubhai C. Patel, P.E., Civil Eng. Manager
Development Review Division (Wastewater)

Subject: ALVERNON & LEE OFFICES, LOTS 1-5 & COMMON AREAS "A AND B"
Final Plat – 1st Submittal
S09-026


The drawings for the proposed Final Plat for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWRD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

We will send to your office via e-mail, a pdf file containing a Sewer Service Agreement for the proposed development. Three originals will need to be printed out from this file for notarized signatures by the Owner of Record. The three signed originals of the Agreement must be returned to this office in order to satisfy the necessary requirements needed to approve the Mylars of the final plat.

SUBJECT TO THE ABOVE, the Pima County Department of Environmental Quality and the Regional Wastewater Reclamation Department hereby approve the above referenced submittal of the Final Plat received by us on June 19, 2009.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.

If you have any questions regarding the above comments, please do not hesitate to contact me.
07/23/2009 JWILLIA4 ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

July 23, 2009

Tanya Grahm
Presidio Engineering
4582 N. 1st Avenue Suite 120
Tucson, Arizona 85718

Subject: S09-026 Alvernon and Lee Offices Final Plat

Dear Tanya:

Your submittal of June 19, 2009 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a set of 3 DETAILED cover letters explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

3 Copies Revised Final Plat (Engineering, PC Wastewater, DSD)

2 Copies Boundary Closure Calculations (Engineering, DSD)

2 Copies Title Report (Engineering, DSD)

3 Copies CC&R's (Zoning, Engineering, DSD)

2 Copies Assurances (Engineering, DSD)

Should you have any questions, please call me at 837-4919.


Sincerely,



John Williams
Planning Technician

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: (520) 795-6747