Plan Review Detail
Review Status: Completed
Review Details: FINAL PLAT REVIEW
Plan Number - S09-023
Review Name: FINAL PLAT REVIEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/25/2010 | FERNE RODRIGUEZ | START | PLANS SUBMITTED | Completed | |
10/25/2010 | FERNE RODRIGUEZ | COT NON-DSD | REAL ESTATE | Passed | |
11/10/2010 | JENNIFER STEPHENS | PIMA COUNTY | ADDRESSING | Denied | 201 N. STONE AV., 2ND FL TUCSON, AZ 85701-1207 AUDREY FARENGA ADDRESSING REVIEW PH #: 740-6800 FAX #: 623-5411 TO: CITY PLANNING FROM: AUDREY FARENGA, ADDRESSING REVIEW SUBJECT: S09-023 TRIPLE CROWN VILLAS TOWNHOMES/FINAL PLAT DATE: November 9, 2010 The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval: Include re-subdivision information on all Title Blocks. Change Desert Steppes Estates Lots 195-170 to Lots 195-470 on sheet 2. Delete all adjacent tax codes. Change War Adminiral Place to War Admiral Place. |
11/16/2010 | STEVE SHIELDS | ZONING | REVIEW | Denied | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Lead Planner PROJECT: Triple Crown Villas S09-023 (1st Review) Final Plat TRANSMITTAL DATE: November 16, 2010 DUE DATE: November 23, 2010 COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. The Zoning Review Section conditionally approves the tentative plat for this subdivision, subject to the following changes on the executed tentative plat. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised tentative plat to verify that those changes do not affect any zoning requirements. 2. D.S. 2-03.6.1.H.3 As this is a resubdivision of a previously recorded plat, indicate the title and the book and page reference of the existing subdivision within the title block. 3. D.S. 2-03.6.1.K Place the S09-023 subdivision case number assigned to the approved tentative plat in the lower right corner of the plat next to the title block. Remove the S06-064 case number as it is not relevant. 4. D.S. 2-03.6.1.K The DSMR number DSMR 06-19 shown in the title block is not correct and or required for the final plat. 5. D.S. 2-03.6.1.J Revise General Note 5 to include "WHICH ESTABLISHED ZONING IN THE PANTANO ANNEXATION AREA". 6. D.S. 2-03.6.3.D Revise the APPROVAL BLOCK as follows; change the name from "KATHLEEN S. DETRICK" to "ROGER W. RANDOLPH", and add the signature line and date as shown in D.S. 2-03.6.3.D. 7. D.S. 2-03.6.3.E Under the ASSURANCES revise the signature line for the "CITY OF TUCSON DEVELOPMENT SERVICES DEPARTMENT DIRECTOR" to read "CITY OF TUCSON PLANNING AND DEVELOPMENT SERVICES DEPARTMENT DIRECTOR" 8. D.S. 2-03.6.6 The title of the declaration of covenants, conditions and restrictions should match what is shown in the title block of the final plat. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 791-5608 ext. 1180. C\planning\cdrc\finaplat\S09-023fp.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised final plat & CC&R's. |
11/16/2010 | LIZA CASTILLO | UTILITIES | TUCSON ELECTRIC POWER | Denied | SUBJECT: Triple Crown Villas Lots 1-30 S09-023 Tucson Electric Power Company (TEP) has reviewed the final plat submitted October 26, 2010. TEP is unable to approve the plat at this time. In order for TEP to approve the final plat, the following will be required. * The 10' TEP easement shown within Common Area C must continue to the property line. (see the area in red on the attached pdf file) * The third paragraph of the dedication can be deleted. This sentence is repeated in the next paragraph. Show the requested changes on the resubmittal of the final plat. Submit a copy to the City of Tucson for TEP's final approval. Please contact me at (520) 917-8745 if you have any questions. Liza Castillo Right of Way Agent II Tucson Electric Power Co. offc-(520) 917-8745 fax-(520) 545-1416 lcastillo@tep.com <mailto:lcastillo@tep.com> |
11/22/2010 | FERNE RODRIGUEZ | PIMA COUNTY | WASTEWATER | Denied | November 22, 2010 To: Diana Floyd Thumm Physical Resource Engineering Thru: Patricia Gehlen, CDRC Manager City of Tucson Development Services Department From: Chandubhai C Patel, P.E., Civil Eng. Manager Development Review Division ( Wastewater) Subject: Tripple Crown Villas Townhomes, Lots 1-30, Common Areas “A”, “B” “C”& “D” Final Plat – 1st Submittal S09-023 The drawings of the Final Plat for the proposed project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWRD).This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use. 1. Sheet 1:DEDICATION, 4th para, 1st line: Add PIMA COUNTY between PUBLIC and AND. 2. Sheet 1: OWNER: The name should be First American Title Insurance Company as Trustee of Trust No. 9253 3. All Sheets: Show the case no. S09-023 The next submittal of this project will be the second (2nd) submittal. A check for the review fee of this submittal in the amount of $50.00 (made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines . If you have any questions regarding the above comments, please do not hesitate to contact me. |
11/23/2010 | PAUL MACHADO | ENGINEERING | REVIEW | Denied | To: Patricia Gehlen DATE: November 23, 2010 CDRC/Zoning Manager SUBJECT: Triple Crown Villas, 1149 S. Sarnoff Dr. Final Plat S09-023 (First Review) T14S, R15E, Section 16 RESUBMITTAL REQUIRED: Final Plat. The Final Plat (FP) cannot be approved as submitted. Please address the following review comments prior to the next submittal. Final Plat: 1. Please include a response letter to the comments along with the corrected copies of the FP. 2. Submit the Subdivision Improvement Assurances for review. The following items are required in the assurance package if a Third Party Trust Agreement will be used: " Title Report " Special Warranty Deed " Trust Agreement " Amendment to Trust " Agreement to Construct 3. Submit the above documents containing original signatures, copies of the documents and signatures will not be forwarded to the City of Tucson attorney for review. 4. Please re-label all common areas that may be used in a dual and/or single use capacity per D.S. 2-03.6.4.C. For example, a Ret./Det. Basin may also be used as a recreation facility or only as a drainage facility or drainage channel and this must be reflected on the Final Plat. A key note explaining the labels could be used in conjunction with the labels, ie.: " Common Area "A" - Streets " Common Area "B" - Drainage/Recreation Facilities " Common Area "C" - Recreation Facilities " Common Area "D" - Drainage Facilities " Common Area "E" - Landscaping 5. All lettering and dimensions will be the equivalent of twelve (0.12) point or greaterin size. The purpose of this requirement is to assure that all lettering is legible when reproduced or when photographically reduced (microfilmed) for recordkeeping purposes. 6. Place the words "Book ____ Page ____" in both the upper and lower right corners outside the margin line. The blanks will be completed by the Pima County Recorder's Office at the time of recordation. 7. All signatures and blanks on the plat must completed prior to approval. 8. The electrical easement shown on the north property line and the drainage easement that is noted to be recorded in Bk16/1but is not shown on that plat. 9. The transformer and electrical easements on the north property line are not tied down or surveyable. Perhaps a detail of the more crowded areas is warranted. Revise as required. 10. The title of the CCR's does not match the title of the FP. The titles, assurances included, must match each other verbatim. Also page 1 of the CCR's is missing. 11. Correct the name of the clerk of the City of Tucson to the current clerk. 12. A title block with the following information is to be provided in the lower right corner of each sheet. 1. Subdivision name; number of blocks, lots, and/or units; and common area. 2. Legal description by section, township, and range. 3. If the final plat is a resubdivision of a previously recorded plat, indicate the title and the book and page reference of the existing subdivision. 13. The S(YR)-___ subdivision case number assigned to the approved tentative plat will be placed in the lower right corner of the plat next to the title block. If the property is subject to a rezoning case, the C9-__-__ rezoning case number is to be noted also. 14. A legend which shows and describes all symbols used on the drawing will be placed on either the first sheet of the plat or the first sheet which contains all or part of the subdivision drawing. 15. The lot for unit no. 19 is encroaching onto common area a. Is it part of the lot, the common area or the ped. easement? Please explain. 16. Identify each block or lot within the subdivision boundary by number, and include the square footage of each. This comment is for lot no. 19. 17. Provide location, dimensions, areas in square footage, and purposes of lots proposed for dedication (such as open spaces, recreation areas, and natural areas) or for reservation for a public use (such as public parks, water facilities, and school sites). The drainage area in common area b shall include that it is also a Drainage basin. 18. All boundary monumentation must be labeled as "found" or "set." a. Fully describe and show all markings on found monuments with the registrants number and/or "No tag". b. A one-half (½) inch iron rod tagged by a registered land surveyor will be set at all corners upon completion of construction. 19. Show the distance and bearing between all monuments used. Indicate whether measured or calculated. Measured is the physical, direct occupation of a point/line by line of sight and not through calculations of other measured distances. Check the arc distance for Sarnoff Drive. 20. Indicate tract boundary lines; right-of-way and centerlines of streets, easements, and other rights-of-way; and property lines of residential lots and other sites, with accurate dimensions, bearings, or deflection angles and radii, arcs, and central angles of all curves. Show centerline information for Whirlaway Lane. 21. Please submit a copy of the subdivision boundary closure calculations. If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov Paul P. Machado Senior Engineering Associate City of Tucson - Planning and Development Services Department 201 N. Stone Avenue P.O. Box 27210 Tucson, Arizona 85726-7210 (520) 837-4932 office (520) 879-8010 fax C:/1149 S. Sarnoff Dr. FP |
11/24/2010 | PGEHLEN1 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Approved | |
11/24/2010 | ED ABRIGO | PIMA COUNTY | ASSESSOR | Approved | Office of the Pima County Assessor 115 N. Church Ave. Tucson, Arizona 85701 BILL STAPLES ASSESSOR TO: CDRC Office Subdivision Review City of Tucson (FAX# 791-5559) FROM: Sherry Hyde Senior Property Technician Pima County Assessor’s Office DATE: 11/24/10 RE: Assessor’s Review and Comments Regarding S09-023 TRIPLE CROWN VILLAS TOWNHOMES * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * X Plat meets Assessor’s Office requirements. _______ Plat does not meet Assessor’s Office requirements. COMMENTS: THANK YOU FOR YOUR SUBMITTAL! NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED. |
11/29/2010 | JOHN WILLIAMS | ZONING-DECISION LETTER | REVIEW | Denied | COMMUNITY DESIGN REVIEW COMMITTEE PLANNING & DEVELOPMENT SERVICES November 29, 2010 D. Floyd Thumm Physical Resource Engineering 4655 N Flowing Wells Road Tucson, Arizona 85705 Subject: S09-023 TRIPLE CROWN VILLAS Final Plat Dear Floyd: Your submittal of October 26, 2010 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a set of 6 DETAILED cover letters explaining how each outstanding requirement has been addressed: ALL BLACKLINES MUST BE FOLDED 6 Copies Revised Final Plat (Addressing, TEP, Zoning, Wastewater, Engineering, PDSD) 2 Copies Boundary Closure Calculations (Engineering, PDSD) 3 Copies Revised CC&R's (Engineering, Zoning, PDSD) 2 Copies Assurance Package (Engineering, PDSD) Should you have any questions, please call me at 837-4893. Sincerely, John Williams Planning Technician All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/ Via fax: 520-690-1769 |