Plan Number: S09-023
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW

Plan Number - S09-023
Review Name: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2010 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Steve Shields
Lead Planner

PROJECT: Triple Crown Villas
Tentative Plat
S09-023 (2nd Review)

TRANSMITTAL DATE: January 4, 2010

DUE DATE: January 6, 2010

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a tentative plat. If, at the end of that time, the tentative plat has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this tentative plat is March 25, 2010.

2. This comment was not addressed. Per D.S. 2-08.3.1 Within a pedestrian circulation path, an accessible route is also required. The accessible route must connect all areas of the development and the pedestrian circulation path located in any adjacent streets. This accessible route may be identical to pedestrian circulation path. The areas within the development which must be connected include, but are not limited to, all places of public accommodation, all buildings, etc. It appears that there are proposed steps located within the required accessible route from the proposed eastern most units. Clearly show the accessible route from units 24-28 to Sarnoff Drive.

3. Depending on how the above comments are addressed additional comments may be forth coming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\cdrc\tentativeplat\S09-023tp.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised tentative plat, and additional requested documents.
01/05/2010 RONALD BROWN ZONING HC REVIEW Approv-Cond 1. General note number 17 was added to include Inclusive Home Design Ordinance not note number 18 as per response.
2. As per our conference with LeeRay and myself, Section 1003.2 of the Inclusive Home Design Ordinance, accessible entrance from the garage is allowed. We did not conclude that access is not required for all units. All units must be accessible as per this section of the Inclusive Home Design Ordinance.
3. OK
01/06/2010 LOREN MAKUS ENGINEERING REVIEW Approv-Cond DATE: January 6, 2010
SUBJECT: Triple Crown Villas, 1149 S. Sarnoff Rd.
Tentative Plat S09-023 (Second Review)

RESUBMITTAL REQUIRED: None, Conditional Approval

The Subdivision Plat (SP) and Drainage Report (DR) can be approved with the following conditions.

Tentative Plat:
1. Revise the Title Block to indicate that this is a resubdivision of a portion of a previous subdivision.
2. Placement of fill in excess of 2' above existing grade at any location in the outer 100' of the developing site is not allowed and/or shall meet the requirements per D.S. 11-01. It is acknowledged that the issue must be resolved before the grading plan is approved. However, if the differential grading is not approved, a revised tentative plat will be required.
3. The water harvesting features are not complete. Additional detail will be required on the grading plans to demonstrate that water harvesting will be utilized to the maximum amount possible for all landscaped areas.


If you have any questions, I can be reached at 837-4927 or loren.makus@tucsonaz.gov
Loren Makus, EIT
Senior Engineering Associate
01/07/2010 JOE LINVILLE LANDSCAPE REVIEW Approved
02/03/2010 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES

January 8, 2010

Kent A. Delph, P.E.
Grenier Engineering, Inc.
5517 E. 5th Street
Tucson, Arizona 85711

Subject: S09-023 Triple Crown Villas Tentative Plat

Dear Kent:

Your submittal of March 26, 2009 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a set of 4 DETAILED cover letters explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

4 Copies Revised Tentative Plat (Zoning, Engineering, HC Site, PDSD)

Should you have any questions, please call me at 837-4919.


Sincerely,






John Williams
Planning Technician

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: (520) 326-7508
02/03/2010 JOHN WILLIAMS ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
PLANNING & DEVELOPMENT SERVICES
***REVISED***
February 3, 2010

Kent Delph
Grenier Engineering, Inc.
5517 East 5th Street
Tucson, Arizona 85711

Subject: S09-023 Triple Crown Tentative Plat

Dear Kent:

The above referenced plan has been CONDITIONALLY APPROVED by the Community Design Review Committee, subject to the revisions required on the blue lines per the on-line comments. Please submit the following documents for sign-off:

1 Blue line set of the Plat, Landscape Plan and NPPO. Please include applicable sheets from any other concurrent reviews.

1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

Additional black line copies will be made from the complete set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your blue lines to the CDRC office for sign-off approval. Your printing company will deliver the original stamped blue line set to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

Please note that the final plat must be approved by Mayor and Council and recorded within one year of date of approval of the tentative plat per LUC 4.1.7.3.

PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.tucsonaz.gov/dsd/CDRC___Rezoning/CDRC/CDRC_Stamp/cdrc_stamp.html. BLUELINE SETS THAT DO NOT HAVE THE STAMP WILL BE RETURNED FOR CORRECTION.

Should you have any questions, please call me at 837-4919.

Sincerely,



Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 1 505 327-1517
12/07/2009 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
12/07/2009 RONALD BROWN ADA REVIEW Passed Not a COT owned/operated project
12/16/2009 FERNE RODRIGUEZ PIMA COUNTY WASTEWATER Approved December 15, 2009

To: KENT DELPH
DELPH ENGINEERING INC.

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

____________________________________________
From: Tom Porter, Sr. CEA (520-740-6719), representing the Pima County Departments of Regional Wastewater Reclamation Department and Environment Quality

Subject: TRIPLE CROWN VILLAS TOWNHOMES, LOTS 1-30, COMMON AREA "A", "B", "C" AND "D"
Tent. Plat – 2nd Submittal
S09-023


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWRD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the tentative or preliminary plat as submitted.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you have any questions regarding the above-mentioned comments, please contact me.