Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Plan Number: S09-019
Parcel: Unknown

Address:
2008 E RIVER RD

Review Status: Completed

Review Details: FINAL PLAT REVIEW

Plan Number - S09-019
Review Name: FINAL PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2009 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
03/30/2009 FERNE RODRIGUEZ PIMA COUNTY WASTEWATER Passed Per CC Patel, no need to review two final plats.
04/06/2009 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved
04/07/2009 DAVID MANN COT NON-DSD FIRE Approved
04/15/2009 ED ABRIGO PIMA COUNTY ASSESSOR Denied Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)

FROM: Joyce Hays, Section Supervisor
Pima County Assessor’s Office
Mapping Department

DATE: 04/09/09


RE: Assessor’s Review and Comments Regarding Final Plat S09-020, Placita Escondida II, 13-14-20


* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Plat meets Assessor’s Office requirements.
___X___ Plat does not meet Assessor’s Office requirements.

COMMENTS: To be approved, the common areas must be labeled with the name and square footage of each, and with the dimensions and bearings of the common area lines.
Brian Sloan
Pima County Assessor’s Office
Deeds/Splits/Mapping
740-4395

NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.
04/16/2009 RONALD BROWN ZONING HC SITE REVIEW Approved
04/16/2009 FERNE RODRIGUEZ COT NON-DSD TUCSON AIRPORT AUTHORITY Approved To Whom It May Concern:

Thank you for the opportunity to comment on S09-019 Placita Escondida I
and S09-020 Placita Escondida II, final plat review applications for
sites located south and east of the southeast corner of River and
Campbell. The sites are not within the Tucson International Airport or
Ryan Airfield public disclosure areas or traffic pattern airspace.

The Tucson Airport Authority does not oppose the subject applications.

Please contact me if you have any questions or concerns.

Respectfully,


Jordan D. Feld, AICP

Director of Planning

Tucson Airport Authority

7005 S. Plumer Ave.

Tucson, AZ 85756

jfeld@tucsonairport.org

www.tucsonairport.org

(520) 573-5115 office

(520) 573-8006 fax

c - file
04/17/2009 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Denied SUBJECT: Placita Escondida I
S09-019
Tucson Electric Power Company (TEP) has reviewed the final plat
submitted March 30, 2009. TEP is unable to approve the plat at this
time.
In order for this Company to approve the final plat, the following is
required:
* Add the following paragraph to the dedication:
"An easement is granted for the purpose of access, installation
replacing repairing and maintenance of electrical meters, cable and
conduits, which grouped electrical meters are attached to the exterior
walls."
Show the dedication on the re-submittal of the plat and submit one copy
of the plat to the City of Tucson for TEP's final approval.
Please contact me at (520) 917-8745 if you have any questions.


Liza Castillo, Right of Way Agent II
Tucson Electric Power Co.
Unisource Energy Services
offc-(520) 917-8745
fax-(520) 545-1416
lcastillo@tep.com
04/23/2009 ANDY STEUART COT NON-DSD REAL ESTATE Denied Comments provided 4/23/09 by Andy Steuart, Property Agent, City Manager's Office/Real Estate Program, (520) 837-6715

The following are requested for Sht. 1 of 5:
1. Under Dedication, 4th paragraph, add a "period" at the end of sentence "No overhead lines shall be used."
2. Under Beneficiary, change City Clerk's name to Roger Randolph.
3. Under Recording Data, a space is needed for the month.
4. Provide a "cross-access easement" (or like provision) for access purposes concerning Agro Farms Sub. and proposed Placita Escondida Condominiums II.

The following are requested for Sht. 2 of 5:
1. Delineate and label the channel of the Camino Real Wash.
2. Show final configuration of Easement for river bank protection & linear parklocation of Dkt./Pg. 8725/1170 & 1174
3. Request validation if two easements, recorded in Miscellaneous Bk. 75 Pg. 247 (comm. fac.) and Misc. Bk. 92 Pg. 548 (util.) are relevant to have locations annotated.
4. Per Keynote 8, request location be annotated.
04/27/2009 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Steve Shields
Lead Planner

PROJECT: Placita Escondida I - Condo Conversion - Final Plat
S09-019
Final Plat

TRANSMITTAL DATE: April 27, 2009

DUE DATE: April 27, 2009

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a plat. If, at the end of that time, the plat has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this tentative plat is March 29, 2010.

2. D.S. 2-03.6.1.K Place the S09-019 subdivision case number assigned to the plat in the lower right hand corner of the plat next to the title block.

3. D.S. 2-03.6.2.D Provide a general note stating "This plat is subject to the conditions of rezoning case number Co9-95-04, unless superseded by a subsequent rezoning ordinance."

4. D.S. 2-03.6.3.D In the Approval block revise the name to be "Roger W. Randolph".

5. D.S. 2-03.6.3.D Revise the Recording Data block to read "FILED FOR RECORD AT".

6. D.S. 2-03.6.4.C General note 4 references "COMMON ELEMENT", the title block and other sheets reference "COMMON AREAS", as this is a Condo plat all of these references should be "COMMON ELEMENTS" and/or "LIMITED COMMON ELEMENTS".

7. Provided documentation that supports how this condo conversion meets the requirements of LUC Section 4.1.9.2.

8. D.S. 2-03.6.6 The table of context page numbers, for both sets of provided CC&Rs do not match the pages of the text.

9. Sheet 2 Common Area Designation "C" states "SEE SHEET 4 OF 7", revise this to read "SEE SHEET 4 OF 5".

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C\planning\cdrc\finaplat\S09-019fp.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised final plat, and additional requested documents.
04/27/2009 LOREN MAKUS ENGINEERING REVIEW Denied April 27, 2009
S09-019
Reviewed by Loren Makus, EIT
Resubmittal Required: Plat, CC&Rs
1. Provide a complete copy of the Declaration of Condominium and of Covenants, Conditions and Restrictions. Ensure that the Table of Contents is correct and provides correct references to all of the sections.
2. Clearly identify on the plat that the residents and visitors to all areas of the two condominiums have access rights to all roadways and parking areas.
3. Address the status of the assurances of the existing project and how they will affect the proposed resubdivision.
04/27/2009 LMAKUS1 CC&R CC&R's Denied April 27, 2009
S09-019
Reviewed by Loren Makus, EIT
Resubmittal Required: Plat, CC&Rs
1. Provide a complete copy of the Declaration of Condominium and of Covenants, Conditions and Restrictions. Ensure that the Table of Contents is correct and provides correct references to all of the sections.
2. Clearly identify on the plat that the residents and visitors to all areas of the two condominiums have access rights to all roadways and parking areas.
3. Address the status of the assurances of the existing project and how they will affect the proposed resubdivision.
04/30/2009 JENNIFER STEPHENS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

JENNIFER STEPHENS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: JENNIFER STEPHENS, ADDRESSING OFFICIAL
SUBJECT: S09-019 PLACITA ESCONDIDA I/FINAL PLAT
DATE: 4/28/09



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

Delete all owners and dockets and pages on Location Map.
Point Camino Real to the correct location on Location Map.
Should he eastern most storage and garage building be labeled 20?
Where is building 11?
05/01/2009 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

May 1, 2009

Michael Censky
HSL Construction Services, LLC
3901 East Broadway Blvd
Tucson, Arizona 85711

Subject: S09-019 Placita Escondida I Final Plat

Dear Mike:

Your submittal of March 30, 2009 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and 7 sets of the DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

7 Copies Revised Final Plat (Assessor, TEP, Real Estate, Zoning, Engineering, Addressing, DSD)

2 Copies LUC Affidavit (Zoning, DSD)

3 Copies CC&R's (Zoning, Engineering, DSD)

Should you have any questions, please call me at 837-4919.




Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 322-6535
fpresubmittal