Parcel: Unknown

Address:
1523 N BRYANT AV

Review Status: Completed

Review Details: FINAL PLAT - CONDO CONVERSION

Plan Number - S08-103
Review Name: FINAL PLAT - CONDO CONVERSION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2008 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
08/19/2008 DAVID MANN COT NON-DSD FIRE Approved
08/21/2008 CDRC1 PIMA COUNTY WASTEWATER Denied August 20, 2008

To: PETER SOLONGA
ORACLE ENGINEERING GROUP, INC

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

___________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environment Quality

Subject: BRYANT CONDOMINIUMS UNITS 1-7 COMMON ELEMENT "A" AND LIMITED COMMON ELEMENTS "1-7"
Final Plat - 1st Submittal
S08-103


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

1. Sheet 1: Add a General Note that states:

THE ON-SITE SEWERS ARE EXISTING AND PRIVATE. NO NEW SEWERS ARE PROPOSED.

2. Sheet 1: In the Dedication Block, third paragraph, third line after the word PUBLIC add the words ,PIMA COUNTY.

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the final plat. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the second (2nd) submittal. A check for the review fee of this submittal in the amount of $50.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above-mentioned comments, please contact me.
08/21/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
08/29/2008 TERRY STEVENS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: S08-103
Bryant Condominiums
Final Plat

TRANSMITTAL: 08/29/2008

DUE DATE: 09/15/08

COMMENTS:


1. An applicant has one (1) year from the date of application to obtain approval and recordation of a final condominium plat that complies with zoning and other development requirements in effect at the time of application. This final condominium plat must be approved and recorded on or before 08/14/09.
2. DS 2-03.6.1.K Case number S08-103 has been assigned to this final plat. Please place this number in the right corner of all sheets of the final plat.
3. Per LUC 4.1.9.2 Please submit a copy of a report on the physical condition of all buildings, structures, and other improvements to the property to be subdivided prior to approval of a final plat by the Mayor and Council. This report shall be provided by the subdivider to all prospective purchasers of units prior to execution of a binding contract of purchase. The report shall contain the following.
a. A statement of the estimated fees or assessments, if any, that the purchaser of a unit will pay, on a monthly and yearly basis, for at least a two (2) year period following purchase.
b. (pest and termite report has been provided)
c. A statement of the unit's average monthly utility costs based on the preceding twelve (12) month period, where the subdivider has access to such utility cost data.
d. A report describing, to the best knowledge or estimate of the subdivider, the physical condition of elements of the structure, equipment, or appliances in a unit, the repair or replacement of which will be the responsibility of the purchaser. The report shall state the approximate date on which the element, equipment, or appliance was originally constructed or installed; the approximate date on which it was subsequently replaced or will likely require replacement; and the current estimated cost of replacement. This report shall not be construed to create any warranties, express or implied.
e. A report containing information to be obtained from the City Fire Department describing the extent to which the buildings and structures to be converted by the plat submitted by the subdivider deviate from applicable requirements of the Building Code, Tucson Code, Chapter 6, and the Fire Prevention Code, Tucson Code, Chapter 13, in the following specified areas of fire safety.
1. Accessibility of buildings and structures to fire-fighting equipment; and
2. Proximity and frequency of fire hydrants.

4. Corners of each building must be tied to the boundary with distance and bearing. See engineering comments.


If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

TLS C:\planning\cdrc\finalplat\S08-103fp.doc
09/08/2008 KAY MARKS PIMA COUNTY ADDRESSING Approv-Cond 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207


JENNIFER STEPHENS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: JENNIFER STEPHENS, ADDRESSING OFFICIAL
SUBJECT: S08-103 BRYANT CONDOMINIUMS/FINAL PLAT
DATE: 9/08/08



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

NOTE: ON FINAL MYLAR:

1.) Delete E. from E. Pima St. on Location Map.
2.) Delete all adjacent tax codes.




***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through Pima
County Addressing. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County's
Geographic Information System. Your support is greatly appreciated.***
09/08/2008 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: BRYANT CONDOMINIUMS

S08-103



Tucson Electric Power Co. (TEP) approves the final plat submitted August
15, 2008.

Please forward any resubmittals of the final plat to this office.



Electric service will be provided to this subdivision in accordance with
the rules and regulations approved by the Arizona Corporation
Commission.



Please contact me at (520) 917-8745 if you have any questions.




Liza Castillo, Right of Way Agent II
Tucson Electric Power Co.
Unisource Energy Services
offc-(520) 917-8745
fax-(520) 545-1416
lcastillo@tep.com <mailto:lcastillo@tep.com>
09/12/2008 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved
09/15/2008 ANDY STEUART COT NON-DSD REAL ESTATE Denied -Request Lawyers Title Agency of Arizona, LLC., an Arizona limited liability company, as Trustee under Trust No 18197-T be shown as the owner for Dedication and KBK LTD be shown as the Beneficiary. Please refer to C.O.T., Development Standard No. 2-03.6.3.B. & C. for additional information.
-Taxes for 2008 are not current as of 9/15/08.
-Request S08-____ show S08-103
09/15/2008 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
09/15/2008 LOREN MAKUS ENGINEERING REVIEW Denied September 15, 2008
S08-103

RESUBMITTAL REQUIRED: Revised Plat
The plat for Bryant Condominiums cannot be approved as submitted. Please provide a revised plat addressing the following comment:

Clearly identify the line segments, with distance and bearing that tie each building to the parcel corners. Units 5-7 do not appear to have clear ties.

If you have any questions, I can be reached at loren.makus@tucsonaz.gov or by phone at 520.837.4927.
09/17/2008 ED ABRIGO PIMA COUNTY ASSESSOR Denied Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)

FROM: Gary Ault, Mapping Supervisor
Pima County Assessor's Office
Mapping Department

DATE: 09/17/08


RE: Assessor's Review and Comments Regarding Final Plat S08-103, BRYANT CONDOMINIUMS


* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

Plat meets Assessor's Office requirements.
___X____Plat does not meet Assessor's Office requirements.


COMMENTS: 1: Lot lines must have bearings.
2: There must be a section tie, with a bearing and distance from a section corner. In the case of a resubdivision a tie, with a bearing and distance, to a lot within the original subdivision is acceptable.


NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.
09/19/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

September 19, 2008

Peter Salonga
Oracle Engineering Group
199 East Fort Lowell
Tucson, Arizona 85705

Subject: S08-103 Bryant Condominiums Final Plat

Dear Peter:

Your submittal of August 15, 2008 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

6 Copies Revised Final Plat (Wastewater, Zoning, Engineering, Real Estate, Assessor DSD)

2 Copies LUC Affidavit (Zoning, DSD)





Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 292-6144