Plan Number: S08-101
Parcel: Unknown

Address:
5975 S TUCSON BL

Review Status: Completed

Review Details: CORE REVIEW

Plan Number - S08-101
Review Name: CORE REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2008 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
08/12/2008 JIM EGAN COT NON-DSD FIRE Approved
08/18/2008 RONALD BROWN ZONING HC SITE REVIEW Denied 1. Add a Generel Note that all site and future home construction will be in compliance with COT Ordinance 10463, The Inclusive Home Design Ordinance, effective 1 JAN 08. This applies to all lots.
08/19/2008 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: TRES PUEBLOS ESTE

S08-101



Tucson Electric Power Company (TEP) has no objection to the preliminary
plat submitted for review August 11, 2008.



TEP will provide a preliminary electrical design on the Approved
Tentative Plat within (type out number) (15) working days upon receipt
of the plat. Additional plans necessary for preparation of the design
are: building plans including water, electrical, landscape, sidewalk
and paving plans. Also, submit the AutoCAD version of the plat on a CD
or email to lcastillo@tep.com <mailto:lcastillo@tep.com> .


Liza Castillo, Right of Way Agent II
Tucson Electric Power Co.
Unisource Energy Services
offc-(520) 917-8745
fax-(520) 545-1416
lcastillo@tep.com <mailto:lcastillo@tep.com>
09/03/2008 CDRC1 PIMA COUNTY WASTEWATER Denied September 2, 2008

To: DAN CASTRO
RICK ENGINEERING

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

___________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environment Quality

Subject: TRES PUEBLOS ESTE, LOTS 1-163 & COMMON AREAS "A-1" THRU "A-3" & "B-1" THRU "B-4"
Tent. Plat - 1st Submittal
S08-101


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

1. This project will be tributary to the Roger Road Wastewater Treatment Facility via the Southeast Interceptor. Obtain a letter from the PCWMD's Development Services Section, written within the past 90 days, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at:

http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf.

The tentative or preliminary plat for this project cannot be approved until a copy of this letter has been received by this office.

2. Sheet 1: Revise General Note #12 to read as follows:

THE ON-SITE SANITARY SEWAGE COLLECTION LINES WILL BE PUBLIC AND DESIGNED AND CONSTRUCTED TO PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT STANDARDS. ALL BUILDING CONNECTION SEWERS WILL BE PRIVATELY MAINTAINED.

3. Sheet 2-6: Show the size of pipe and material for the proposed public sewer line on plan.

4. Sheet 3: Show the complete IMS # for all of the existing public manholes shown on plan.

5. Sheet 3: The inverts shown for the existing public manhole #3696-39 do not correspond to the depth of manhole shown on Map Guide. Verify the values shown on plan.

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the tentative or preliminary plat. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the second (2nd) submittal. A check for the review fee of this submittal in the amount of $250.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above-mentioned comments, please contact me.
09/03/2008 KAY MARKS PIMA COUNTY ADDRESSING Approv-Cond 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207


JENNIFER STEPHENS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: JENNIFER STEPHENS, ADDRESSING OFFICIAL
SUBJECT: S08-101 TRES PUEBLOS ESTE/REVISED TENTATIVE PLAT
DATE: 9/02/08



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

NOTE: ON FINAL PLAT:

1.) Change Tucson Airport Commerce Center to Country Club Commerce Center on page 5.




***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through Pima
County Addressing. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County's
Geographic Information System. Your support is greatly appreciated.***
09/04/2008 ROGER HOWLETT COT NON-DSD URBAN PLANNING & DESIGN Denied DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S08-101 Tres Pueblos Este Core Review 9/4/09

Items reviewed: Tentative Plat and Landscape Plan

Related annexation, rezoning, CDRC cases: N/A

Land Use Plan: Kino Area Plan

Gateway or Scenic Route: Tucson Blvd. is a Gateway Route

COMMENTS DUE BY: 9/9/08

Please address the comments below, and resubmit the tentative plat and landscape plan:

1) Please show the phasing lines on the plat.

2) Please add recreational facilities (active or passive) in Common Areas B-1 and B-4, and show them on the plat and landscape plan.

3) Please revise the view wall detail on plat sheet 2/6, so that the solid masonry portion at the bottom is no higher than 2'-6".

4) The Rodeo Wash linear park needs to be constructed in entirety at the beginning of the project, with the road, and not in phases.

Please revise General Note #19 to read as follows: "Except for the Rodeo Wash linear park, all improvements and amenities …"

Please add a new General Note that says, " The Rodeo Wash linear park and related amenities, including but not limited to landscaping, must be completed, and accepted by the City of Tucson, prior to the issuance of the first occupancy permit for a residential unit."

5) Please revise the pathway detail so that 2-foot-wide clear areas are provided on each side of the trail, for a 14-foot (total) corridor width.
S08-101, Tres Pueblos Este



6) Regarding the trail easement, please change the wording on sheet 2/6 so that it reads as follows:

"90' public, non-motorized recreation and trail easement granted to the City of Tucson by final plat."

Please contact the reviewer below if you would like to discuss any of the above comments.

REVIEWED BY: Joanne Hershenhorn, 837-6965 or 791-4505
DATE: 9/4/08




























S:\Case_Review\CDRC\S08-101 Tres Pueblos Este Core Review.doc
09/08/2008 JOE LINVILLE LANDSCAPE REVIEW Approved
09/09/2008 ELIZABETH EBERBACH ENGINEERING REVIEW Denied TO: Patricia Gehlen; CDRC Manager
SUBJECT: Tres Pueblos II (Este) (S05-134) Subdivision Tentative Plat counter Engineering Review
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: S08-101

SUMMARY: Revised Tentative Plat package documents were submitted for core review. The revised Tentative Plat, revised Drainage Report, and Landscape documents were reviewed by Engineering. Development Services Department Engineering Division does not recommend approval at this time. The Drainage Report was reviewed for Tentative Plat purposes only.

PROJECT SAC SUMMARY: The Tres Pueblos Este project proposes encroachment into the Rodeo W.A.S.H. Ordinance wash. The existing Rodeo Wash is a constructed channel, approximately 8 feet deep and top width 80 feet, with earthen bottom and 3.5:1(H:V) side slopes. Proposed encroachment includes proposed basin outflow pipes with gabion outlet structures that cross the W.A.S.H. Study Area and continue into the wash channel slopes at two locations on the north and northwest sides of the project. A shallow weir is to be constructed outside of the 50-ft W.A.S.H. Study Area near one of the north basins to allow for sheet flow conditions across the W.A.S.H. Study Area. There is also proposed trail / maintenance road, paved pathways, weirs, scuppers, railing, basin channel, access ramps, and landscaping proposed within the Rodeo W.A.S.H. Study Area. A SAC meeting has been completed under S05-134. Engineering maintains acceptance the W.A.S.H. Report.

OVERLAY COMMENTS:
1) DS Sec.2-03.2.2.B.7: Regarding special overlay zone, submit copy of the W.A.S.H. Report and extra copy of the W.A.S.H. exhibit "Drainage Details for Rodeo Wash at Tres Pueblos Este".

DRAINAGE REPORT COMMENTS:
2) City of Tucson Development Standards (DS) Section No.2-03.2.4.L: Address the following comments for the Drainage Report:
a) In drainage report, include discussion of Rodeo W.A.S.H. section for on/off site conditions. Include discussion of authority for maintenance of the W.A.S.H.
b) Provide drainage maintenance checklist in report, providing operating conditions and stating how maintenance personnel are to address drainage problems on the site.
c) Add details for outlets to existing Rodeo W.A.S.H. area on a drainage exhibit.
3) DS Sec.2-03.2.4.L: Address the following drainage comments for the Tentative Plat:
a) Drainage channel section E/1 shows 1:1(H:V) with gunite. On this detail, clarify reinforcement requirements per geotechnical report.
b) DS Sec.10-02.2.3.1.6.A.4.a: Riprap areas shall show thickness of minimum D50 unless the rip rap is handplaced. Revise drainage report and all tentative plat details to reflect geotechnical report and show adequate thickness of rip rap.
c) DS Sec.10-02.2.3.1.6 A.4.d: The Geotechnical Report discusses provision for 15-ft of drainage away from structures. Show how lots provide for this on the tentative plat typical lot details and discuss building setbacks, with dimensions between structures (pavement or buildings) and any proposed basins or drainageways in revised drainage report.
d) DS Sec.10-02.2.3.1.6.A.4: Regarding detail M/6, clarify whether cut-off wall is needed at end of pipe.
e) For N/6, O/6, & P/6 details, show existing and proposed grades at outlet structures.
f) Many cross sections and hydraulic section calculations do not match the geotechnical report for slope stability. Slopes steeper than 1.5:1(H:V) shall be reinforced per prior comment letter reference to geotechnical report. Also slopes between 2:1(H:V) and 1.5:1(H:V) shall be grouted rip rap or wire tied riprap. Revise channel sections and calculations to match geotechnical report.
4) In drainage report and in detail T/6, provide cross section for basin pipes crossing utility pipes in proposed street. Show sufficient cover over pipes and WSEL below road structure, show WSEL and provide minimum distance dimensioning between top of water and sewer utility pipes and bottom of stormwater pipe, as well as minimum dimension between top of stormwater pipe and bottom of pavement.

TENTATIVE PLAT COMMENTS:
5) DS Sec.10-02.1.5.1: Address the following trail comments:
a) The 80' drainage easement is indicated to be maintained by Pima County and the proposed trail is indicated by notation to lie within the Pima County drainage easement area and specifically on the existing maintenance access road as noted on the planview sheets. If the existing maintenance road lies within this existing drainage easement, provide a letter from the county regarding their authorization of proposed design for the proposed trail and its maintenance within the drainage easement. Otherwise, provide a trail location that does not overlap the maintenance access road. It was stated in response letter that this would be coordinated with Pima County; provide correspondence regarding acceptance of design.
b) Detail H/2 appears to be missing.
c) The trail is proposed to be built over access road. Provide a cross section showing that the crossings shall be traversable by motorized vehicle and pedestrians. Show that maintenance vehicles access is not obstructed.
d) Label proposed materials.
e) Clarify / show proposed easements for drainage outlets to be maintained by HOA.
6) Per D.S. 2-03.2.4.K: Regarding the conceptual grading design for the project, address the following comments:
a) Clarify / provide cross sections for the following areas for clarification of conceptual grading:
i) For details N/6, O/6, & P/6, provide existing and proposed grades at outlet structures. Also, depict existing slope of wash, top of bank, elevated maintenance road, trail, and rear of a proposed lot.
ii) Provide existing elevation sections for the north side of the project to include a lot pad elevation near lots 16 and 159 through the basins and outlet channels, with existing and proposed grades, slopes, property line, setbacks, and to the adjacent wash. Detail K is insufficient since it does not depict existing and proposed grades. Detail K should show setback from basin as well.
iii) Revise sections D/1, F/1, & G/1 to reflect erosion protection rip rap to extend up to water surface elevation in each section.
b) To assure the tentative plat lot layout provides for sufficient horizontal area for slope run outs, swales, and other parameters, and also for clarification of proposed flow conditions on these RCP lots, clarify typical lot grading detail, that shows direction of drainage around proposed lots and explains the following:
i) Show/clarify area for utility pads / mechanical equipment or A/C unit locations, if it is located along the side yards.
ii) Show any building setbacks to swales, slope setbacks for screen walls, minimum side and rear building setbacks, per geotechnical report and drainage report.
iii) On sheet 6, assure Side Yard Drainage Section complies with geotechnical recommendations for minimum sideyard setback dimensions for positive drainage away from structures.
7) DS Sec.10-01.III.3.5.1.3.a, 10-02.14.2.6: Submit a copy of the geotechnical report including minimum slope recommendations, boring test results, and basin percolation results. The soils report shall also include minimum distance from foundations to drainage swales.
8) Add linetypes to legend - check delineations to assure all linetypes are represented on planview and legend. Specfically all clarify floodplain lines.
9) Submit a copy of the current title report to assure all easements have been addressed.

Submit geotechnical report, revised Drainage Report, revised Tentative Plat, drainage report response letter, copies of W.A.S.H. documentation, title report, complete tentative plat response letter, and any other supporting documentation such as the Pima County letter. The tentative plat will be denied until all comments are addressed. Call if you have any questions, 837-4934.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services
09/09/2008 ANDY VERA ENV SVCS REVIEW Approved All lots have adequate street frontage access for APC curbside refuse and recycle collection services.
09/10/2008 PETER MCLAUGHLIN ZONING REVIEW Approv-Cond PROJECT:Tres Pueblos Este Lots 1-163
Tentative Plat (1st Review) S08-101
ref: S05-134
TRANSMITTAL: August 20, 2008

COMMENTS:
1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a tentative plat. If, at the end of that time, the tentative plat has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this tentative plat is August 10, 2009.

2. Add the CDRC subdivision case number (S08-101) along with any other related case numbers and the expired subdivision case number (S05-134) in the lower right corner of each sheet on the tentative and final plat, landscape and NPPO plans. DS 2-03.2.2.B.1

3. The Final Plat may not be approved until the CC&R's are reviewed and approved by the Zoning Review Section. The CC&R's must meet criteria listed in L.U.C. 3.6.1.5. If applicable, the CC&R's must also detail the restrictions on any proposed natural areas. D.S. 2-10.3.2.E; L.U.C. 3.6.1.5

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 837-4898 or e-mail Peter.McLaughlin@tucsonaz.gov.
09/15/2008 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
10/23/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

September 16, 2008

Dan Castro
Rick Engineering Company
1745 East River Road, Suite 101
Tucson, Arizona 85718

Subject: S08-101 Tres Pueblos Este Tentative Plat

Dear Dan:

Your submittal of August 11, 2008 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

5 Copies Revised Tentative Plat (ADA, Wastewater, DUPD, Engineering, DSD)

3 Copies Revised Landscape Plan (DUPD, Engineering, DSD)

2 Copies Geotechnical Report (Engineering, DSD)

2 Copies Revised Drainage Report (Engineering, DSD)

2 Copies WASH documentation (Engineering, DSD)

2 Copies Title Report (Engineering, DSD)


Should you have any questions, please call me at 837-4919.

Sincerely,

Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 322-6956
10/23/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES
***REVISED***

October 23, 2008

Dan Castro
Rick Engineering Company
1745 East River Road, Suite 101
Tucson, Arizona 85718

Subject: S08-101 Tres Pueblos Este Tentative Plat

Dear Dan:

The above referenced plan has been CONDITIONALLY APPROVED by the Community Design Review Committee, subject to the revisions required on the bluelines per the on-line comments. Please submit the following documents for sign-off:

1 Blueline set of the Plat, Landscape Plan and NPPO. Please include applicable sheets from any other concurrent reviews.
2 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

Additional blackline copies will be made from the complete set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your bluelines to the CDRC office for sign-off approval. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

Please note that the final plat must be approved by Mayor and Council and recorded within one year of date of approval of the tentative plat per LUC 4.1.7.3.

PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.tucsonaz.gov/dsd/CDRC___Rezoning/CDRC/CDRC_Stamp/cdrc_stamp.html. BLUELINE SETS THAT DO NOT HAVE THE STAMP WILL BE RETURNED FOR CORRECTION.


Should you have any questions, please call me at 791-5608 extension 1179.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 322-6956
tp-approved