Plan Number: S08-099
Parcel: Unknown

Address:
332 E ELVADO RD

Review Status: Completed

Review Details: TENTATIVE PLAT REVIEW

Plan Number - S08-099
Review Name: TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2008 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
08/11/2008 DAVID MANN COT NON-DSD FIRE Denied Fire turn around and drive must be 2 inches of AC on 4 inches of ABC, see Devlopment Stds. A fire hydrant must be provded within 400 feet of all portions of the homes, see IFC 508.5.1 as amended.

Automatic fire sprinklers in the new units may be substituted for these requirements.
08/14/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
08/15/2008 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved ADOT has NO COMMENT on this project.

--------------------------------------------------------


Confidentiality and Nondisclosure Notice: This email transmission and any attachments are intended for use by the person(s)/entity(ies) named above and may contain confidential/privileged information. Any unauthorized use, disclosure or distribution is strictly prohibited. If you are not the intended recipient, please contact the sender by email, and delete or destroy all copies plus attachments.
08/18/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1. Add the CDRC subdivision case number along with any other related case numbers in the lower right hand corner of the plat. DS 2-04.2.2.B.1

2. The minimum required text size is 12 point (0.12"). Revise all lettering and dimensions (within the Location Map and in the Elvado Road Typical Cross Section detail) that does not meet this minimum standard. DS 2-03.2.1.C
08/22/2008 ED ABRIGO PIMA COUNTY ASSESSOR Approv-Cond Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)

FROM: Gary Ault, Mapping Supervisor
Pima County Assessor’s Office
Mapping Department

DATE: 08/22/08


RE: Assessor’s Review and Comments Regarding Tentative Plat S08-099


* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

x Plat meets Assessor’s Office requirements.
_______ Plat does not meet Assessor’s Office requirements.


COMMENTS: For final approval plat must show tie to section corner. Lines showing easements, flood/erosion setbacks etc. should be lightest line weight and dotted or dashed. Only the perimeter and lots lines should be solid, unless making them so would violate the guidelines of another agency reviewing the plan. If you have any questions about these specifications please call Brian Sloan in the Pima County Assessor’s Office, Mapping Dept. at 740-4395. Thank you for your submittal.

NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.
08/25/2008 CDRC1 OTHER AGENCIES PIMA ASSN OF GOVTS Approved CASE: S08-099, GOLDEN DAWN SPLIT: TENTATIVE PLAT REVIEW

COMMENT: NO OBJECTIONS OR ADVERSE COMMENTS





Vehicle Trip Generation: Daily: 29 PM Peak: 3











Please call if you have questions or need additional information.





-------------------------------------------

KoSok Chae, Ph.D.



177 N. Church Ave., Suite 405

Tucson, AZ 85701



520-792-1093 x487 [tel]

520-620-6981 [fax]

www.PAGnet.org
08/26/2008 TERRY STEVENS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: S08-099
Golden Dawn Split
Tentative Plat

TRANSMITTAL: 08/26/2008

DUE DATE: 09/05/08

COMMENTS:

1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a tentative plat. If, at the end of that time, the tentative plat has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this tentative plat is 08/07/09.

2. Per DS 2-03.2.1.C, all lettering (existing conditions on location map) need to be revised to ensure they are all a minimum of 12 point. Cannot read street names, subdivision names, etc.

3. Per DS 2-03.2.1.D, with regards to location map:
a) check to ensure map is at 3" to 1 mile scale
b) add south 6th Ave, Valencia, and south 12th Avenue to map
c) add section corners

4. DS 2-03.2.2.A.2 List the name, address, and telephone number of the person, firm, or
organization that prepared the plat.

5. DS 2-05.2.2.B.1 This project has been assigned the subdivision case number S08-099. Please list the case number in the lower right corner of all tentative plat sheets including the NPPO and landscape sheets. Remove the old case number (S06-271) from the plans.

6. DS 2-03.2.2.B.5 Revise general note #3. The proposed use should read as follows: Family Dwelling "I", subject to: Sec. 3.5.7.1.F

7. DS 2-03.2.2.B.7 Add a note stating that the plat is designed to meet the overlay zone criteria: LUC, Sec. 2.8.5, Airport Environs Zone.

This project is within the Airport Hazard District portion of the Airport Environs Zone overlay for the Tucson International Airport. Review LUC Sec. 2.8.5.11 Airport Hazard Districts for TIA and comply. Provide calculations on the plat clearly indicating compliance with this section. The mean sea level elevation for the south west runway for TIA is 2,561 feet M.S.L. The maximum allowed height of proposed structure is 80' above the M.S.L. of the SW end of the runway. Provide the MSL elevation of the finished floor of all proposed structures and the MSL of the height of the proposed structures clearly indicating compliance.

8. DS 2-03.2.3 Provide documentation showing that the existing ramada on parcel 51A (note #13) has been permitted.

The removal of apportion of the ramada must meet building code requirements for firewall protection or a minimum of 3' from the south property line of parcel 51A Provide dimensions from the south end of the ramada to the south property line of parcel 51A.

9. DS 2-03.2.4.J The ingress/egress utility easement (note #28) and the 1' N.A.E .(note#2) are indicated as being recorded by docket and page. Change to "By Final Plat".

The 1' N.A.E. is required to continue along the east side of the ingress/egress easement to the south property line of parcel 51A.

10. DS 2-03.2.4.M Provide wall heights of each elevation for the new structures. Required in order to determine required setbacks from property lines.

Sight visibility triangles are not indicated correctly. See engineering comments.

11. Provide lot coverage calculations for each lot proposed.

12. Provide density calculations for the entire sight.

13. In the title block revise the legal description to read: "A resubdivision of Golden Dawn Farms W 100' of lot 51."

14. Near the lower left corner, remove the indicted "approved by the subdivision and development review committee and signature line". Provide on the plan the approval stamp required by CDRC. This is available on the City of Tucson web site by typing in CDRC in the search line. Provide this stamp near the lower right corner of the plat.

15. Based on changes to this plat and responses to the above comments additional comments may be forth coming.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961
TLS C:\planning\cdrc\tentativeplat\S08-099tp.doc
09/02/2008 ANDY STEUART COT NON-DSD REAL ESTATE Denied -Per Pima Co. Treasure, 9/2/08, it appears taxes for 2008 have not been paid as of this date.
-Request S06-271 be changed to S08-099.
-Because this is a plat and will be accepted by Mayor & Council, easements per Keynote 2 & 28 may be dedicated "by plat" in-place of separate instrument.
09/03/2008 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

JENNIFER STEPHENS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: JENNIFER STEPHENS, ADDRESSING OFFICIAL
SUBJECT: S08-099 GOLDEN DAWN SPLIT/TENTATIVE PLAT
DATE: 9/02/08



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:

1.) Some of the Location Map is not legible. Please correct.
2.) Delete street direction on Location Map.
3.) Spell out all street suffixes.
4.) Label lots 1-3.
5.) Include "A resubdivision of" Golden Dawn…. on Title Block.
09/05/2008 FERNE RODRIGUEZ PIMA COUNTY WASTEWATER Denied September 03, 2007

TO: Aura Otero
Desert Wolf Drafting

THRU: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

FROM: Chandubhai C. Patel, P.E., Civil Eng. Manager
Development Review Division (Wastewater)
Pima County Development Services Department

SUBJECT: Golden Dawn Farms
Tentative Plat – 1st Submittal
S08-099


The proposed sewer collection lines to serve the above-referenced development have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ), and the Pima County Regional Wastewater Reclamation Department (PCRWRD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


SHEET 1. Change the project number from S06-271 to S08-099. This is the new number assigned to this project.

As per the PCRWRD, a sewer capacity letter is not required for this development.


3. SHEET 1. Show the proposed and existing HCS using different line types. Show these same line types in the LEGEND also.

SHEET 1. Show the same line type in the LEGEND for existing public sewer as used to show the existing public sewer in EL VADO RD.

SHEET 1. Show an HCS for parcel 51 A. If this parcel is sharing other HCS, a sewer use/maintenance agreement will be required.

SHEET 1. Show the size and slope of all HCS. Provide cleanouts on HCS every 100 feet and all changes in direction. Show invert and rim elevations at all cleanouts.

Show existing MH down stream of the connection point of the HCS on the existing public sewer, and provide rim and invert elevation for this MH.

Show inverts of the new HCS where they connect to the existing public sewer.

The private sewer easement must be recorded prior to having the mylars signed for this project. It must be called out as UTILITY and SEWER easement.

The next submittal of this project will be the 2nd submittal. A check for the review fee of this submittal in the amount of $50.00 made out to PIMA COUNTY TREASURER must accompany the revised set of bluelines and the response letter.


If you have any questions regarding the above comments, please do not hesitate to contact me.
09/08/2008 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
09/08/2008 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: September 08, 2008

TO: DSD_CDRC@ tucsonaz.gov

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov


SUBJECT: S08-099 Golden Dawn Split: Tentative Plat Review(7-08-08)



Staff has no comments.
09/09/2008 ANDY VERA ENV SVCS REVIEW Approved 1. All three SFR/lots have adequate street frontage access for APC curbside refuse and recycle collection services. Each individual lot/resident will be responsible for rolling their APC's (Automated Plastic Containers) out to El Vado and comply with all ES requirements regarding residential curbside collection.

2. Substandard turnaround not adequate for on site solid waste collection/disposal services.

If you have any questions you may contact Andy Vera at (520) 791-5543 ext 1212 or e-mail: Andy.Vera@tucsonaz.gov
09/10/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied To: Patricia Gehlen
CDRC/Zoning Mannager
From: Bianca Ramirez, CFM
Engineering Division

Subject: Tentative Plat for Golden Dawns Farms D08-0099 (First Review) T15S, R13E, Section 13

SUBMITTAL REQUIRED: Tentative Plat, Drainage Report (Drainage Statement Submitted)
The Tentative Plat and Drainage Report (Submitted as Drainage Statement) have been reviewed by the Engineering Division and we do not recommend approval at this time. The following review comments must be addressed.

DRAINAGE STATEMENT:
This development is located within a City of Tucson identified 100-year floodplain and plat will not be approved unless all wheather access and buildable lots are provided. Prior to approval of Tentative Plat, approved grading plan is required to show elevations and to provide buildable lots. For tentative plat, address the following drainage report comments:

1. Drainage Report is required for this development. Resubit report as Drainage Report.
2. Include full backwater analysis
3. Provide discussion explaining how water surface elevations (WSE's) are lowered after development.
4. Provide readable exhibit for Exhibit C-1.
5. Provide locations for cross-sections from the analysis.
6. Provide exhibit of floodplain delineations for pre and post development.
7. Explain how minimum finished floor elevation is determined from water surface elevations. The finished floor elevation does not match and of that watersurface elevations indicated in the table for after development water surface elevations.
8. Provide hydrology map indicating where offsite watershed is located that is impacting the project. The City data indicates a Draft Q100 at upstream culvert equal to 269 cfs. Explain descrepency.
9. Additional comments may be forthcoming.

TENTATIVE PLAT:
1. DS Sec.2-03.2.1.B. Verify that sheet includes a one-half (½) inch margin on each side to allows for standardization of material for more efficient record keeping and assures legibility when microfilmed.
2. DS Sec.2-03.2.1.C: Verify that all lettering and dimensions within the locations map and the cross section detail are the equivalent of twelve (0.12) point or greater in size.
3. Location map. Include section corners.
4. Provide address on plan: 332 E Elvado Rd.
5. DS Sec.2-03.2.1.G.1: Revise the proposed name of the subdivision. Revise title block to read Being a Resubdivision of a Portion of Golden Dawn Farms.
6. Include and common areas in title block including private street for utilites and all weater access.
7. Revise General notes 9 and 10 to include distances for any public or private streets included as part of the revision.
8. DS Sec.2-03.2.2.A.2: Add the surveyor information along with pertinant information. Include the surveyors name, address, and telephone number, firm, or organization that prepared the plat.
9. DS Sec.2-03.2.2.B.1: Revise to correct case number: S08-99.
10. DS Sec.2-03.2.2.C.2.a: "The following lots are affected by the City of Tucson Floodplain Regulations: 51A, 51B and 51C." All three lots should be identified as being affected by the City of Tucson identified 100-year floodplain.
11. DS Sec.2-03.2.2.C.2.b: "A floodplain use permit and/or finished floor elevation certificates are required for the following lots: 51A, 51 B and 51C." Revise to include all three lots in general note 7.
12. DS Sec.2-03.2.3 Existing Conditions: The following information shall be provided on the plat to indicate the existing conditions on site and within one hundred (100) feet of the site, except where the site is bounded by a street with a width of one hundred (100) feet or greater. In those situations, existing conditions across the street will be provided.
13. DS Sec.2-03.2.3.A: Provide local benchmark location. The basis of elevation appears to be very far from the property. Revise Basis of Elevation to be presented (per City of Tucson Book and Page) or other acceptable survey datum.
14. DS Sec.2-03.2.3.F: Verify that the ground elevation indicated on the tentative plat are based on City of Tucson Datum (indicate City of Tucson field book number and page) or other acceptable survayable datum.
15. DS Sec.2-03.2.3.C: Verify that all existing easements have been drawn on the plat. Also verify that recordation information, locations, widths, and purposes are included.
16. DS Sec.2-03.3.1.E: Verify that current title report is submitted.
17. Revise keynote 2 to include recorded book and page.
18. DS Sec.2-03.2.3.D: The following information regarding the existing public right-of-way will be called out and labeled.: type and dimensioned width of paving, curbs, curb cuts, and sidewalks. Within one hundred (100) feet of the site. Identify all utilities on Elvado cross section or on plan view.
19. Identify and label Elvado as a public street.
20. DS Sec.2-03.2.3.G: Verify that all existing storm drainage facilities on and adjacent to the site have been shown and called out on plan.
21. DS Sec.2-03.2.3.J: On plan view, provide City of Tucson Identified 100-year floodplain information, including the location of the 100-year flood limits and 100-year flood water surface elevations.
22. DS Sec.2-03.2.3.J.3: Povide a symbol in legend and on plan view representing the water surface contour intervals.
23. DS Sec.2-03.2.4.B: Identify squar footage of existing residence.
24. DS Sec.2-03.2.4.F: Proposed traffic circulation will be designed in accordance with street Is required per Development Standard 3-01.0.
25. Show cross section of private street to include sidewalk per section DS Sec 3-01.10 Figure 1.
26. DS Sec.2-03.2.4.J: Unless the utilities are located withinthe streets, verify that all proposed easements (utility, sewer, drainage, access, etc.) are dimensioned and labeled as to their purposes and whether they are public or private.
27. DS Sec.2-03.2.4.K: A conceptual grading plan is required on projects with significant topographic conditions. Unable to determine if requirement is applicable. Provide pad elevations for the building pads. All pads shall meet grading standards for the two-foot differential limit, otherwise the procedures for differential grading will apply. DS Sec 11-01.8.1. Indicate the finished floor elevation of each building for further review.
28. DS Sec.2-03.2.3.F.1: Verify that spot elevations have been provided at all breaks in grade and at selected points to describe conceptual proposed elevations for grading.
29. Provide the Engineer information for the Drainage Report (Subitted as Drainage Statement) on the Tentative Plat include all pertinant information.
30. On Tentative Plat show offsite and onsite drainage for site including Q100 entering and leaving site. Include any symbols added to plan to the legend. DS Sec.2-03.2.4.L.7: Draw locations and indicate types of off-site runoff acceptance points and/or on-site runoff discharge points.
31. Approval of tenative plan requires that proposed location of buildings are elevated 1' above determined base flood elevation.
32. Provide estimated cut and fill quantities on the plan.
33. DS Sec.2-03.5.2 A grading permit will be required for this project. Generally, the grading plans may be submitted for review upon approval of the tentative plat. The grading plan can be submitted after the second resubmittal of the tentative plat; however, the grading plan cannot be approved unless it is in conformance with an approved tentative plat.
34. A Floodplain Use Permit will be required for the proposed buildings.
35. Revise location of Sight Visibility Triangles. They are to align with the edge of the curb not to center of the driveway.
36. If identified ½ Right of Way is both existing and future Right of way indicate by labeling Future/Existing.
37. Submit required assurances, including street, utilites and fill.
38. Include docket and page for keynote 28.
39. Keynote 30 - identify Far = and Near = so that dimensions are labeled. Or call out dimensions for sight visibility triangles on plan.
40. Verify that 2' grading off-set have been provided from property line to proposed street.
41. Provide symbols for existing and proposed spot elevation points in plan view in legend.
42. DS Sec 2-02.2.1.A.11 & DS Sec 3-01.3.2.C: Depict and label the appropriate curb returns. Provide curb returns with appropriate radaii per City of Tucson/Pima County Standard Detail 213 (PC/COT 213) at the driveway enterance along Fort Lowell Road. The curbs should be constructed at the edge of pavement and entirely on the subject property, which must also be depiced on the site plan. If you have further questions refarding curb returns, contact City of Tucson, Transportation Department.
43. Explain if there will be a home owners association.
44. General note 12 complete statement by adding ,,, "at the time of submittal of plumbing or building plans."
45. Provide arrow for keynote 16 located within the south-east portion of parcel.
46. Provide finished flood elevations on the plan view for each of the buildings.
47. Explain regarding Elvado Street, whether a PIA is proposed.
48. Additional comments may be forthcoming.

If you have any questions, I can be reached at bianca.ramirez@hotmail.com or 837-4928.

Bianca C. Ramirez, CFM
Engineering Associate
City of Tucson - Development Servides Department
201 N Stone Avenue
PO Box 27210
Tucson, AZ 85726
(520) 837-4928 Office
(520) 879-8010 Fax
09/12/2008 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S08-099 Golden Dawn Split 09/03/08

(XXXX) Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Revised Plan/Plat
( ) Board of Adjustment
( ) Other - Record of Survey

CROSS REFERENCE:

NEIGHBORHOOD PLAN: 12th Avenue/Valencia

GATEWAY/SCENIC ROUTE: N/A

COMMENTS DUE BY: 09/5/08

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

( ) No Annexation or Rezoning Conditions, Not an RCP - No Comment
(XXXX) Proposal Complies with Annexation or Rezoning Conditions
( ) RCP Proposal Complies with Plan Policies
( ) See Additional Comments Attached
( ) No Additional Comments - Complies With Planning Comments Submitted on:
( ) Resubmittal Required:
( ) Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Other

REVIEWER: drcorral 791-4505 DATE: 9/2/08
09/12/2008 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved
09/15/2008 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Denied 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR# 201958 September 12, 2008



Desert Wolf Drafting
Attn: Aura Otero
4801 S. Agave Ranch Dr.
Tucson, Arizona 85735

Dear Aura Otero:

SUBJECT: Golden Dawn - Split
S08-099

Tucson Electric Power Company (TEP) has reviewed the plan submitted September 3, 2008. TEP is unable to approve the plan at this time. There are existing electrical facilities within the boundaries of this project. In order for TEP to approve the plan the facilities and easements must be depicted on the plans.

Enclosed is a copy of a TEP facility map showing the approximate location of the existing facilities. Existing underground services are not shown on the plan. All costs associated with the relocation of the facilities in conflict will be billable to the developer.

Please resubmit two revised bluelines to City of Tucson Development Services Department for TEP's review. You may contact the area Designer, Warren McElyea at 918-8268 should you have any technical questions.

Sincerely,



Henrietta Noriega
Office Specialist

hn
Enclosure
cc: P. Gehlen and F. Rodriguez, City of Tucson (by e-mail)
W. McElyea, Tucson Electric Power
09/16/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

September 16, 2008

Aura Otero
Desert Wolf Drafting
4801 South Agave Ranch Drive
Tucson, Arizona 85735

Subject: S08-099 Golden Dawn Split Tentative Plat

Dear Aura:

Your submittal of August 8, 2008 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

9 Copies Revised Tentative Plat (Fire, Landscape, Zoning, Real Estate, Addressing, Wastewater, Engineering, TEP, DSD)

4 Copies Revised Landscape Plan (Landscape, Zoning, Engineering, DSD)

2 Copies Drainage Report (Engineering, DSD)


Should you have any questions, please call me at 837-4919.



Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 792-8541
Tp-resubmittal