Plan Number: S08-071
Parcel: Unknown

Review Status: Completed

Review Details: ASSURANCES

Plan Number - S08-071
Review Name: ASSURANCES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/23/2009 PATRICIA KRAUSMAN START ASSURANCES RECEIVED Completed
05/13/2009 PAUL MACHADO ENGINEERING REVIEW Denied To: Patricia Gehlen DATE: May 13, 2009
CDRC/Zoning Manager

SUBJECT: Colonial Solana, 13246 E. Broadway Blvd.
Assurances S08-071 (First Review)
T14S, R14E, Section 16

RESUBMITTAL REQUIRED: Assurances.

The Assurances cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Final Plat Assurances:

1. Please include a detailed response letter to the comments along with the corrected copies of the FP.
2. The title block of the plat must match the Subdivision Assurances verbatim. The FP does not have in the title the words "and utility access easement" that the assurances list. The title block or the assurances must be revised to match each other.
3. Exhibit "A", the legal description, does match either the title on the assurances nor does it match the title block of the FP. All three descriptions shall match one another. Revise as required.


If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/3246 E. Broadway Blvd Assur.