Plan Number: S08-043
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW

Plan Number - S08-043
Review Name: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2008 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
09/05/2008 STEVE SHIELDS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Steve Shields
Lead Planner

PROJECT: The Shops at Midvale
1801 W. Valencia Road
S08-043 (3rd Review)

TRANSMITTAL DATE: September 5, 2008

DUE DATE: September 10, 2008

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The Zoning Review Section conditionally approves the tentative plat/development plan for this subdivision, subject to the following changes on the executed tentative plat. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised tentative plat to verify that those changes do not affect any zoning requirements.

2. Provide the docket and page for the recordation of the CC&Rs.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\cdrc\tentativeplat\S07-158tpca-3rd.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised tentative plat, and additional requested documents.
09/05/2008 JASON GREEN ENGINEERING REVIEW Approv-Cond DATE: September 5, 2008
SUBJECT: The Shops at Midvale- 3rd Tentative Plat Engineering Review
TO: Patricia Gehlen, CDRC Manager
LOCATION: 1801 W Valencia Road, T15S R13E Sec15 Ward 1
REVIEWERS: Jason Green, CFM
ACTIVITY: S08-043


SUMMARY: Engineering Division of Development Services Department has received and reviewed the revised Tentative Plat, Drainage Report (The WLB Group, Inc., 28MAR08, revised 09JUL08), Environmental Resource Report (The WLB Group, Inc., 07/2008), Geotechnical Engineering Report (LMT Engineering, Inc., 23APR08, addendum 02SEP08) Pre-Annexation Agreement, and Covenants, Conditions, Restrictions and Easements for The Shops @ Midvale. The Drainage Report was reviewed for Tentative Plat purposes only. The Tentative Plat is conditionally approved at this time. The following item need to be addressed prior to Final Mylar approval:

TENTATIVE PLAT MYLAR:

Prior to Tentative Plat Mylar approval The Covenants, Conditions, Restrictions and Easements for The Shops @ Midvale must be recorded and the recordation information must be provided in General Notes #45 and #47.


GENERAL COMMENTS:

Provide the Tentative Plat Mylar for review and approval through the CDRC office. Provide the recordation information for the CC&Rs on the Mylar prior to approval.


If you have any questions, I can be reached at (520) 837-4929.



Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
09/08/2008 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S08-043 The Shops at Midvale Lots 1-5 09/08/08

( ) Tentative Plat
( X ) Development Plan
( X ) Landscape Plan
( ) Revised Plan/Plat
( ) Board of Adjustment
( ) Other

CROSS REFERENCE: C9-07-20

NEIGHBORHOOD PLAN: General Plan

GATEWAY/SCENIC ROUTE: Gateway

COMMENTS DUE BY: September 10, 2008

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

( ) No Annexation or Rezoning Conditions, Not an RCP - No Comment
( ) Proposal Complies with Annexation or Rezoning Conditions
( ) RCP Proposal Complies with Plan Policies
( ) See Additional Comments Attached
( X ) No Additional Comments - Complies With Planning Comments Submitted on: 8/12/08
( X ) No Resubmittal Required:
( ) Tentative Plat
( X ) Development Plan
( X ) Landscape Plan
( ) Other

REVIEWER: JBeall 791-4505 DATE: 9/12/08
09/08/2008 KAY MARKS PIMA COUNTY ADDRESSING Approv-Cond 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207


JENNIFER STEPHENS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: JENNIFER STEPHENS, ADDRESSING OFFICIAL
SUBJECT: S08-043 THE SHOPS AT MIDVALE LOTS 1-5/REVISED TENTATIVE PLAT
DATE: 9/08/08



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.


NOTE: ON FINAL PLAT:

1.) Change Elvira Rd to St and change Elvira St to Rd on Location Map.


***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through Pima
County Addressing. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County's
Geographic Information System. Your support is greatly appreciated.***
09/09/2008 ANDY VERA ENV SVCS REVIEW Approved
09/09/2008 CDRC1 PIMA COUNTY WASTEWATER Denied September 9, 2008

TO: John Holley
The WLB Group

THRU: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

FROM: Tom Porter , Sr. Civil Eng.r
Development Review Division (Wastewater)
Pima County Development Services Department

SUBJECT: The Shops At Midvale, Lots 1-5
Development Plan - 2nd Submittal
S08-043


The proposed sewer collection lines to serve the above-referenced development have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ), and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.



1. We will send to your office via e-mail, a .pdf file containing a Sewer Service Agreement for the proposed number of wastewater fixture unit equivalents. Three originals will need to be printed out from this file for notarized signatures by the Owner of Record. The three signed originals of the Agreement must be returned to this office in order to satisfy the necessary requirements needed to approve the Mylars of the .

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the development plan. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the third submittal. A check for the review fee of this submittal in the amount of $39.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above comments, please do not hesitate to contact me.

Sincerely,



Tom Porter ,Sr CEA
Telephone: (520) 740-6579

Copy: Project file
09/09/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Approved
09/09/2008 CDRC1 PIMA COUNTY WASTEWATER Denied September 9, 2008

TO: John Holley
The WLB Group

THRU: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

FROM: Tom Porter , Sr. Civil Eng.r
Development Review Division (Wastewater)
Pima County Development Services Department

SUBJECT: The Shops At Midvale, Lots 1-5
Development Plan - 2nd Submittal(rev)
S08-043


The proposed sewer collection lines to serve the above-referenced development have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ), and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.



1. We will send to your office via e-mail, a .pdf file containing a Sewer Service Agreement for the proposed number of wastewater fixture unit equivalents. Three originals will need to be printed out from this file for notarized signatures by the Owner of Record. The three signed originals of the Agreement must be returned to this office in order to satisfy the necessary requirements needed to approve the Mylars of the .

Subject to the above, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan if the SSA is submitted to our office by 9/10/08.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.

If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above comments, please do not hesitate to contact me.

Sincerely,



Tom Porter ,Sr CEA
Telephone: (520) 740-6579

Copy: Project file
09/09/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

September 9, 2008

John Holley/David Whitney
The WLB Group Inc.
4444 East Broadway Blvd.
Tucson, Arizona 85711

Subject: S08-043 The Shops at Midvale Park Tentative Plat

Dear John:

The above referenced plan has been APPROVED by the Community Design Review Committee, subject to the revisions required on the mylars. Please submit the following documents for sign-off:

1 Reproducible Océ or Photo Mylar of the Plat, Landscape Plan and NPPO.
2 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

Additional blackline copies will be made from the complete set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the mylar and three (3) blackline copies to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

Please note that the final plat must be approved by Mayor and Council and recorded within one year of date of approval of the tentative plat per LUC 4.1.7.3.

TO ENSURE A MORE RAPID REVIEW OF THE MYLARS, PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.ci.tucson.az.us/dsd/CDRC Rezoning/CDRC/CDRC Stamp/cdrc stamp.html.

PRIOR TO SUBMITTAL TO THE CDRC OFFICE, THE MYLARS MUST BE REVIEWD AND APPROVED BY PCWWM. THE APPROVAL MUST BE IN WRITING (E-MAIL IS OKAY).


Should you have any questions, please call me at 837-4919.

Sincerely,




Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 881-7492
tp-approved
09/09/2008 CDRC1 PIMA COUNTY WASTEWATER Denied Hi Patricia,


I have reviewed the mylars received by us on 9-11-08, and have received
the SSA. The Mylars are approvable now.

John/Ed,

You may arrange to have the mylars picked up, and taken to Patricia for
further processing.

C.C. Patel, P.E.
Pima County DSD