Plan Review Detail
Review Status: Active
Review Details: LOT SPLIT REVIEW
Plan Number - S08-003
Review Name: LOT SPLIT REVIEW
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2008 | DROBEY1 | START | PLANS BEING WALKED THRU | Completed | |
| 01/08/2008 | ANY | BUILDING-RESIDENTIAL | REVIEW | Active | |
| 01/08/2008 | ANY | PLUMBING-COMMERCIAL | REVIEW | Active | |
| 01/08/2008 | ANY | ZONING-RECORDATION | REVIEW | Active | |
| 07/22/2008 | LAITH ALSHAMI | ENGINEERING | REVIEW | Denied | Laith Alshami, Engineering and Floodplain Review, 07/22/2008, The parcel has a regulatory floodplain. Splitting the parcel and developing it may cause an encroachment on the floodplain. Verification that the lot split will create a buildable new lot that has all weather access is required. Submit a drainage report that addresses all drainage related issues, Additionally, an Environmental Resource Report is also required for encroaching on the floodplain. With all these requirements, over the counter review is not possible. A formal submittal through CDRC is required. |
| 07/22/2008 | DAVID RIVERA | ZONING | REVIEW | Denied | Zoning cannot approve the lot split until the WASH or ERR report is approved. Additional review is required for the developmnent on the site once the lot split is approved. David Rivera Zoning Review Section July 22, 2008 |