Plan Number: S07-204
Parcel: Unknown

Review Status: Completed

Review Details: TENTATIVE PLAT REVIEW

Plan Number - S07-204
Review Name: TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2008 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
01/08/2008 JIM EGAN COT NON-DSD FIRE Approved
01/09/2008 CDRC1 PIMA COUNTY WASTEWATER Denied January 8, 2008

To: HANK HULBERT
LEADS & CEI ENGINEERING ASSOCIATES, INC.

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department


___________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environment Quality

Subject: CIRCLE K SWC VALENCIA ROAD & NOGALES HIGHWAY
Tent. Plat - 1st Submittal
S07-204

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

1. This project will be tributary to the Roger Road Wastewater Treatment Facility via the SCI and NWO.
Obtain a letter from the PCWMD's Development Services Section, written within the past 90 days, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at:

http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf.

The tentative or preliminary plat for this project cannot be approved until a copy of this letter has been received by this office.

2. All Sheets: Show the jurisdiction's case number, S07-204, in or near the title block of each sheet. This case number should be shown larger and bolder than any associated cross-reference numbers.

3. Sheet 1: Wastewater Management Note #2 change the word tits to its.

4. Sheet 1: Revise Wastewater Management Note #4 to read as follows:


THE ON-SITE SANITARY SEWERS WILL BE PRIVATE AND WILL BE CONSTRUCTED, OPERATED AND MAINTAINED ON A PRIVATE BASIS, AND IN ACCORDANCE WITH AN APPROVED OPERATION AND MAINTENANCE PLAN, IF REQUIRED. THE LOCATION AND METHOD OF CONNECTION TO AN EXISTING PUBLIC SANITARY SEWER IS SUBJECT TO REVIEW AND APPROVAL BY THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT.

5. Sheet 2: Show the public sewer continuing north along Nogales Hwy and along Valencia Rd.

6. Sheet 2: The public sewer size in Nogales Hwy is 10" not 24" as shown on this plan.

7. Sheet 2: Show the construction plan # for public sewer lines shown on this plan.

8. Sheet 2: Show directional flow arrows for both the proposed and existing sewer lines on plan.

9. Sheet 2: Indicate the IMS# with rim and invert elevations for all public manholes.

10. Sheet 2: In the Legend revise the pipe size of the symbol shown for both existing and proposed sewer lines.

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the tentative or preliminary plat. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the second (2nd) submittal. A check for the review fee of this submittal in the amount of $100.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.

If you have any questions regarding the above-mentioned comments, please contact me.
01/10/2008 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved >>> "Douglas Kratina" <DKratina@azdot.gov> 01/10/2008 2:15 PM >>>
ADOT has NO COMMENT on this project
S07-204
LEADS. INC
CIRCLE K STORES
VALENCIA ROAD and NOGALES HIGHWAY
01/14/2008 CDRC1 OTHER AGENCIES PIMA ASSN OF GOVTS Approved >>> "Aichong Sun" <asun@pagnet.org> 01/14/2008 2:08 PM >>>
CASE: S07-204, CIRCLE K STORE: TENTATIVE PLAT REVIEW

COMMENT: NEED EXTENSIVE REVIEW OF TRAFFIC OPERATIONS AND REQUIRE THE
NEED FOR TRAFFIC MITIGATION



Vehicle Trip Generation: Daily: 14,243 PM Peak:
1,012

Please call if you have questions,
01/15/2008 KAY MARKS PIMA COUNTY ADDRESSING Denied 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S07-204 CIRCLE K STORE/TENTATIVE PLAT
DATE: January 15, 2008



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval:


This is a re-sub of a portion of Lots 1 & 6 of Golden Dawn Farms, Bk 4, Pg. 98. Please add to legal description in Title Block.
Delete direction from Valeska Road in Location Map.



jg
01/17/2008 JOE LINVILLE LANDSCAPE REVIEW Denied 1) Any required storm water detention/retention basins shall be landscaped to enhance the natural configuration of the basin. Design criteria are set forth in Development Standard and in the conditions of rezoning. 10-01.0. LUC 3.7.4.3.A

2) All lettering and dimensions shall be the equivalent of twelve (0.12") point or
greater in size. DS 2-05.2.1.A

3) A minimum two (2) inch layer of organic or inorganic material (i.e., decomposed granite, rock mulch, or other material) will be used as ground cover under and around the vegetation in landscaped areas to help cool soil areas, reduce evaporation, and retard weed growth per DS 2-06.5.2.C. Revise general Note E on sheet L-1.

4) Canopy trees must be evenly distributed throughout the vehicular use area. Every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk).
Revise the Phase 2 portion of the landscape plan as necessary. LUC 3.7.2.3.A

5) Add the CDRC case number and any related case numbers, such as rezoning, to the landscape and native plant preservation plans. DS 2-07.2.1.B

6) The loading area near the southwest corner of the site is required to be screened per LUC table 3.7.2-I. Revise the landscape and development plans to specify the required walls (west and south sides).

7) Clarify where 5 and 6 foot high walls begin and terminate along the west property line.

The NPP exception application is approved.
01/22/2008 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Denied DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S07-204 Circle K Store

(XXXX) Tentative Plat
() Development Plan
(XXXX) Landscape Plan
() Revised Plan/Plat
() Board of Adjustment
() Other

CROSS REFERENCE: C9-06-10

NEIGHBORHOOD PLAN: 12th Avenue/Valencia Area Plan

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: 02/04/08

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

() No Annexation or Rezoning Conditions, Not an RCP - No Comment
() Proposal Complies with Annexation or Rezoning Conditions
() RCP Proposal Complies with Plan Policies
() See Additional Comments Attached
() No Additional Comments - Complies With Planning Comments Submitted on:
(XXXX) Resubmittal Required:
(XXXX) Tentative Plat
() Development Plan
() Landscape Plan
(XXXX) Other – Elevations

REVIEWER: drcorral 791-4505 DATE: 01/15/08

Please list rezoning conditions under the General Notes section of the Tentative Plat.

2. Per condition #9, architectural elements are to be applied to sides and rear building facades, when structures are visible from the right-of-way and any pedestrian links or paths. To satisfy this requirement, please submit a copy of colored elevations.
01/29/2008 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Steve Shields
Lead Planner

PROJECT: Circle K Store - Southwest Corner of Valencia & Nogales Highway
Tentative Plat
S07-204 (1st Review)

TRANSMITTAL DATE: January 29, 2008

DUE DATE: February 04, 2009

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a tentative plat. If, at the end of that time, the tentative plat has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this tentative plat is January 03, 3009.

2. It appears that the proposed zoning for this project has changed. Per re-zoning case # C9-06-10 and PDP-1, revised 06/23/06, the proposed zoning was C-1 & C-2. Per the submitted tentative plat the proposed zoning is all C-2. This change will require a new re-zoning, contact, Michael Wynekin @837-4955.

3. For the next submittal combine the development plan D07-0030 and this tentative plat as one plan. Contact Patricia Gehlen @837-4919 in regards to this combination.

4. D.S. 2-03.2.1.D.2 Identify the following conditions within the area of the location map, subdivisions (by book and page), railroads, section corners and City's jurisdictional limits.

5. D.S. 2-03.2.2.B.1 Place the S07-204 subdivision case number in the lower right corner of the plat next to the title block.

6. D.S. 2-03.2.2.B.5 Under General Note 4 add the "SUBJECT TO LUC SEC. 3.5.9.2.A".

7. D.S. 2-03.2.2.B.7 Add the LUC "SEC. 2.8.3" to NOTE #1 along with "SEC. 2.8.4 GATEWAY CORRICOR ZONE (GCZ); SEC. 2.8.5 AIRPORT ENVIRONS ZONE (AEZ)".

8. D.S. 2-03.2.2.B.J If applicable show all proposed easements (utility, sewer, drainage, access, etc.)

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\cdrc\tentativeplat\S07-204tp.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised tentative plat, site plan and additional requested documents.
01/29/2008 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved
02/01/2008 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
02/05/2008 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR192750 February 5, 2008


Leads, Inc.
Attn: Hank Hulbert
2400 N Central Ave. Ste. 203
Phoenix, AZ 85004

Dear Mr. Hulbert :

SUBJECT: Circle K Stores
S07-204


Tucson Electric Power Company has reviewed and approved the development plan submitted January 21, 2008 It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development.

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, offsite and electrical load plans. Include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to:

Tucson Electric Power Company
Attn: Ms. Mary Boice
New Business Project Manager
P. O. Box 711 (DB-101)
Tucson, AZ 85702
520-917-8732

Please call the area Designer Steve Garcia at (520) 917-8739, should you have any questions.


Sincerely,



Henrietta Noriega
Office Specialist
Design/Build
hn
Enclosures
cc: City of Tucson, (Email only)
S. Garcia, Tucson Electric Power
02/05/2008 FRODRIG2 COT NON-DSD REAL ESTATE Denied S07-204 Circle K Store: Tentative Plat Review
-Request approx. 10' along Valencia Rd. be dedicated for R/W to accommodate 150' for M,S&R, updated 8/20/07. The W. bound lane shows a width of approx. 75' from Centerline to N. boundary of R/W for Valencia. The E. bound lane shows a width of approx. 65' from Centerline to S. boundary of R/W for Valencia.

Andy
(520) 837-6715
Real Estate Division

fax 791-5641
02/07/2008 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR



TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)

FROM: Gary Ault, Mapping Supervisor
Pima County Assessor's Office
Mapping Department

DATE: February 6, 2008


RE: Assessor's Review and Comments Regarding Tentative Plat
S07-204 Circle K Store T151313

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

X Plat meets Assessor's Office requirements.
_______ Plat does not meet Assessor's Office requirements.


COMMENTS: Thank you for your submittal. Please add the number of miles of new roads to the general notes, even if the number is 0.

NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.






Susan King
02/07/2008 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved PARKS AND RECREATION DEPARTMENT COMMENTS

City of Tucson CDRC - Community Design Review Committee


CASE NUMBER: S07-204
CASE NAME: Circle K Store: TP
Submittal #: 1

COMMENTS DUE: 2/4/08 COMMENTS SENT: 2/6/08


Items being reviewed: (ü) Tentative or Final Plat
( ) Development Plan
(ü) Landscape Plan
( ) Other -

Related Cases: annexation - N/A
rezoning - C9-06-10
CDRC - D07-0030

Parks and Recreation Department Staff has reviewed this proposal and offers the following comments:


(ü) APPROVED - No Resubmittal Required.

(ü) No comment
( ) Proposal complies with annexation or rezoning conditions
( ) Proposal satisfies trails, recreational amenities, and/or parks and open space requirements
( ) No additional comments - complies with comments submitted on:


( ) NOT APPROVED - Resubmit the following. See attached comments.

( ) Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Other


REVIEWER: Joanne Hershenhorn DATE: 2/6/08


S:\PARKS_AND_RECREATION_DEPT\REVIEW_COMMENTS\CDRC_Cases\2008_ReviewsS07-204_Circle_K.doc
02/08/2008 ANDY VERA ENV SVCS REVIEW Denied 1. Must provide refuse/recycle enclosure detail and meet the minimum design criteria. Refer to DS 6-01.0

2. Access and maneuverability within development works. Approach to enclosure areas good.

Please make necessary corrections on resubmittal.

If you have any questions you may contact Andy Vera at (520) 791-5543 ext 1212 or e-mail: Andy.Vera@tucsonaz.gov
02/25/2008 LOREN MAKUS ENGINEERING REVIEW Denied Provide a tentative plat consistent with the development plan that is being reviewed by Jason Green.
02/26/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

February 26, 2008

Hank Hulbert
LEADS, Inc.
2400 North Central Avenue, #203
Phoenix, Arizona 85004

Subject: Circle K Store Tentative Plat

Dear Hank:

Your submittal of January 4, 2008 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

9 Copies Revised Tentative Plat (Wastewater, Addressing, Landscape, DUPD, Real Estate, ESD, Engineering, Zoning, DSD)

5 Copies Revised Landscape Plan (Landscape, DUPD, Engineering, Zoning, DSD)

2 Copies Color Elevations (DUPD, DSD)





Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: (602) 254-1700
Tp-resubmittal