Plan Number: S07-202
Parcel: Unknown

Address:
9430 E STEFAN RD

Review Status: Completed

Review Details: FINAL PLAT PACKAGE

Plan Number - S07-202
Review Name: FINAL PLAT PACKAGE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/18/2009 CDRC1 START FINAL PLAT PACKAGE Completed Mylar, copy of title, and copy of amended, recorded CCR's forwarded to engineering.
05/29/2009 BEVERLEY HESTER ENGINEERING ASSIGN REVIEW Completed Mylar package left with landscaping reviewer 5/19. Returned the same day.
05/29/2009 BEVERLEY HESTER ENGINEERING ASSIGN REVIEW Completed Mylar package left with zoning reviewer 5/20 and returned 5/27.
05/29/2009 BEVERLEY HESTER ENGINEERING ASSIGN REVIEW Completed To: Patricia Gehlen DATE: June 1, 2009
CDRC/Zoning Manager

SUBJECT: Stefan Acres, 9430 E. Stefan Rd.
Final Plat S07-202 (Second Review)
T14S, R15E, Section 15

RESUBMITTAL REQUIRED: Final Plat and Assurances.

The Final Plat (FP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Final Plat:

1. Please include a response letter to the comments along with the corrected copies of the FP.
2. Add a general note to the FP indicating that the original CCR's from "Lot 4 of Halcyon Acres, Bk. 6, M&P at Pg. 40" and recorded in Dkt. 10781, Pg. 987 will also be the CCR's for this project. Include all the recording numbers in the general note from the documents.
3. The pin description for the "Found location of 2"lead cap pipes" in two places along south side of Harrison Road R/W, indicates to see note no. 7. However general note 7 has to do with water service. Revise as required.
4. The title block of the plat must match the Subdivision Assurances verbatim or visa versa.
5. Submit the Subdivision Improvement Assurances for review. The following items are required in the assurance package if a Third Party Trust Agreement will be used: Per previous request.
" Title Report
" Special Warranty Deed
" Trust Agreement
" Amendment to Trust
" Agreement to Construct
6. Submit the above documents containing original signatures, copies of the documents and signatures will not be forwarded to the City of Tucson attorney for review. Per previous request.
7. Please submit a copy of the subdivision boundary closure calculations. Per previous request.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/9430 E. Stefan Rd. FP 2
06/01/2009 CDRC1 CDRC STAFF CITY AGENDA OFFICE Denied
06/01/2009 PAUL MACHADO ENGINEERING REVIEW Denied Mylar package left with landscaping reviewer 5/19. Returned the same day.
06/01/2009 CDRC1 CDRC STAFF CITY CLERK'S OFFICE Denied
06/01/2009 PAUL MACHADO ENGINEERING REVIEW Denied Mylar package left with zoning reviewer 5/20 and returned 5/27.
06/01/2009 PAUL MACHADO ENGINEERING REVIEW Denied To: Patricia Gehlen DATE: June 1, 2009
CDRC/Zoning Manager

SUBJECT: Stefan Acres, 9430 E. Stefan Rd.
Final Plat S07-202 (Second Review)
T14S, R15E, Section 15

RESUBMITTAL REQUIRED: Final Plat and Assurances.

The Final Plat (FP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Final Plat:

1. Please include a response letter to the comments along with the corrected copies of the FP.
2. Add a general note to the FP indicating that the original CCR's from "Lot 4 of Halcyon Acres, Bk. 6, M&P at Pg. 40" and recorded in Dkt. 10781, Pg. 987 will also be the CCR's for this project. Include all the recording numbers in the general note from the documents.
3. The pin description for the "Found location of 2"lead cap pipes" in two places along south side of Harrison Road R/W, indicates to see note no. 7. However general note 7 has to do with water service. Revise as required.
4. The title block of the plat must match the Subdivision Assurances verbatim or visa versa.
5. Submit the Subdivision Improvement Assurances for review. The following items are required in the assurance package if a Third Party Trust Agreement will be used: Per previous request.
" Title Report
" Special Warranty Deed
" Trust Agreement
" Amendment to Trust
" Agreement to Construct
6. Submit the above documents containing original signatures, copies of the documents and signatures will not be forwarded to the City of Tucson attorney for review. Per previous request.
7. Please submit a copy of the subdivision boundary closure calculations. Per previous request.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/9430 E. Stefan Rd. FP 2
06/01/2009 BEVERLEY HESTER ENGINEERING PROCESSING Passed Mylar package left with landscaping reviewer 5/19. Returned the same day.
06/01/2009 BEVERLEY HESTER ENGINEERING PROCESSING Passed Mylar package left with zoning reviewer 5/20 and returned 5/27.
06/01/2009 BEVERLEY HESTER ENGINEERING PROCESSING Passed To: Patricia Gehlen DATE: June 1, 2009
CDRC/Zoning Manager

SUBJECT: Stefan Acres, 9430 E. Stefan Rd.
Final Plat S07-202 (Second Review)
T14S, R15E, Section 15

RESUBMITTAL REQUIRED: Final Plat and Assurances.

The Final Plat (FP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Final Plat:

1. Please include a response letter to the comments along with the corrected copies of the FP.
2. Add a general note to the FP indicating that the original CCR's from "Lot 4 of Halcyon Acres, Bk. 6, M&P at Pg. 40" and recorded in Dkt. 10781, Pg. 987 will also be the CCR's for this project. Include all the recording numbers in the general note from the documents.
3. The pin description for the "Found location of 2"lead cap pipes" in two places along south side of Harrison Road R/W, indicates to see note no. 7. However general note 7 has to do with water service. Revise as required.
4. The title block of the plat must match the Subdivision Assurances verbatim or visa versa.
5. Submit the Subdivision Improvement Assurances for review. The following items are required in the assurance package if a Third Party Trust Agreement will be used: Per previous request.
" Title Report
" Special Warranty Deed
" Trust Agreement
" Amendment to Trust
" Agreement to Construct
6. Submit the above documents containing original signatures, copies of the documents and signatures will not be forwarded to the City of Tucson attorney for review. Per previous request.
7. Please submit a copy of the subdivision boundary closure calculations. Per previous request.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/9430 E. Stefan Rd. FP 2