Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Plan Review Detail
Review Status: Completed
Review Details: RECORD OF SURVEY REVIEW
Plan Number - S07-174
Review Name: RECORD OF SURVEY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2008 | PATRICIA GEHLEN | ZONING-RECORDATION | REVIEW | Needs Review | |
| 01/02/2008 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Denied | COMMUNITY DESIGN REVIEW COMMITTEE DEVELOPMENT SERVICES January 2, 2008 Christopher Rechlin FABOE 1 4151 East La Paloma Tucson, Arizona 85718 Subject: S07-174 Palo Verde Record of Survey Dear Christopher: Your submittal of November 5, 2007, for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed: ALL BLUELINES MUST BE FOLDED 8 Copies Revised Record of Survey (Traffic, Addressing, Real Estate, Assessor, Engineering, Zoning, Wastewater, DSD), 3 Copies Title Report (Real Estate, Engineering, DSD) 2 Copies Building floor plans and elevations (Zoning, DSD) 2 Copies Finalized Right-of-way permit (Engineering, DSD) Should you have any questions, please call me at 879-4919. Sincerely, Patricia Y. Gehlen CDRC Manager All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/ Via fax: 529-2964 |
| 01/02/2008 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Denied | March 26, 2010 Christopher Rechlin FABOE 1 4151 East La Paloma Tucson, Arizona 85718 SUBJECT: CLOSURE OF CDRC FILES Record of Survey Per Section 4.1.7.3, Maximum Review Period The subdivider has one (1) year from the date of Record of Survey submittal to obtain approval of the plans. Failure to obtain approval means the review period has expired Case # Case Name DSD Transmittal Date S07-174 Palo Verde Record of Survey November 5, 2007 Please note that this case has been closed and that, in order to continue review of the project, new development plan/tentative plat applications are required which comply with regulations in effect at the time of the new submittals. Thank you for your assistance. Sincerely, Patricia Y. Gehlen CDRC Manager xc: CDRC file S07-174 |
| 11/05/2007 | FERNE RODRIGUEZ | START | PLANS SUBMITTED | Completed | |
| 11/09/2007 | FRODRIG2 | PIMA COUNTY | WASTEWATER | Denied | November 8, 2007 To: T. Wayne Ashby, R.L.S. Thru: Patricia Gehlen, CDRC Manager City of Tucson Development Services Department ____________________________________ From: Felipe Ip, Sr. Civil Eng. Assistant Development Review Division Pima County Development Services Department Subject: Record of Survey 3001 N. Palo Verde, 1st submittal S07-174 The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use. Provide a letter from the PCWMD's Development Services Section, written within the past 90 days, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at: http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf. The record of survey for this project cannot be approved until a copy of this letter has been received by this office. Add the project number, S07-174, to the title block of each sheet. This number should be shown larger or bolder than any cross-reference numbers (e.g. re-zonings, etc) In DEDICATION: Add PIMA COUNTY between THE PUBLIC and AND ALL UTILITY COMPANIES. Add a Permitting Note so it states: A PROJECT CONSTRUCTION PERMIT MUST BE SECURED FROM THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT BEFORE BEGINNING ANY WORK ON THIS PROJECT. Add a General Note so it states: THE ON-SITE SANITARY SEWERS WILL BE PRIVATE AND WILL BE CONSTRUCTED, OPERATED AND MAINTAINED ON A PRIVATE BASIS, AND IN ACCORDANCE WITH AN APPROVED OPERATION AND MAINTENANCE AGREEMENT, IF REQUIRED. THE LOCATION AND METHOD OF CONNECTION TO AN EXISTING PUBLIC SANITARY SEWER IS SUBJECT TO REVIEW AND APPROVAL BY THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT. Add a General Note so it states: MAINTENANCE AND OPERATION OF THE PRIVATE SANITARY SEWERS (HCS) TO ITS POINT OF CONNECTION TO THE PUBLIC SEWER IS THE RESPONSIBILITY OF THE PROPERTY OWNER. Show the public and private sewer lines using different line-types, so that they can readily be distinguished from each other. Revise the Legend block accordingly. Label the properties surrounding the proposed project site (e.g. Parcel ID). Show the correct footprints of the existing houses on Parcels 1, 2 and 3, and their HCS connections to the public sewer main G-223 on N. Palo Verde Ave. Show how the proposed residence on Parcel 3 will be sewered. Add a label or keynote to each proposed HCS that states “New HCS per PCWMD Engineering Directive ENG-2005-01”. If the residences are to share a private HCS, the project will need to create a Sewer Access Easement for the HCS and a JOINT SEWER USE AND MAINTENANCE AGREEMENT for the portions of the private sewers that are shared by proposed parcels. The agreement will need to be reviewed and approved by Ms. Ilene Deckard of the Pima County Wastewater Management Department (740-6544). Revise the plan to show and label all public sewer elements that are located within 100’ or shown on this project. Label existing sewer lines with their Pima County construction plan numbers, pipe sizes, pipe materials, and flow arrows. Label all public manholes that are downstream from any existing and proposed House Connection Sewer (HCS) for this project with their IMS numbers, and rim and invert elevations. For example, show and label the existing public sewer east of the proposed project as EXIST. 8” VCP G-223 and the existing public manholes as EXIST MH 9809-82 and EXIST MH 9809-83. Existing public sewer information may be found on the PCWMD Maps and Records (5th floor) or on the PCWMD and PCDOT MapGuide internet websites. This office will require a revised set of plans, and a response letter, addressing these comments. Additional comments may be made during the review of these documents. The next submittal of this project will be the 2nd submittal. A check for the review fee of this submittal in the amount of $50.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter. If you have any questions regarding the above mentioned comments, please do not hesitate to contact me at 520-740-6706. CC: Project file |
| 11/13/2007 | TOM MARTINEZ | OTHER AGENCIES | AZ DEPT TRANSPORTATION | Approved | ADOT has NO COMMENT on the record of survey S07-174 FABOE 1 PALO VERDE -------------------------------------------------------- Confidentiality and Nondisclosure Notice: This email transmission and any attachments are intended for use by the person(s)/entity(ies) named above and may contain confidential/privileged information. Any unauthorized use, disclosure or distribution is strictly prohibited. If you are not the intended recipient, please contact the sender by email, and delete or destroy all copies plus attachments. |
| 11/14/2007 | PGEHLEN1 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Approved | |
| 11/19/2007 | CDRC1 | OTHER AGENCIES | PIMA ASSN OF GOVTS | Approved | >>> "Aichong Sun" <asun@pagnet.org> 11/19/2007 10:50 AM >>> CASE: S07-174, PALO VERDE RECORD OF SURVEY COMMENT: NO OBJECTIONS OR ADVERSE COMMENTS Vehicle Trip Generation: Daily: 29 PM Peak: 3 Please call if you have questions, Aichong Sun Pima Association of Governments 177 N. Church Ave, #405 Tucson, AZ 85701 Tel: (520) 792-1093, Fax: (520) 620-6981 Web: www.PAGnet.org and www.RTAmobility.com |
| 11/21/2007 | PETER MCLAUGHLIN | LANDSCAPE | REVIEW | Approv-Cond | Add the CDRC case number (S07-174) to the lower right hand corner of all sheets near the title block. |
| 11/23/2007 | ROGER HOWLETT | COT NON-DSD | COMMUNITY PLANNING | Approved | DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS Regarding SUBJECT: Community Design Review Committee Application CASE NUMBER: CASE NAME: DATE SENT S07-174 Palo Verde Record of Survey 11/21/07 ( ) Tentative Plat ( ) Development Plan ( ) Landscape Plan ( ) Revised Plan/Plat ( ) Board of Adjustment (XXXX) Other - Record of Survey CROSS REFERENCE: NEIGHBORHOOD PLAN: Grant-Alvernon GATEWAY/SCENIC ROUTE: COMMENTS DUE BY: 12/5/07 SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS: (XXXX) No Annexation or Rezoning Conditions, Not an RCP - No Comment ( ) Proposal Complies with Annexation or Rezoning Conditions ( ) RCP Proposal Complies with Plan Policies ( ) See Additional Comments Attached ( ) No Additional Comments - Complies With Planning Comments Submitted on: ( ) Resubmittal Required: ( ) Tentative Plat ( ) Development Plan ( ) Landscape Plan ( ) Other REVIEWER: drcorral 791-4505 DATE: 11/16/07 |
| 11/26/2007 | JOSE ORTIZ | COT NON-DSD | TRAFFIC | Approved | Traffic Engineering approves the Record of Survey, but the proposed driveway for the proposed residence will need to be modified to provide 12' of offset from the neighboring parcel's existing driveway to the west. |
| 11/27/2007 | GLENN HICKS | COT NON-DSD | PARKS & RECREATION | Approved | DATE: November 27, 2007 TO: DSD_CDRC@ tucsonaz.gov FROM: Glenn Hicks Parks and Recreation 791-4873 ext. 215 Glenn.Hicks@tucsonaz.gov SUBJECT: S07-174 Palo Verde Record of Survey(11-5-07) Parks and Recreation has no comments on this project. |
| 11/29/2007 | STEVE SHIELDS | ZONING | REVIEW | Denied | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Steve Shields Lead Planner PROJECT: Palo Verde Record of Survey S07-174 Record of Survey (1st Review) TRANSMITTAL DATE: November 29, 2007 DUE DATE: December 05, 2007 COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. D.S. 2-03.11.0 permits a maximum of one year from the date of application to obtain approval of a Record of Survey. If, at the end of that time, the development plan has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this record of survey is November 04, 2008. 2. Based on information within The City of Tucson's Permits Plus there are several permits that have expired, T06BU00084, 85, 86 and T06CM00260, these permits will need to be either finaled or renewed. The demo permits need to finaled prior to approval of the Record of Survey. The following comments are based on the provided record of survey: 3. Remove all development information from the Record of Survey, i.e. sight visibility triangles (SVT's), fencing and existing buildings. 4. D.S. 2-03.11.7.D Provide a location map that meets the minimum requirements of this section. 5. D.S. 2-03.11.7.F A title block with the following information is to be provided approximately in the lower right corner of the Record of Survey; D.S. 2-03.11.7.F.2 provide proposed name of the Record of Survey, D.S. 2-03.11.7.F.3 the number of proposed lots is to be noted. 6. D.S. 2-03.11.8.A.1 Based on the Pima County Assessors page the owners name is not totally correct. The assessor's page shows SURGES RICHARD J & MELISSA A JT/RS 50% & RECHLIN CHRISTOPHER C 50%. If it is dual ownership show both parties on the plan. 7. Place the Record of Survey case number S07-174 in the lower right hand corner of the plan. Remove the old lot split number, S0600014, from the plan. 8. D.S. 2-03.11.8.B.1 Revise note 3 to read "THE GROSS AREA OF THE EXISTING PARCLE IS 18,036.00 SQ. FT. 9. D.S. 2-03.11.9.A Provide a Certificate of Survey per this section. 10. D.S. 2-03.11.9.B Zoning acknowledges that a signature line has been provided under the Dedication, list the owners name under the line and provide an area for the date. 11. D.S. 2-03.11.10.C.3 All boundary monumentation must be labeled as "FOUND" or "SET". 12. D.S. 2-03.11.11.A If applicable, all existing easements of record will be drawn on the plan, and recordation information, locations, widths, and purposes shall be included. 13. D.S. 2-03.11.11.B The following information regarding the existing right-of-way (ROW) will be provided: indicate the ROW widths as ROW, recordation data, type and dimensioned width of paving, curb, curb cuts and sidewalks. 14. D.S. 2-03.11.11.B If applicable, show the required information in regards to existing utilities per this section. 15. D.S. 2-03.11.12.A If applicable, all proposed easements (utility, sewer, drainage, access, etc.) are to be dimensioned and labeled as to their purposes and whether they will be public or private. Recordation information (docket and page) must be included on the plan prior to final approval. 16. D.S. 2-03.11.12.A Show locations of all proposed driveways on the plan. 17. The proposed sidewalk, as shown on the plan, will require a pedestrian access easement for the area of the sidewalk that encroaches into the southeast corner of Parcel 3. A curb access ramp maybe required at this intersection of Palo Verde and Blacklidge, see engineering comments, if this is the case once shown correctly on the plan an easement may not be required. The following comments are based on the provided supplemental site plan 18. Remove all references to Record of Survey from the plan, i.e. dedication, recording data etc. 19. Provide a copy of the approved model plan for the existing and proposed structure, include floor plans and elevations. 20. Clearly indicate on the plan if the existing and proposed residence is a single family or duplex. 21. Show all utilities for all lots on the site plan. 22. Show the required sight visibility triangles (SVT's) on the plan. 23. Show the proposed sidewalk within the ROW along Palo Verde and Blacklidge on the plan, see comment 17 above. 24. Show the required zoning setbacks to all property lines. Once the model plan elevations have been provided, see comment 19 above, all setbacks can be verified. 25. Once the model plan elevations have been provided, see comment 18 above, required parking can be verified. 26. Provide a lot coverage calculation for each individual lot, there appears to be difference in vehicle use area between parcels 1 & 2 and parcel 3. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956. C:\planning\cdrc\record of survey\S07-174ros.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Record of Survey and additional requested documents. |
| 11/29/2007 | JIM EGAN | COT NON-DSD | FIRE | Approved | |
| 12/03/2007 | ANDY VERA | ENV SVCS | REVIEW | Approved | Adequate street frontage access for refuse and recycle curbside APC collection services. |
| 12/04/2007 | KAY MARKS | PIMA COUNTY | ADDRESSING | Denied | 201 N. STONE AV., 1ST FL TUCSON, AZ 85701-1207 KAY MARKS ADDRESSING OFFICIAL PH: 740-6480 FAX #: 740-6370 TO: CITY PLANNING FROM: KAY MARKS, ADDRESSING OFFICIAL SUBJECT: S07-174 PALO VERDE RECORD OF SURVEY DATE: 12/03/07 The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval: Project Location must be 3”= 1 mile. Please correct. Also, include S-T-R and shade the project. Add suffixes to all street names and spell out. Change Palo Verde Blvd. to Avenue. Change Blacklidge Road to Drive. Label lots 1-3 and include in Title Block along with the legal description on lower right hand corner. es |
| 12/04/2007 | FRODRIG2 | COT NON-DSD | REAL ESTATE | Denied | S07-174 Palo Verde Record of Survey: Record of Survey Review -No title report provided. -One owner owns the N. two lots (Parcels 1 & 2) and a separate owner owns the S. lot (Parcel 3). The Dedication block does not show this arrangement. -Request confirmation of the "1'" annotation along the W. boundary of subject Record of Survey. -Request clarification if the sidewalk would encroach w/in the SEC of Parcel 3. |
| 12/05/2007 | ED ABRIGO | PIMA COUNTY | ASSESSOR | Approv-Cond | Office of the Pima County Assessor 115 N. Church Ave. Tucson, Arizona 85701 BILL STAPLES ASSESSOR TO: CDRC Office Subdivision Review City of Tucson (FAX# 791-5559) FROM: Gary Ault, Mapping Supervisor Pima County Assessor’s Office Mapping Department DATE: December 3, 2007 RE: Assessor’s Review and Comments Regarding Tentative Plat S07-174 PALO VERDE –ROS- T131433 * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * X Plat meets Assessor’s Office requirements. _______ Plat does not meet Assessor’s Office requirements. COMMENTS: PLEASE MAKE THE FOLLOWING ADJUSTMENTS BY FINAL PLAT STAGE: THE TITLE BLOCK SHOULD INCLUDE “LOTS 1-3”. ADD “RESUB OF 4/89 M&P” TO TITLE BLOCK. ADD RECORDING FOR EXISTING STREETS. SHOW TIE TO THE SECTION WITH DIMS AND BEARINGS. THANK YOU FOR YOUR SUBMITTAL. IF YOU HAVE ANY QUESTIONS PLEASE CALL ROSANNA WERNER AT 740-4390 ROSANNA WERNER |
| 12/10/2007 | JASON GREEN | ENGINEERING | REVIEW | Denied | DATE: December 10, 2007 SUBJECT: UN-named Record of Survey- Engineering Review TO: Patricia Gehlen, CDRC Manager LOCATION: 3001 N Palo Verde Blvd, T13S R14E Sec33 Ward 3 REVIEWERS: Jason Green, CFM ACTIVITY: S07-174 SUMMARY: Engineering Division of Development Services Department has received and reviewed the Record of Survey. The Record of Survey is not approved at this time. Please address the following comments: RECORD OF SURVEY COMMENTS: 1) Revise the Record of Survey (Sheet 1) to only include Horizontal references, General Notes, Easements, Dedication Language, Certificate of Survey, Curve Table, Location Map, Street and Right of Way dimensions, and Recording Data. All improvements (houses, walls, fencing,) and details (sidewalk, curbing, sight visibility triangles, driveway access, handicap curb access) shown in plan view should be provided on a supplemental sheet (Sheet 2). Provide dimensions and improvements to be constructed within the right-of-way on Sheet 2. 2) Provide a supplemental sheet (Sheet 2) for all information that is required but can not be shown on a Record of Survey (Sheet 1). Specifically, the supplemental sheet must include all existing and proposed sidewalks, curbing, water/sewer lines, fire hydrants, driveway locations with setback dimensions, walls, fences, and all other information that is required per DS Sec.2-03 Land Survey Exception. 3) DS Sec.2-03.11.1.C: Provide documentation showing that the required 5-foot wide sidewalk with curb has been installed, documentation can be in the form of a finalized right-of-way use permit. The permit application submitted does not show that the Tucson Department of Transportation has finalized the construction of the sidewalk and curb. The 5-foot sidewalk must be installed prior to Record of Survey approval. Revise the supplemental sheet of the ROS to label the sidewalk as 5-feet. 4) Revise the location of the proposed sidewalk at the intersection of Blacklidge Rd and Palo Verde Blvd. The proposed sidewalk, as shown, will require a pedestrian access easement for the portion of the sidewalk that encroaches into the southeast corner of Parcel 3. Verify on the supplemental sheet that a handicap curb access ramp is being constructed at the intersection of Palo Verde Blvd and Blacklidge Rd. The easement will not be required if the sidewalk is constructed entirely within the public right-of-way. 5) DS Sec.2-03.11.7.D.1: Revise the project location map to show the subject property approximately centered within a 1 square mile area. 6) DS Sec.2-03.11.7.D.2: Revise the project location map to identify conditions within the square mile area, such as major watercourses and recorded subdivision plats, reference all recorded plats by book and page numbers. 7) DS Sec.2-03.11.7.D.3: Provide the Section, Township and Range section corners on the project location map after re-centering the subject parcel. Provide the map at a scale of 3 inch equals 1 mile. 8) DS Sec.2-03.11.7.F: Revise the title block with the following information in the lower right corner of the Record of Survey: 1) Provide the proposed name of the Land Survey Exception; 2) Provide the number of proposed lots. 9) DS Sec.2-03-11.8.A.1: Revise the ownership note on the Record of Survey. Per the Pima County assessor's page it shows SURGES RICHARD J & MELISSA A JT/RS 50% & RECHLIN CHRISTOPHER C 50% as owners of the subject property. If it is dual ownership show both parties on the plan. 10) DS Sec.2-03.11.8.B.1: Revise the Record of Survey to indicate the subdivision cases number assigned (S07-174), it may be added to the lower right hand corner of the plans. 11) DS Sec.2-03.11.8.B.4: Revise General Note #3 of the Record of Survey to read: "The total gross area of the existing parcel is 18,036.00." 12) DS Sec.2-03.11.9.A: Provide the following paragraph signed and sealed by a Registered Professional Land Surveyor," I hereby certify that the boundary survey as shown on this Record of Survey was performed under my direction and that all existing or proposed survey monuments and markers shown are correctly described. I further certify that this Record of Survey was prepared under my direction." 13) DS Sec.2-03.11.9.B: Revise the signature lines for the property owners to include property owners names under the line and include an area for the date of the signatures. 14) DS Sec.2-03.11.10.A: Revise the Record of Survey to indicate primary control points, or descriptions and ties to such control points, to which all dimensions, angles, bearings, and similar data on the Record of Survey will be referred. Specifically, course and distance must tie at least one (1) corner of the property to the section corner or the quarter section corner, or an established City or County survey monument. The plan must include a description of that corner marker and an indication of how the bearings were determined. Corner tie recordation information is to be provided on the plan. 15) DS Sec.2-03.11.10.C.1: Provide the description for the 2 found physically monumented points for the Basis of Bearing shown on the plan. If the monuments at each end of the reference line are fully described on the plan, they need not be described in the Basis of Bearing statement. 16) DS Sec.2-03.11.11.A: Verify that all easements of record are drawn on the plan, and recordation information, locations, widths and purposes are included. Provide a copy of the latest Title Report that shows all existing or abandoned easements must be current within 90 days. 17) DS Sec.2-03.11.11.B: Provide the following information regarding the existing public right of way for both Palo Verde Blvd and Blacklidge Road: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts and sidewalks. 18) DS Sec.2-03.11.11.C: Provide the location of any adjacent fire hydrants, storm drains and sanitary sewers, including pipe diameter and the invert and rim elevations of all manholes and clean outs. If water mains and sewers are not located on or adjacent to the property indicate the direction, distance to, and size of those nearest the property. 19) DS Sec.2-03.11.12.A: Revise the Record of Survey to show that all proposed easements (utility, sewer, access, etc.) are dimensioned and labeled as to their purpose and whether they will be public or private. Recordation information must be included on the plan prior to final approval. 20) DS Sec.2-03.11.12.E: Revise the supplemental sheet to show all adjacent and proposed driveways to verify the 12-foot minimum setback required between driveways. Provide on the supplemental sheet the dimensions of the proposed driveway width (the maximum driveway width for residential driveways is 20 feet). Any unused curb cuts must be closed. Give star designations for the corner lots access point. 21) DS Sec.6-01.4: Provide a letter from Environmental Services for curbside pickup. GENERAL COMMENTS: Please provide a revised Record of Survey, supplemental information sheet, a finalized right-of-way use permit, and a current Title Report that address the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments. Further comments may be generated upon resubmittal of the Record of Survey and additional documentation. For any questions or to schedule a meeting, call me at (520)-837-4929. Jason Green, CFM Senior Engineer Associate Engineering Division Development Services |
| 12/10/2007 | ROBERT YOUNG | PIMA COUNTY | PIMA CTY - DEV REVIEW | Passed | |
| 12/27/2007 | LIZA CASTILLO | UTILITIES | TUCSON ELECTRIC POWER | Approved | 4350 E. Irvington Road, Tucson, AZ 85714 Post Office Box 711, Tucson, AZ 85702 WR#190743 December 27, 2007 FABOE 1 Attn: Christopher Rechlin 4151 E La Paloma Tucson, Arizona 85718 Dear Mr. Rechlin: SUBJECT: Palo Verde Record of Survey S07-174 Tucson Electric Power Company has reviewed and approved the development plan submitted November 15, 2007. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development. Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer. In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans. If easements are required, they will be secured by separate instrument. Your final plans should be sent to: Tucson Electric Power Company Attn: Ms. Mary Boice New Business Project Manager P. O. Box 711 (DB-101) Tucson, AZ 85702 520-917-8732 Should you have any technical questions, please call the area Designer Warren McElyea at (520) 918-8268. Sincerely, Elizabeth Miranda Office Support Specialist Design/Build lm Enclosures cc: DSD_CDRC@tucsonaz.gov, City of Tucson (email) w. McElyea, Tucson Electric Power |