Plan Number: S07-158
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW

Plan Number - S07-158
Review Name: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/02/2008 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
07/07/2008 FRODRIG2 PIMA COUNTY WASTEWATER Approved July 3, 2008


To: Maolin Zheng
BSW International

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

___________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environment Quality

Subject: Walmart Store #4684-00
DP/TP – 3rd Submittal
S07-158


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan as submitted.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you have any questions regarding the above-mentioned comments, please contact me.
07/11/2008 STEVE SHIELDS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Steve Shields
Lead Planner

PROJECT: Wal-Mart Store #4684-00 - Tentative Plat
Valencia & Alvernon
S07-158 (3rd Review)

TRANSMITTAL DATE: July 11, 2008

DUE DATE: July 31, 2008

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

The Zoning Review Section conditionally approves the tentative plat/development plan for this subdivision, subject to the following changes on the executed tentative plat. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised tentative plat to verify that those changes do not affect any zoning requirements.

D.S. 2-05.2.4.D.P Parking space detail 1/C2 has been removed from the plan and appears to be relocated to Sheet C6. Per LUC Section 3.3.7.2 provide the "A" Parking Angle, "C" Space Depth, "E" Curb Length on the detail.

D.S. 2-05.2.4.D.Q The bicycle parking calculation is not correct. Based on 497 vehicle parking spaces provided, 497 x 8% = 39.76. Per LUC 3.3.3.8 Fractional Amounts. When the final result of the calculation of required motor vehicle and bicycle parking spaces results in a fractional number, a fraction of one-half (½) or more is adjusted to the next higher whole number, and a fraction of less than one-half (½) is adjusted to the next lower whole number. This said the total number of required bicycle parking is forty (40). Please revise the bicycle parking calculation.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\cdrc\tentativeplat\S07-158tpdp-3rd.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised tentative plat, and additional requested documents.
07/17/2008 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
07/17/2008 JOE LINVILLE LANDSCAPE REVIEW Approv-Cond 1) Show the trail easement proposed on the landscape plan on the tentative and final plats, if applicable.

Per LUC 4.1.8.4 "Easements shall be provided for utilities, vehicular and pedestrian access, drainage, and other purposes as required by the appropriate utility agency or City department".
07/24/2008 GLENN HICKS COT NON-DSD PARKS & RECREATION Approv-Cond PARKS AND RECREATION DEPARTMENT COMMENTS

City of Tucson CDRC – Community Design Review Committee

CASE NAME & NUMBER: S07-158, Wal-Mart Store #4684-00, TP/DP
Southwest corner Valencia & Alvernon
Submittal #: 3

COMMENTS DUE: 7/31/08 COMMENTS SENT: 7/22/08


Items reviewed: Tentative Plat/Development Plan and Landscape Plan

Related: rezoning - N/A, being developed under existing I-1 zoning
land use plan(s) – General Plan

Parks and Recreation Department Staff has reviewed this proposal and offers the following comments:


CONDITIONALLY APPROVED – Subject to revising landscape plans as per comment #1 below. No resubmittal to Parks required. See comment #2 regarding the potential future dedication of a trail easement.

Please remove all references to a 35-foot-wide trail easement on the landscape plan. Although staff is requesting such a dedication (see comment #2 below), it is our understanding that an agreement to dedicate has not been reached yet.

As per previous comments, staff requests dedication of a 35-foot-wide, public, non-motorized recreational trail easement to the City of Tucson, along the southern 35 feet of the site, for a trail along the Rodeo Wash. Discussions with the developer’s representatives continue, and if agreement is reached, the easement may be dedicated in the future, either by final plat or separate instrument.




REVIEWER: Joanne Hershenhorn DATE: 7/22/08








S:\PARKS_AND_RECREATION_DEPT\REVIEW_COMMENTS\CDRC_Cases\2008_ReviewsS07-158a_Wal_Mart_Val_Alv.doc
07/31/2008 PAUL MACHADO ENGINEERING REVIEW Approved To: Patricia Gehlen DATE: July 30, 2008
CDRC/Zoning Manager


SUBJECT: Wal-mart Store, 3786 E. Valencia Road
Tentative Plat S07-158 (Third Review)
T15S, R14E, Section 16

RESUBMITTAL REQUIRED: Tentative Plat and Drainage report.


Tentative Plat:

1. Please include a response letter to the comments along with the corrected copies of the TP.
2. The proposed parcel that Wal-mart will be occupying must accept and/or account for the drainage of the 3 proposed lots on the East side of the project per Arizona Revised Statutes.

Drainage Report:
3. Please include a response letter to the comments along with the corrected copies of the DR.
4. Address the amount of storm water coming from the 3 proposed lots on the East side of the project per Arizona Revised Statutes.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.govs
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:/3786 E. Valencia Rd_CDRC_3
07/31/2008 PAUL MACHADO ENGINEERING REVIEW Approved All comments have been addressed. PM. 08-18-08
08/06/2008 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Approved To Whom It May Concern: :

SUBJECT: WAL-MART STORE #4684-00 (RESUBMITTAL)
S07-158


Tucson Electric Power Company has reviewed and approved the development
plan submitted July 3, 2008.


Alberta Adrian
Office Specialist
918-8347 Ofc.
793-7504 Pgr.
08/22/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

August 16, 2008

Maolin Zheng
BSW International, Inc.
10835 North 25th Avenue
Phoenix, Arizona 85029

Subject: S07-158 Wal-Mart Store #4684-00 Tentative Plat

Dear Maolin:

Your submittal of July 3, 2008 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

5 Copies Revised Tentative Plat (Zoning, Engineering, Landscape, Parks and Recreation, DSD)

Copies Revised Landscape Plan (Zoning, Engineering, Landscape, Parks and Recreation, DSD)

2 Copies Revised Drainage Report (Engineering, DSD)

DUE TO THE NUMBER AND TYPE OF CONDITIONAL APPROVALS, ANOTHER SUBMITTAL IS REQUIRED.


Should you have any questions, please call me at 837-4919.

Sincerely,

Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: (602) 567-2560
08/22/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approv-Cond COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES
***REVISED***


August 22, 2008

Maolin Zheng
BSW International, Inc.
10835 North 25th Avenue
Phoenix, Ariozna 85029

Subject: S07-158 Wal-Mart Store #4684-00 Tentative Plat

Dear Maolin:

The above referenced development plan has been CONDITIONALLY APPROVED by the Community Design Review Committee. Once the necessary corrections are made per the on-line comments, please submit the following documents for sign-off.

1 Double Matte right-reading Océ or Photo Mylar of the COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal).
AND
1 Double Matte right-reading Océ or Photo Mylar of the Development Plan.
AND
1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

The extra Double Matte right-reading Océ or Photo Mylar that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete mylar set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the mylar and two (2) blackline copies to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

TO ENSURE A MORE RAPID REVIEW OF THE MYLARS, PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.ci.tucson.az.us/dsd/CDRC Rezoning/CDRC/CDRC Stamp/cdrc stamp.html.

Should you have any questions, please call me at 837-4919.


Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: (602) 567-2560