Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Plan Number: S07-154
Parcel: Unknown

Review Status: Completed

Review Details: TENTATIVE PLAT REVIEW

Plan Number - S07-154
Review Name: TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2008 ELIZABETH EBERBACH ENGINEERING REVIEW Denied TO: Patricia Gehlen; CDRC Coordinator
FOR: Kent Delph, PE Grenier Engineering
SUBJECT: Brichta Wash Townhomes Tentative Plat Engineering Review
LOCATION: T14S R13E Section 3
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: S07-154

SUMMARY: Engineering has reviewed the Tentative Plat, Landscape documents, and Drainage Report and does not recommend approval of the Tentative Plat or the Drainage Report at this time. The Drainage Report was reviewed for Tentative Plat purposes only.

DRAINAGE REPORT COMMENTS:
1) City of Tucson Development Standards (DS) Section No. 10-01.4.3.1: Address the following basin comments:
a) DS Sec.10-02.2.3.1.3.A: Address the following offsite hydrologic comments:
i) Verify Offsite Area 2 watershed area. South boundary of watershed appears truncated.
ii) After correcting watershed area, revise the following:
(1) Hydrologic data sheet for Offsite Area 2.
(2) Hydrologic Summary table on page 2 of the report.
iii) Correct associated basin calculations.
b) DS Sec.10-01.2.2: Discuss capacity of existing Brichta Wash drainage channel including downstream culvert and impact from proposed runoff from development and proposed detention.
c) DS Sec.10-01.2.1: Revise detention calculations in the drainage report to provide balanced basin detention reduction for the development to assure that the developed peak discharges do not exceed the existing 2- and 10-year peak discharge events.
d) DS Sec.10-01.3.Table 3.4: Retention volume appears too low; check runoff coefficient data for retention calculation by addressing the following comments:
i) Provide calculations for any Cw's not directly from table 3.4.
ii) Explain which columns and assumptions are used for the 5-yr retention runoff coefficients.
e) DS Sec.10-01. 3.3.2: Clarify and revise routing and provide a storage-discharge table incorporating inflow and outflow hydrograph data. Also, discuss results in a conclusion section of the drainage report.
f) DS Sec. 10-01.4.3: Where human activity zones are proposed in the basin area, 8:1(H:V) side slopes are needed at location of pedestrian access, and shall not conflict with inlets to the basin.
g) DS Sec. 10-01.4.3: Wall along north side of basin will not be accepted. Revise design to meet basin requirements per this section of the standards.
h) DS Sec. 10-01.4.3.1: Continuous slopes shall not exceed 20% of the basin perimeter. Show varying basin perimeter design.
i) Revise basin size and project layout to provide for sufficient basin volume after addressing the above comments.
j) DS Sec.10-01.3.3.4: State that erosion protection will be required for unattenuated flow conditions for the basin side slopes. Show on the plan and sections.
k) DS Sec.10-01.III.3.5.1.3.a: Discussion of infiltration test results will be required in drainage report to demonstrate the drain time for the retained stormwater for proposed Common Area "A" basin meets the maximum disposal time.
2) DS Sec.2-03.2.4.L: Clarify / address the following Brichta Wash drainage comments:
a) Add discussion in the Drainage Report stating whether the existing conditions of Brichta Wash convey the jurisdictional flow within the channel.
b) State freeboard height with respect to low chord elevation of existing crossing structure.
c) A palo verde tree was seen growing out of the middle of the concrete box culvert bridge structure. Discuss the existing condition of the structure in the Drainage Report. Provide a current or latest copy of the Bridge Report for this structure showing that the existing condition of the crossing can be utilized for the proposed development. Also, provide correspondence documentation from TDOT stating acceptance of crossing structure's condition for subdivision.
d) State maintenance responsibility of bridge in report.
3) DS Sec.2-03.2.4.L.2: Clarify the following proposed drainage solutions:
a) State stormdrain pipe outlet maintenance responsibility in report.
b) Provide discussion and cross section in report that describes existing wash embankment.
c) Provide clarification of developed conditions drainage exhibit.
i) Label existing and post developed flowrates at proposed pipe outlet into Brichta Wash showing that no increased flowrate is flowing into Brichta Wash.
ii) Show flows arrows for street flows and label concentration points.
d) DS Sec.2-03.2.4.L.5: Verification is required when any drainage solution occurring outside the boundaries of the plat is constructed with adjacent owners' permission.
i) Additional documentation of TDOT approval of the proposed pipes entering Brichta Wash from the basin will need to be submitted with the drainage report.
ii) Authorization is also required for improvements proposed at south corner of project where a proposed drop inlet basin is proposed.
e) DS Sec.1.5.1: Sidewalk with scuppers are required at street stormwater entrances to basins; provide scupper calculations.
f) DS Sec.10-02 page 8.06: Table 8.1: For determining capacity of proposed roadways, provide worksheets for roadway capacities to reflect a roadway Manning's coefficient of .020 for the maximum value for asphalt when cars are present, per this section of the standards.
4) For the proposed stormdrain system address the following:
a) Clarify in report or on drainage exhibit CP1 and CP2 references in grade line table data sheet in appendix.
b) In the Drainage Report, discuss assumptions for losses for the hydraulic grade line analysis for the proposed HDPE stormwater drainage system to demonstrate that the friction losses at the bends/manholes for the system have been accounted for in the sizing of the pipes in the system.
5) DS Sec.10-02.2.3.1.1.B: Label the administrative / site address and subdivision case number on the front cover of report.
6) DS Sec.10-02.1.5.1: Regarding basin maintenance checklist, add drainage facilities including catch basin inlets, stormdrain pipes, and stormdrain pipe outlets to the Drainage Report in a drainage maintenance list. At minimum, this will be required at Grading Plan review.
7) DS Sec.10-02.14.3.2: The maintenance notes specified in this section must be included on the Final Plat or in the CC&Rs. At minimum, this will need to be addressed at Final Plat stage.
8) DS Sec.10-02.5.5.1: Show floodplain limits on cross sections 3 and 5 on sheet 2.
9) DS Sec.2-03.2.3.J.2: Calculate the 100-year water surface elevations along Brichta Wash and state datum for calculations in report. WSEL's shall be determined at minimum every 200-feet and derive minimum finish floor elevations.
10) DS Sec.10-02.2.4: Add assumptions section to the drainage report discussing assumptions made in the report including the acceptance of the Cella Bar data.
11) DS Sec.10-02.2.3.1, 10-01.5.2: Only existing and design conditions sections were provided in the drainage report. Assure sufficient drainage information is provided and discussed in the drainage report - see these sections of the Det/Ret and City's drainage manuals for further minimum report requirements.

TENTATIVE PLAT COMMENTS:
12) DS Sec.10-01.III.3.5.1.3.a, 10-02.14.2.6: Submit a bound copy of the soils report that discusses suitability and feasibility of the project; the report should discuss existing geotechnical conditions, and proposed recommendations for foundations and pavement design. Infiltration test results will be required to be submitted. The geotechnical report shall specifically address all criteria listed in this section. See last sentence of this section for items 6 (c) & (d) regarding hydro-collapsing soils and 30-foot test boring for basin design. Infiltration rates shall meet Water Harvesting and Detention / Retention criteria per DS Sec.10-01.III.3.5.1.3.a. Geotechnical recommendations for building or pavement setbacks from basins will be provided.
13) DS Sec.2-03.2.3.J: Address comments for the following drainage elements:
a) Label 8:1(H:V) side slope grades for side slopes for human activity zone emergency exits.
b) Label and dimension all basin setbacks from:
i) Existing parcel at the north of the basin.
ii) Buildings for lots 13 and 14.
c) Provide cross sections on tentative plat that describes material and labels dimensions of existing wash embankment.
d) Assure easement data is correct (see R-87-10 right-of-way plans) and shown on the tentative plat including drainage swale easement Dkt.5427 pg.597, and 20-ft stormdrain pipe easement.
e) Label dimensions of the Brichta Wash drainage way.
f) Delineate and label width for drainage easements for proposed stormdrain systems on planview.
g) Clearly delineate the 100-year WSEL's along Brichta Wash at minimum every 200-feet on planview sheet 3 of the Tentative Plat.
h) Label scuppers at basin entrance per revised drainage report. Scuppers may not conflict with basin maintenance entrance.
14) DS Sec.2-03.2.4.L.4: For clarification of proposed flow conditions, provide typical lot grading detail, that shows direction of drainage around proposed lots and explains the following:
a) Clarify and provide flow arrows, area for mechanical equipment, A/C unit locations, swale dimensions, slope setbacks for screen walls, slope run-outs, building setbacks, minimum slope grades, and general access.
b) Show general / typical high point or grade break locations, as well as minimum flow grades around building pads.
15) DS Sec.2-03.2.4.C: Clarify property limits and check linetypes for sheet index map on sheet 1.
16) DS Sec.2-03.2.1.J: For the legend, address the following comments:
a) Existing bollard symbol.
b) Clarify existing and proposed rip rap.
c) Clarify all easement delineations in legend - providing differentiated linetypes to clarify easements. Easement lines along west side of project need clarification.
17) DS Sec.2-03.2.3.A: Label the basis of elevation location (or local benchmark elevation with datum) on planview.
18) DS Sec.2-03.2.3.F.1: Label contour lines.
19) DS Sec.2-03.2.3.C: Provide a copy of the Title Report, Schedule B for current easement data. All existing easements need to be drawn on the plat, and recordation information, locations, widths, and purposes shall be included. If easements are relocated, not in use, or proposed for abandonment, then the documentation of the vacation/abandonment/relocation shall be submitted prior to approval of Final Plat. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Any easements in conflict with proposed footprints of new buildings must be resolved prior to Final plat approval. There appears to be an existing water line in conflict with proposed structures that must be physically abandoned prior to Final Plat approval, otherwise revise layout.
20) DS Sec.2-03.2.3.E: Provide information of the following existing conditions:
a) Existing CMU wall opening locations along east boundaries.
b) Show location of any fire hydrants within 100 feet of the site.
c) Describe all existing structures and whether they will be removed or relocated.
21) DS Sec.2-05.2.4.F: Address the following access comments:
a) Only one access is indicated for project, across the bridge. Clarify emergency access area to the project. Verification will need to be provided for the access improvement as well as any proposed new utility easements, which occur outside the boundaries of the development plan area, such that it is constructed with adjacent owners' permission. (Additional notarized documentation of that approval will be submitted).
b) Show access for tract A.
22) DS Sec.2-03.2.4.F: Address the following street comments:
a) DS Sec.3-01.10.Fig.22: On planview sheets, show 50-foot ROW tangents, label 60-foot radial dimensions, and revise proposed survey monument locations for standard curb knuckle.
b) DS Sec.3-01.3.3: Clarify sidewalk connections adjacent to crossing structure.
c) Provide a copy of the proposed private street design plans.
d) Provide cross section at bridge with drainage data - low chord elevation, WSEL, freeboard dimensioned, and wash contour.
23) DS Sec.2-03.2.4.L.4: Provide clarification of FFE with respect to the finished pad grade for the lots as well as per minimum FFE's with respect to WSEL's.
24) DS Sec.2-03.2.4.M: Label SVT's on planviews on landscape plan.
25) DS Sec.11-01.2.1.A: A Grading Plan and Permit and floodplain use permit will eventually be required. Proposed developments exceeding 1 acre are subject to AzPDES requirements.

The next submittal should address all the above items. Submit soils report, authorization documentation, revised Drainage Report, and revised Tentative Plat. You may schedule a meeting to go over comments, or if you have any questions, please call me at 837-4934.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services
01/07/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

January 7, 2008

Kent A. Delph, P.E.
Grenier Engineering, Inc.
1660 North Alvernon Way
Tucson, Arizona 85712

Subject: S07-154 Brichta Wash Townhomes Tentative Plat

Dear Kent:

Your submittal of October 10, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

8 Copies Revised Tentative Plat (Wastewater, Zoning, Landscape, Real Estate, DUPD, ESD, Engineering, DSD)

5 Copies Revised Landscape Plan (Zoning, Landscape, DUPD, Engineering, DSD)

2 Copies Revised NPPO Plan (Landscape, DSD)

2 Copies Soils Report (Engineering, DSD)

2 Copies Authorization Documentation (Engineering, DSD)

2 Copies Revised Drainage Report (Engineering, DSD)

Should you have any questions, please call me at 837-4919.

Sincerely,

Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 326-7508
10/10/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
10/12/2007 JIM EGAN COT NON-DSD FIRE Approved
10/18/2007 FRODRIG2 PIMA COUNTY WASTEWATER Denied October 17, 2007


To: Kent Delph
Grenier

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

___________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environment Quality

Subject: Brichta Wash Town Homes Subdivision Lots 1-50, Common Area "A", "B" & "C" and Tract "A"
Tent. Plat - 1st Submittal
S07-154


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

This project will be tributary to the Roger Road Wastewater Treatment Facility via the North West Outfall.
Requires Capacity Determination Letter from the owner of the private sewer to which connection is proposed. County capacity response exists : #07-145 (7/20/07).

A Joint Use and Maintenance Agreement between this project and the owner of the private sewer you are proposing to connect into will be required before this office will be able to approve this development plan. Prior to signature or recordation, this agreement must be reviewed and approved by Ms. Ilene Deckard of the PCWMD Development Services Section. Please contact Ms. Deckard about this matter as soon as possible. She can be reached at 740-6544.

All Sheets: Show the jurisdiction’s case number, S07-154, in or near the title block of each sheet. This case number should be shown larger and bolder than any associated cross-reference numbers.

Sheet 1: Revise Sanitary Sewer General Note #2 to read as follows:

THE ON-SITE SANITARY SEWERS WILL BE PRIVATE AND WILL BE CONSTRUCTED, OPERATED AND MAINTAINED ON A PRIVATE BASIS, AND IN ACCORDANCE WITH AN APPROVED OPERATION AND MAINTENANCE PLAN, IF REQUIRED. THE LOCATION AND METHOD OF CONNECTION TO AN EXISTING PUBLIC SANITARY SEWER IS SUBJECT TO REVIEW AND APPROVAL BY THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT.

Sheet 4: There are two proposed private manholes identified as #9. Please revise accordingly.

Sheet 4: Show the size of pipe and flow direction for the existing private sewer shown on plan.

Sheet 4: The invert shown for MH#7 does not allow for gravity flow of sewer. Please revise accordingly.

Sheet 4: Show the sewer line invert in relation to drainage pipes wherever the two cross.

Sheet 5: It will be necessary to demonstrate access method to existing private manhole which will be in the rear of proposed Lot 20 for maintenance and emergencies.

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the tentative or preliminary plat. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the second (2nd) submittal. A check for the review fee of this submittal in the amount of $150.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above-mentioned comments, please contact me.
10/23/2007 KAROL ARAGONEZ ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Karol Aragonez
Planner

PROJECT: S07-154
Brichta Wash Townhomes
Tentative Plat

TRANSMITTAL DATE: October 16, 2007

DUE DATE: November 7, 2007

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Zoning Review staff considers this submittal a change of use from the previous preliminary concept (C9-81-23) that was submitted and approved by Mayor and Council. Previous concept was for multifamily development (changes from original commercial concept) with proposed access approved by Mayor and Council to Grant Road and with connections to existing multi-family units to the south. Staff recommends that this tentative plat be sent back to rezoning staff for consultation. Approval of the change of use, which includes access points, may require approval by Mayor and Council.


If you have any questions about this transmittal, please call David Rivera or Glenn Moyer, (520) 791-5608.

KAA S:\zoning review\karol\planning\cdrc\tentativeplat\S07-154tp.doc
10/26/2007 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved CASE: S07-154, BRICHTA WASH TOWNHOMES: TENTATIVE PLAT REVIEW

COMMENT: NO OBJECTIONS OR ADVERSE COMMENTS




Vehicle Trip Generation: Daily: 293 PM Peak: 26



Please call if you have questions,



Aichong Sun

Pima Association of Governments

177 N. Church Ave, #405

Tucson, AZ 85701

Tel: (520) 792-1093, Fax: (520) 620-6981

Web: www.PAGnet.org and www.RTAmobility.com
10/26/2007 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR#189234 October 26, 2007

Cerenier Engineering Inc.
Attn: Kent Delph
1660 N Alvernon Way
Tucson, Arizona 85712

Dear Mr. Delph:

SUBJECT: Brichta Wash Townhomes
S07-154

Tucson Electric Power Company has reviewed and approved the development plan submitted October 3, 2007. It appears that there are no conflicts with the existing facilities within the boundaries of this proposed development

Enclosed is a copy of a TEP facilities map showing the approximate location of the existing facilities. Any relocation costs will be billable to the customer.

In order to apply for electric service, call the New Construction Department at (520) 918-8300. Submit a final set of plans including approved site, electrical load, paving off-site improvements and irrigation plans, if available include a CD with the AutoCAD version of the plans.

If easements are required, they will be secured by separate instrument. Your final plans should be sent to:
Tucson Electric Power Company
Attn: Ms. Mary Boice
New Business Project Manager
P. O. Box 711 (DB-101)
Tucson, AZ 85702
520-917-8732

Should you have any technical questions, please call the area Designer Mike Kaiser at (520) 918-8244.

Sincerely,


Elizabeth Miranda
Office Support Specialist
Design/Build
lm
Enclosures
cc: DSD_CDRC@tucsonaz.gov, City of Tucson (email)
M. Kaiser, Tucson Electric Power
10/31/2007 JOE LINVILLE LANDSCAPE REVIEW Denied 1) The NPPP aerial photo received was too light. Submit a photo with more detail.

2) Provide canopy trees in the vehicular use area such none are more than forty feet from a canopy tree. LUC 3.7.2.3
There is one space on the east side of the project that does not meet the requirements.

3) Revise the common area designation for the "open space" between lots 36 & 37 on sheet 4 of the tentative plat. It appears to be a parking lot, rather than open space.

4) Revise the landscape and development to clarify compliance with the screening requirements for common areas containing vehicular use areas plans at the southern boundary of the site. A 5' high masonry screen wall is required at the property line per LUC Table 3.7.2-I.

5) Per the previously approved plans, a landscape buffer is shown on both sides of Brichta Wash. The buffer is necessary and consistent with the provisions of TCC 26-8(3).

6) Reference the rezoning case number(s) on the plans. Note the conditions on plans and provide correspondence addressing how any conditions have been addressed.
11/06/2007 KAY MARKS PIMA COUNTY ADDRESSING Approv-Cond 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S07-154 BRICHTA WASH TOWNHOMES/TENTATIVE PLAT
DATE: November 5, 2007



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

ON FINAL PLAT
LABEL APPROVED INTERIOR STREET NAMES.



***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through Pima
County Addressing. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County’s
Geographic Information System. Your support is greatly appreciated.***


jg
11/07/2007 CDRC1 COT NON-DSD REAL ESTATE Denied >>> Andy Steuart 11/07/2007 12:53 PM >>>
S07-154 Brichta Wash Townhomes: Tentative Plat Review
-Per Easement Keynote 10, Dkt./Pg. 9133/1975 does not provide an ingress/egress easement as stated.
-As of 11/7/07, it appears property taxes for 2006 are not paid.

Andy
(520) 837-6715
Real Estate Division

fax 791-5641
11/08/2007 JOSE ORTIZ COT NON-DSD TRAFFIC Approved
11/09/2007 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Passed
11/09/2007 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Passed
11/13/2007 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)
FROM: Gary Ault, Mapping Supervisor
Pima County Assessor’s Office
Mapping Department

DATE: November 9, 2007


RE: Assessor’s Review and Comments Regarding Tentative Plat
S07-154 BRICHTA WASH TOWNHOMES T141303


* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

X Plat meets Assessor’s Office requirements.
_______ Plat does not meet Assessor’s Office requirements.


COMMENTS: PLEASE MAKE THE FOLLOWING ADJUSTMENTS BY FINAL PLAT STAGE:

THANK YOU FOR YOUR SUBMITTAL. IF YOU HAVE ANY QUESTIONS PLEASE CALL ROSANNA WERNER AT 740-4390

NOTE: THE ASSESSOR’S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.




ROSANNA WERNER
11/13/2007 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Denied DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S07-154 Brichta Wash Townhomes 11/09/07

() Tentative Plat
( ) Development Plan
() Landscape Plan
( ) Revised Plan/Plat
( ) Board of Adjustment
( ) Other

CROSS REFERENCE: N/A – not a rezoning

NEIGHBORHOOD PLAN: Santa Cruz Area Plan, General Plan

GATEWAY/SCENIC ROUTE: N/A

COMMENTS DUE BY: November 7, 2007

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

( ) No Annexation or Rezoning Conditions, Not an RCP - No Comment
( ) Proposal Complies with Annexation or Rezoning Conditions
( ) RCP Proposal Complies with Plan Policies
() See Additional Comments Attached
( ) No Additional Comments - Complies With Planning Comments Submitted on:
() Resubmittal Required:
() Tentative Plat
( ) Development Plan
() Landscape Plan
( ) Other

REVIEWER: J. Hershenhorn 791-4505 DATE: 11/6/07


S07-154
Brichta Wash Townhomes



Because this project is using the Residential Cluster Project (RCP) option, Land Use Code § 3.6.1 and specifically 3.6.1.4 apply. Per 3.6.1.4.A.1, the RCP must comply with the provisions of the General Plan and the Santa Cruz Area Plan. The plans as submitted generally comply with Santa Cruz Area Plan policies. However, to demonstrate compliance with the General Plan, the following need to be addressed:

To promote increased visual character, architectural elevations, including the architectural style, building elevation, and exterior colors, when viewed from the internal street (i.e., front elevations), shall not be repeated more often than every other lot. Please place a General Note on the plan as follows:

“Architectural front elevations (i.e., when viewed from the internal street), including the architectural style, building elevation, and exterior colors, shall not be repeated more often than every other lot.”

Any screen walls, including those along individual lot lines, that abut a common open space area, including detention/retention basins (i.e., lots 13, 14, and 26) shall be designed as view walls, to promote increased visibility of these areas, and enhanced site safety. The walls shall be designed so that no more than the lowest 30 inches above grade will be of solid masonry construction. At least 75% of wall portions above 30 inches shall be constructed of open materials, such as wrought iron.

Please provide a view wall detail on the Tentative Plat, and indicate where view walls will be located.

Please relocate the ramada with tables and barbecue away from the drainage inlet structure and splash pad, in the detention retention basin.
11/14/2007 ANDY VERA ENV SVCS REVIEW Denied 1. Turnarounds located in front of lots 44 &45 and next to lot 7 do not provide the required 60 ft to the face of curb then the surrounding 4 ft buffer. Per DS 3.01.0 figure 23.
Not adequate maneuverability for refuse/recycle service vehicle.

2. Adequate street frontage for curbside refuse and recycle collection.

Please correct above mentioned on resubmittal.
11/16/2007 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: November 15, 2007

TO: DSD_CDRC@ tucsonaz.gov

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov


SUBJECT: S07-154 Brichta Wash Townhomes: Tentative Plat Review(10-10-07)


Staff has no comments.