Review Details: FINAL PLAT REVIEW

Plan Number - S07-137
Review Name: FINAL PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/24/2007 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
09/24/2007 FRODRIG2 PIMA COUNTY WASTEWATER Denied September 14, 2007


To: Anthony Villarleal
Barry R. Barcus Architects, Inc.

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

___________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environment Quality

Subject: Chapman Automotive East
Final Plat - 1st Submittal
S07-137


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

The final plat can not be approved until the tentative plat has been approved (D07-039).

Public sewer line M-123 crosses this property. Check the title report for an easement over this line. If no public sewer easement exists over this public sewer on property such an easement will need to be granted by this final plat.

This office will require a revised set of blue lines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the final plat. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the second (2nd) submittal. A check for the review fee of this submittal in the amount of $100.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above-mentioned comments, please contact me.
10/01/2007 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 10/01/2007,


TO: Patricia Gehlen FROM: Laith Alshami, P.E.
CDRC Engineering

SUBJECT: Chapman Detail Building
S07-137, T14S, R14E, SECTION 22
REF. D07-0039

RECEIVED: Final Plat on September 24, 2007

The subject project has been reviewed. The project can not be approved at this time. Address the following comments before review can continue. Prepare a detailed response that explains the revisions that where made and references the exact location in the drainage report and the development plan where the revisions were made:

1. Provide the correct S(YR)- _______ number (D.S. 2-03.6.1.K.).
2. Revise the Certification of Survey text to match the text in D.S. 2-03.6.3.A.
3. Provide in General Note #4 the Rezoning Case number (D.S. 2-03.6.2.D.).
4. Add a general note stating that a floodplain use permit is required for developing this parcel as required by D.S. 2-03.6.2.E.
5. Add the word "for" between the words "access" and installation in the second paragraph of the Dedication (D.S. 2-03.6.3.B.2.b.).
6. General Note #1 states that the parcel is 10.09 acres. The plat, on Sheet 2 of 2, states that the area is 8.38 acres. Clarify the discrepancy.
7. Call out the basis of bearing on Sheet 2 of 2.
8. In order to expedite the plat review and approval, provide the boundary survey and closure calculations report in accordance with D.S. 2-03.6.5.C.3.
9. The easement information shown on the plat does not match the easement information included in the title report. Revise the plat easement information to in accordance with the title report information.
10. Show the erosion setback line as required by D.S. 2-03.6.4.E.
11. Show all applicable 100-year floodplain for all flows of 100 cfs or more in a surveyable and readily retraceable manner with frequent ties to intersecting lots line as required by D.S. 2-03.6.4.F.

Prepare a detailed response that explains the revisions that were made and references the exact location in the drainage report and on the Development Plan where the revisions were made.

RESUBMITTAL REQUIRED: Revised Final Plat
10/01/2007 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)
FROM: Gary Ault, Mapping Supervisor
Pima County Assessor’s Office
Mapping Department

DATE: October 24, 2007


RE: Assessor’s Review and Comments Regarding DEVELOPMENT PLAN

S07-137 CHAPMAN DETAIL BUILDING
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

X Plat meets Assessor’s Office requirements.
_______ Plat does not meet Assessor’s Office requirements.


COMMENTS:
THANK YOU FOR YOUR SUBMITTAL. IF YOU HAVE ANY QUESTIONS PLEASE CALL ROSANNA WERNER AT 740-4390



ROSANNA WERNER
10/02/2007 KAY MARKS PIMA COUNTY ADDRESSING Approv-Cond 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S07-137 CHAPMAN DETAIL BUILDING/FINAL PLAT
DATE: 10/02/07



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

NOTE: Approved with the following conditions:

1.) Delete "East" from 22nd Street on sheet 2 of mylar.

2.) Delete "South" from Columbus and spell out Boulevard on sheet 2 of mylar.




***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through Pima
County Addressing. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County's
Geographic Information System. Your support is greatly appreciated.***


es
10/11/2007 KAROL ARAGONEZ ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Karol Aragonez
Planner

PROJECT: S07-137
Chapman Detail Building
Final Plat

TRANSMITTAL DATE: October 9, 2007

DUE DATE: October 22, 2007

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. An applicant has one (1) year from the date of submittal to obtain approval of a final plat that complies with zoning and other development requirements in effect at the time of application. This final plat must be approved and recorded on or before September 24, 2008.

2. Please show the subject property approximately centered within a one (1) square mile area. Identify subdivisions within the square mile area referenced by book and page numbers.
DS 2-03.6.1.D.1 & 2

3. Please revise location of words "Book ____, Page ____ " by removing from the bottom right margin and placing in bottom margin.
DS 2-03.6.1.G

4. Case number S07-137 has been assigned to this final plat. Please place this number and the rezoning case number C9-96-10 in the right corner of all sheets of the final plat.
DS 2-03.6.1.K

5. Please fill in the rezoning case number C9-96-10 in general note 4.
DS 2-03.6.2.D

6. Please add the following general note "Any relocation, modification, etc., of existing utilities and/or public improvements necessitated by the proposed development will be at not expense to the public".
DS 2-03.6.2.I

7. Please replace surveyor's certificate with "Certification of Survey" paragraph with signature lines as required in DS 2-03.6.3.

8. Please add signature lines for dedication paragraph depending on the number of persons who have a fee title interest according to the title report current within thirty (30) days of recordation of the proposed plat.
DS 2-03.6.3.B.4


If you have any questions about this transmittal, please call Karol Aragonez, (520) 837-4960.

KAA S:\zoning review\karol\planning\cdrc\finalplat\S07-137fp.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised final plat additional requested documents.
10/11/2007 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved SUBJECT: CHAPMAN DETAIL BUILDING

S07-137



Tucson Electric Power Company (TEP) approves the Final Plat submitted
for the subject project.

Please forward any resubmittals of the final plat to this office.



Please contact me at (520) 917-8745 if you have any questions.


Liza Castillo, Right of Way Agent
Tucson Electric Power Co.
Unisource Energy Services
offc-(520) 917-8745
fax-(520) 545-1416
lcastillo@tep.com
10/23/2007 FRODRIG2 COT NON-DSD REAL ESTATE Approved >>> Andy Steuart 10/22/2007 1:53 PM >>>
S07-137 Chapman Detail Building: Final Plat Review - No comment.
10/23/2007 FRODRIG2 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Passed
10/24/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

October 24, 2007

Anthony Villarreal
Barry R. Barcus Architect, Inc.
5251 North 16th Street #800
Phoenix, Arizona 85016

Subject: S07-137 Chapman Detail Building Final Plat

Dear Anthony:

Your submittal of September 24, 2007 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

4 Copies Revised Final Plat (Wastewater, Engineering, Zoning, DSD)








Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: (602) 264-2542
fpresubmittal