Plan Number: S07-122
Parcel: Unknown

Address:
1631 N SWAN RD

Review Status: Completed

Review Details: FINAL PLAT REVIEW

Plan Number - S07-122
Review Name: FINAL PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2008 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
02/28/2008 FRODRIG2 PIMA COUNTY WASTEWATER Approved February 27, 2008

To: Marty Magelli
Baker & Associates

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

___________________________
From: Tom Porter, Sr. CEA (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environment Quality

Subject: Swan/Lee Offices, Lots 1-17 and Common Area "A"
Final Plat – 1st Submittal
S07-122


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the final plat as submitted.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you have any questions regarding the above-mentioned comments, please contact me.
03/05/2008 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Approved
03/17/2008 CDRC1 COT NON-DSD REAL ESTATE Denied S07-122 Swan/Lee Offices: Final Plat Review
-Sht. 1 of 2, dedication language need to be added in the DEDICATION block concerning the 20' along Swan Rd. for M,S&R purposes. Examples of statements for dedication are provided in C.O.T. Development Standard 2-03.6.3.B.
03/17/2008 STEVE SHIELDS ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Steve Shields
Lead Planner

PROJECT: Swan Lee Offices - Lots 1 - 17
S07-0122
Final Plat

TRANSMITTAL DATE: March 17, 2008

DUE DATE: March 17, 2008

COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a plat. If, at the end of that time, the plat has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this tentative plat is February 14, 2009.

2. D.S. 2-03.6.1.H Revise the title block to read "AND COMMON AREA "A" (PARKING/PAAL/LANDSCAPE/DRAINAGE).

3. D.S. 2-03.6.2.G Once the Board of Adjustment for the loading space size has been approved a general note stating "THIS PLAT IS SUBJECT TO BOARD OF ADJUSTMENT VARIANCE C10-___-___, UNLESS EXPIRED OR SUPERSEDED BY A SUBSEQUENT APPLICATION" will need to added to the plan.

4. D.S. 2-03.6.3.D Revise the Approval paragraph to read "I ROGER W. RANDOLPH".

5. D.S. 2-03.6.6 Add the following to the title of the covenants, conditions, restrictions and easements; "LOTS 1- 17 AND COMMON AREA "A" (PARKING/PAAL/LANDSCAPE/DRAINAGE)".

6. Additional comments may be forth coming depending on how each comment has been addressed.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C\planning\cdrc\finaplat\S07-122fp.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised final plat, CC&R's and additional requested documents.
03/17/2008 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor
115 N. Church Ave.
Tucson, Arizona 85701

BILL STAPLES
ASSESSOR




TO: CDRC Office
Subdivision Review
City of Tucson (FAX# 791-5559)

FROM: Gary Ault, Mapping Supervisor
Pima County Assessor's Office
Mapping Department

DATE: March 17, 2008


RE: Assessor's Review and Comments Regarding Final Plat
S07-122 Swan/Lee Offices T141403

* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *

X Plat meets Assessor's Office requirements.
_______ Plat does not meet Assessor's Office requirements.


COMMENTS: Thank you for your submittal.

NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.






Susan King
03/20/2008 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approv-Cond SUBJECT: Swan/Lee Offices

S07-122



Tucson Electric Power Company has reviewed and approved the final plat
submitted February 15, 2008.



There is an existing overhead pole line within the project, all remove
and relocation costs will be billable to the developer.



In order to apply for electric service, call the New Construction
Department at (520) 918-8300. Submit a final set of plans including
approved site, offsite and electrical load plans. Include a CD with the
AutoCAD version of the plans. If easements are required, they will be
secured by separate instrument. Your final plans should be sent to:



Tucson Electric Power
Company

Attn: Ms. Mary Boice

New Business Project
Manager

P. O. Box 711 (DB-101)

Tucson, AZ 85702

520-917-8732



Please call the area Designer Mike Kaiser at (520) 918-8244, should you
have any questions.



Liza Castillo, Right of Way Agent
Tucson Electric Power Co.
Unisource Energy Services
offc-(520) 917-8745
fax-(520) 545-1416
lcastillo@tep.com
03/24/2008 KAY MARKS PIMA COUNTY ADDRESSING Approved
03/27/2008 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 03/27/2008,

TO: Patricia Gehlen FROM: Laith Alshami, P.E.
CDRC Engineering

SUBJECT: Swan/Lee Offices
S07-122, T14S, R14E, SECTION 03

RECEIVED: Final Plat and CC & R's on February 15, 2008

The subject submittal has been reviewed and it can not be approved at this time. Address the following comments before review can continue. Prepare a detailed response that explains the revisions that were made and references the exact location in the Final Plat and Assurances where the revisions were made:

Final Plat:

1. Since this is a commercial subdivision, revise General Note #6 by removing the word "homeowner's" and replacing it with words that are more appropriate to a commercial subdivision (e.g. lot owners', property owners', etc).
2. Replace the name "Kathleen Detrick" with the words "the undersigned".
3. Add the following sentence to the Surveyor's Certificate: "I further certify that this plat was prepared under my direction (D.S. 2-03.6.3.A.).
4. Add the word "drainage" between the words "utilities" and "private sewers" in the fourth line of the second paragraph of the Dedication (D.S. 2-03.6.3.B.2.c.).
5. Provide a copy of a recent Title Report to assist in the review of existing easements.
6. Provide 1' "No Vehicular Access Easements" where applicable (D.S. 2-03.6.4.H.).
7. Show retention area in a surveyable readily retractable manner (D.S. 2-03.6.4.I.). Additionally, the retention area shall be called out as an underground system.
8. In order to expedite the plat review and approval, provide the boundary survey and closure calculations report in accordance with D.S. 2-03.6.5.C.3.

CC & R's:

1. The CC & R's are acceptable pertaining to Engineering and Floodplain Review. This Office recommends including the Drainage Facilities Maintenance Checklist as an exhibit to the CC & R's to facilitate the Property Owners' Association maintenance responsibility.

Assurances:

1. Revise the project name in the Agreement Recitals and in the Amendment to match the project name in the Final Plat Title Block including the common area description.
2. Provide the subdivision case number on the Agreement and the Amendment.
3. Provide the Trust Number on the first page of the "Trust Agreement".
4. Revise, in the "Termination Section" of the Amendment, the Paragraph number from "18" to "19". The City Clerk's Office identified that the number in the Template that was produced by the City is incorrect.
5. Include in the Assurances Package an up to date Title report.
6. The "Agreement to construct Subdivision Improvements" is missing Exhibit "A" to Exhibit "A" and Exhibit "B" to Exhibit "A".
7. The "Amendment to Trust" is missing Exhibit "A".
8. The first Page 6 of 6 has the title company name "Ticor Title Agency of Arizona" and an acknowledgement date of 2006. This information appears to be incorrect. Revise as necessary.

RESUBMITTAL REQUIRED: Revised Final and Assurances
04/01/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

April 1, 2008

Martin V. Magelli, P.E.
Baker & Associates Engineering, Inc.
3561 East Sunrise Drive #225
Tucson, Arizona 85718

Subject: S07-122 Swan/Lee Offices Final Plat

Dear Marty:

Your submittal of February 15, 2008 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

4 Copies Revised Final Plat (Zoning, Real Estate, Engineering, DSD)









Should you have any questions, please call me at 837-4919.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 318-1930
fpresubmittal