Plan Review Detail
Review Status: Completed
Review Details: RECORD OF SURVEY REVIEW
Plan Number - S07-118
Review Name: RECORD OF SURVEY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/30/2007 | FERNE RODRIGUEZ | START | PLANS SUBMITTED | Completed | |
| 08/06/2007 | CDRC1 | PIMA COUNTY | WASTEWATER | Denied | August 3rd, 2007 To: Peter Solanga P.E., Oracle Engineering Group Thru: Patricia Gehlen, CDRC Manager City of Tucson Development Services Department ____________________________________ From: Felipe Ip, Sr. Civil Eng. Assistant Development Review Division Pima County Development Services Department Subject: Record of Survey 3617 & 3619 E Monte Vista Drive, 1st submittal S07-118 The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use. 1. Provide a letter from the PCWMD's Development Services Section, written within the past 90 days, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at: http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf. The site plan and the record of survey for this project cannot be approved until a copy of this letter has been received by this office. 2. All Sheets: Add the project number, S07-118, to the title block of each sheet. This number should be shown larger or bolder than any cross-reference numbers (e.g. re-zonings, etc) 3. All Sheets: Label the properties surrounding the proposed project site (e.g. Parcel ID). Also, the buildings in Parcels 1 and 2 are currently labeled as EXISTING. Please label them as PROPOSED if they are yet to be constructed. 4. Sheet 1: Add a Permitting Note so it states: A PROJECT CONSTRUCTION PERMIT MUST BE SECURED FROM THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT BEFORE BEGINNING ANY WORK ON THIS PROJECT. 5. Sheet 1: Add a General Note so it states: THE ON-SITE SANITARY SEWERS WILL BE PRIVATE AND WILL BE CONSTRUCTED, OPERATED AND MAINTAINED ON A PRIVATE BASIS, AND IN ACCORDANCE WITH AN APPROVED OPERATION AND MAINTENANCE AGREEMENT, IF REQUIRED. THE LOCATION AND METHOD OF CONNECTION TO AN EXISTING PUBLIC SANITARY SEWER IS SUBJECT TO REVIEW AND APPROVAL BY THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT. 6. Sheet 1: Add a General Note so it states: MAINTENANCE AND OPERATION OF THE PRIVATE SANITARY SEWERS (HCS) TO ITS POINT OF CONNECTION TO THE PUBLIC SEWER IS THE RESPONSIBILITY OF THE PROPERTY OWNER. 7. Sheet 1: Add a General Note so it states: A JOINT USE AND MAINTENANCE AGREEMENT, REVIEWED AND APPROVED BY PCWMD, IS REQUIRED PRIOR TO CONNECTION OF ANY SHARED PRIVATE SEWERS. 8. Sheet 1: Add a General Note so it states: THERE WILL BE NO FURTHER DIVISION OF LOTS WITHOUT THE EXPRESSED APPROVAL OF THE CITY OF TUCSON. 9. Sheet 1: Show the public and private sewer lines using different line-types, so that they can readily be distinguished from each other. Revise the Legend block accordingly. 10. Sheet 1: Revise the plan to show and label all public sewer elements that are located within 100' or shown on this project. a. Label existing sewer lines with their Pima County construction plan numbers, pipe sizes, pipe materials, and flow arrows. b. Label all public manholes that are downstream from any existing and proposed House Connection Sewer (HCS) for this project with their IMS numbers, and rim and invert elevations. For example, label the existing public sewer on E. Monte Vista Dr. as EXIST. 8" VCP G-223 and the existing public manholes as EXIST MH9809-44 and EXIST MH 9809-43. Existing public sewer information may be found on the PCWMD Maps and Records (5th floor) or on the PCWMD and PCDOT MapGuide internet websites. 11. Sheet 1: Revise the plan to show all connections that will provide sewer services separately for Parcels 1 and 2. Show and label the proposed pipe connections to the public sewers (HCSs) for Parcels 1 and 2. HCS connections to existing public sewer main need to be 5 feet apart at the point of connection, and the 5-ft separation need to be maintained in the entire public Right-Of-Way up to the property line. Add a label or keynote to each proposed HCS that states "New HCS per PCWMD Engineering Directive ENG-2005-01". 12. This office will require a revised set of plans, and a response letter, addressing these comments. Additional comments may be made during the review of these documents. The next submittal of this project will be the 2nd submittal. A check for the review fee of this submittal in the amount of $50.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter. If you have any questions regarding the above mentioned comments, please do not hesitate to contact me at 520-740-6706. CC: Project file |
| 08/09/2007 | LIZA CASTILLO | UTILITIES | TUCSON ELECTRIC POWER | Denied | 4350 E. Irvington Road, Tucson, AZ 85714 Post Office Box 711, Tucson, AZ 85702 WR#182702 August 8, 2007 Oracle Engineering Group Attn: Peter Salonga 199 E Fort Lowell Road Tucson, Arizona 85705 Dear Mr. Salonga: SUBJECT: Monte Vista Eggman S07-118 Tucson Electric Power Company (TEP) has reviewed the plan submitted July 30, 2007. TEP is unable to approve the plan at this time. There are existing electrical facilities within the boundaries of this project. In order for TEP to approve the plan the facilities and easements must be depicted on the plans. *There is an easement and above ground pedestal on the SW corner of the property that is not shown on the site plan. Enclosed is a copy of a TEP facility map showing the approximate location of the existing facilities. All costs associated with the relocation of the facilities in conflict will be billable to the developer. Please resubmit two revised bluelines to City of Tucson for TEP’s review. You may contact the area Designer, Warren McElyea, at 918-8268 should you have any questions. Sincerely, Elizabeth Miranda Office Specialist lm Enclosure cc: DSD_CDRC@Tucsonaz.gov, City of Tucson W. McElyea, Tucson Electric Power |
| 08/10/2007 | TOM MARTINEZ | OTHER AGENCIES | AZ DEPT TRANSPORTATION | Approved | ADOT has NO COMMENT on the Record of Survey S07-118 Oracle Engineering Group MONTE VISTA EGGMAN -------------------------------------------------------- Confidentiality and Nondisclosure Notice: This email transmission and any attachments are intended for use by the person(s)/entity(ies) named above and may contain confidential/privileged information. Any unauthorized use, disclosure or distribution is strictly prohibited. If you are not the intended recipient, please contact the sender by email, and delete or destroy all copies plus attachments. |
| 08/20/2007 | PETER MCLAUGHLIN | LANDSCAPE | REVIEW | Approved | Per approved site/landscape plan. |
| 08/20/2007 | GLENN HICKS | COT NON-DSD | PARKS & RECREATION | Approved | DATE: August 20, 2007 TO: DSD_CDRC@ tucsonaz.gov FROM: Glenn Hicks Parks and Recreation 791-4873 ext. 215 Glenn.Hicks@tucsonaz.gov SUBJECT: S07-118 Monte Vista Eggman: Record of Survey Review(7/30/2007) No Comments |
| 08/22/2007 | KAY MARKS | PIMA COUNTY | ADDRESSING | Denied | 201 N. STONE AV., 1ST FL TUCSON, AZ 85701-1207 KAY MARKS ADDRESSING OFFICIAL PH: 740-6480 FAX #: 740-6370 TO: CITY PLANNING FROM: KAY MARKS, ADDRESSING OFFICIAL SUBJECT: S07-118 MONTE VISTA EGGMAN/ RECORD OF SURVEY REVIEW DATE: August 22, 2007 The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and the following matters must be resolved prior to our approval: 1.) Include scale 3"= 1 mile on Location Map. 2.) The Project Site is in the wrong location on the Location Map. It should be east of Richey Boulevard. 3.) Add Avenue to Palo Verde on Location Map. 4.) Add lots 1-2 on all Title Blocks. 5.) Spell out all street suffixes except on Location Map. 6.) Delete all addresses. 7.) Correct the legal description on all the Title Blocks. Is it the entire W1/2 of Lot 8? 8.) Please provide recorded deeds with legal descriptions in order to obtain address certificates. jg |
| 08/22/2007 | FRODRIG2 | OTHER AGENCIES | PIMA ASSN OF GOVTS | Approved | CASE: S07-118, MONTE VISTA EGGMAN, REC OF SURV REVIEW COMMENT: NO OBJECTIONS OR ADVERSE COMMENTS Vehicle Trip Generation: Daily: 19 PM Peak: 2 Please call if you have questions Tom Cooney, Travel Forecasting Manager Pima Association of Governments 177 N. Church Ave, #405 Tucson, AZ 85701 Tel: (520) 792-1093, Fax: (520) 620-6981 Web: www.PAGnet.org and www.RTAmobility.com |
| 08/23/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | TO: Patricia Gehlen; CDRC Coordinator DATE: August 30, 2007 SUBJECT: Engineering review of the Monte Vista Eggman Record of Survey. The activity number is S07-118. SUMMARY: The Record of Survey was received by Engineering on July 30th, 2007. Engineering has reviewed the received items and does not recommend approval of the Record of Survey. RESUBMITTAL REQUIRED: RECORD OF SURVEY SUBMITTAL REQUIRED: TITLE REPORT RECORD OF SURVEY COMMENTS 1. Each sheet will measure 24" x 36" and include a two (2) inch margin on the left side and one-half (½) inch margins on the remaining sides. Provide the required margins. DS 2-02.3.11.7.A. 2. All lettering and dimensions will be the equivalent of twelve (0.12) point or greater in size. The purpose of this requirement is to assure that the lettering is legible when reproduced or when photographically reduced (microfilmed) for record keeping purposes. DS 2-02.3.11.7.C. 3. Provide the scale for the location map. DS 2-03.11.7.D. 4. Place the words "Book ____ Page ____" in both the upper and lower right corners outside the margin line. The blanks will be completed by the Pima County Recorder's Office at the time of recordation. DS 2-03.11.7.E. 5. Provide a title block that conforms with the following DS 2-03.11.7.F. 6. Provide the north arrow in the upper right hand corner. DS 2-03.11.7.G. 7. Provide a legend which shows and describes all symbols used on the drawing will be placed on either the first sheet or the first sheet which contains all or part of the drawing. DS 2-03.11.7.I. 8. Provide all the applicable notes for this project found in DS 2-03.11.8. 9. Revise the Certificate of Survey paragraph per DS 2-03.11.9.A. to read as follows; CERTIFICATE OF SURVEY "I hereby certify that the boundary survey as shown on this Record of Survey was performed under my direction and that all existing or proposed survey monuments and markers shown are correctly described. I further certify that this Record of Survey was prepared under my direction." 10. Provide the DEDICATION language found DS 2-03.11.9.B. 11. Include a 5"X5" box for the County Recorders stamp. The title over the box must read, "RECORDING DATA". DS 2-03.11.9.C. 12. Remove from the record of survey all site plan information and verbiage, specifically the line weight for the vertical curb, the verbiage "Edge of pavement, water valve, concrete sidewalk, etc" and the house footprints. 13. At least one (1) corner of the property will be tied by course and distance to a section corner or a quarter section corner. Provide a description of that corner marker and an indication of how the bearings were determined. Corner tie recordation information is to be provided on the plan. DS 2-03.11.10.A. 14. Indicate whether the distance and bearing between all monuments used are measured or calculated. DS 2-03.11.10.B.4. 15. Correct the discrepancies with all the existing easement the Real Estate section outlines in their comments. DS 2-03.11.11.A. 16. All proposed easements (utility, sewer, drainage, access, etc.) are to be dimensioned and labeled as to their purposes and whether they will be public or private. Recordation information (docket and page) must be included on the plan prior to final approval. If applicable provide data. DS 2-03.11.12.A. 17. Show no-vehicular access easements where applicable. DS 2-03.11.12.B. 18. Depending on how each comment has been addressed additional comments could be forthcoming. |
| 08/23/2007 | CDRC1 | COT NON-DSD | REAL ESTATE | Denied | S07-118 Monte Vista Eggman: Record of Survey Review - No title report provided. Dkt./Pg. 12737/67 & 12487/2176 do not establish the 20' wide esmt. w/in the W. 1/2 of Lot 8. Request consideration be made for a "cross-access" easement for Parcels 1 & 2. Also, the offsite easement established by Dkt./Pg. 12737/67 & 12487/2176 is not annotated correctly (i.e. utility esmt. is shown as 24' in width rather than the 42' width established). |
| 08/23/2007 | JIM EGAN | COT NON-DSD | FIRE | Denied | A fire hydrant is required within 400 feet of all portions of the buildings on the two subdivided lots. See IFC Section 508.1 as amended. |
| 08/27/2007 | JOSE ORTIZ | COT NON-DSD | TRAFFIC | Approved | |
| 08/28/2007 | ANDY VERA | ENV SVCS | REVIEW | Approved | Adequate street frontage access for APC curbside refuse and recycle service to be placed off Monte Vista. |
| 08/30/2007 | HEATHER THRALL | ZONING | REVIEW | Denied | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Heather Thrall Senior Planner PROJECT: S07-118, Monte Vista Eggman 3617 & 19 E. Monte Vista Record of Survey, 1st Review TRANSMITTAL DATE: August 30, 2007 DUE DATE: August 27, 2007 COMMENTS: 1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a tentative plat. If, at the end of that time, the tentative plat has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this tentative plat is July 29, 2008. 2. This project was reviewed for compliance with the Land Use Code (LUC), Development Standards (DS), American National Standards Institute (ANSI), and International Building Code (IBC) 2003. The content of the project was reviewed for under DS 2-03.11.0 Record of Survey. Note, staff reviewed the survey document by Arrow Land Survey for the Record of Survey requirements. The accompanying site plan sheet was a helpful reference and should be left in with the resubmittal, thank you. 3. Per DS 2-03.11.7.B - provide a ½ inch margin on the top and bottom of the document. 4. Per DS 2-03.11.7.C - enlarge all lettering throughout the notes and on the drawing to a minimum of 12 point for microfilming. 5. Per DS 2-03.11.7.D - on location map: A) include the Township Range and Section of this project, and adjacent TRS info. B) Include the scale of 3" = 1 mile C) Please outline recorded subdivisions on map and list their names under the map 6. Per DS 2-03.11.7.E - please place the words "Book_____Page____" in both the upper and lower RIGHT corners, OUTSIDE the margin line. (for recordation) 7. Per DS 2-03.11.7.F - provide a title block in the lower right hand corner of the first page on the Record of Survey. A) The first line of the title block must read "RECORD OF SURVEY" B) Provide a title for the project C) List the number of proposed lots D) Move the brief legal description listed on the right side of the plan to the title block 8. Per DS 2-03.11.8.A.1.- list the names, addresses, and telephone numbers of the primary owners. 9. Per DS 2-03.11.8.A.2, move the listed 10. Per DS 2-03.11.8.B.1 - list the subdivision number for the project near the title block. 11. Per DS 2-03.11.8.B.2 - list as a general note "Existing zoning is R-2". 12. Per DS 2-03.11.8.B.3 - add the following note "The number of lots is 2." 13. Per DS 2-03.11.8.B.4 - add a note listing the gross area of the existing parcel as 12,000 square feet. 14. Per DS 2-03.11.8.B.5 - add the following note "There will be no further division of lots without the expressed approval of the City of Tucson." 15. Per DS 2-03.11.9.C - Add a 5" x 5" box for the County Recorder's stamp and add a title over the box that reads "RECORDING DATA" See engineering comments for survey certification, utilities relocation note, and dedication data requirements. 16. Per DS 2-03.11.11.A -access easement from Monte Vista across site to west appears to not be across full width of the pavement of that driveway. Is there an error as to where the easement is depicted? Any place a vehicle can travel across that adjacent property to get to the subject site should be included in the full width/length of that easement. 17. Per DS 2-03.11.11.A - it is not clear where 10' wide PUE across west side of proposed parcel 1 ENDS - does it continue across the west 10' of parcel 2 as well? 18. Per DS 2-03.11.11.B - label the curb of Monte Vista, provide recordation information for Monte Vista, dimension from centerline to curb. 19. Note further comments may be forthcoming, depending upon responses provided. I may be reached at Heather.Thrall@tucsonaz.gov or at 520-837-4951 for any questions. C:\planning\cdrc\S07-118 Monte Vista Eggman.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised record of survey. |
| 08/30/2007 | ROGER HOWLETT | COT NON-DSD | COMMUNITY PLANNING | Approved | DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS Regarding SUBJECT: Community Design Review Committee Application CASE NUMBER: CASE NAME: DATE SENT S07-118 Monte Vista Eggman 08/30/07 ( ) Tentative Plat ( ) Development Plan ( ) Landscape Plan ( ) Revised Plan/Plat ( ) Board of Adjustment ( ) Other CROSS REFERENCE: NEIGHBORHOOD PLAN: Grant-Alvernon GATEWAY/SCENIC ROUTE: COMMENTS DUE BY: 8/27/07 SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS: (XXXX) No Annexation or Rezoning Conditions, Not an RCP - No Comment ( ) Proposal Complies with Annexation or Rezoning Conditions ( ) RCP Proposal Complies with Plan Policies ( ) See Additional Comments Attached ( ) No Additional Comments - Complies With Planning Comments Submitted on: ( ) Resubmittal Required: ( ) Tentative Plat ( ) Development Plan ( ) Landscape Plan ( ) Other REVIEWER: drcorral 791-4505 DATE: 8/27/07 |
| 08/31/2007 | PATRICIA GEHLEN | ZONING-RECORDATION | REVIEW | Needs Review | COMMUNITY DESIGN REVIEW COMMITTEE DEVELOPMENT SERVICES August 31, 2007 Peter Salonga Oracle Engineering Group 199 East Fort Lowell Road Tucson, Arizona 85705 Subject: S07-118 Monte Vista Eggman Record of Survey Dear Pete: Your submittal of July 30, 2007, for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed: ALL BLUELINES MUST BE FOLDED 8 Copies Revised Record of Survey (Wastewater, TEP, Real Estate, Addressing, Fire, Engineering, Zoning, DSD), 3 Copies Title Report (Real Estate, Engineering, DSD) Should you have any questions, please call me at 837-4919. Sincerely, Patricia Y. Gehlen CDRC Manager All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/ Via fax: 292-6144 |
| 08/31/2007 | PGEHLEN1 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Passed | |
| 08/31/2007 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Denied | see comments under recordation folder. |