Plan Number: S07-101
Parcel: Unknown

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW

Plan Number - S07-101
Review Name: RESUBMITTAL - CDRC - TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2008 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
03/18/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Approved
03/19/2008 ELIZABETH EBERBACH ENGINEERING REVIEW Approved DATE: March 19, 2008
TO: Patricia Gehlen; CDRC Manager
SUBJECT: Riverfront Plaza Tentative Plat 3rd Resubmittal Engineering Review
LOCATION: T14S R13E Section 35, 119-42-009C
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: S07-101

SUMMARY: The revised Tentative Plat, revised Drainage Report, and response letter were received by Engineering. A meeting was held February 13, 2008 at request of consultant to discuss rezoning condition for bank protection. Engineering has reviewed the received items and recommends approval of the Tentative Plat. The Drainage Report was reviewed for Tentative Plat purposes only.

PROJECT SAC SUMMARY: The Riverfront Plaza Drainage report has addressed EHS requirements. There is no proposed encroachment of the W.A.S.H. Ordinance wash of the WBSCRDC. The existing WBSCRDC is within a FEMA Special Flood Hazard Zone A and consists of a constructed channel, approximately 7 feet deep and top width 200 feet, with an updated 100-year flowrate of 9,908 cfs, with earthen bottom and 3:1(H:V) side slopes covered with rip rap and filter fabric, and has an existing 2.4-ft deep concrete toedown running along the toe of the slope adjacent to the project. The Santa Cruz River along the east side of the project is bank protected. The area of the W.A.S.H. 50-foot Study Area includes both City and County properties. From aerials, there is some minimal vegetation within the Study Area. There is no W.A.S.H. Overlay Study area disturbance proposed and therefore no SAC scheduling required.

If you have any questions, please call me at 837-4934.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services
03/19/2008 STEVE SHIELDS ZONING REVIEW Approved CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office
FROM: Steve Shields
Lead Planner

PROJECT: Riverfront Plaza
S07-0101
Tentative Plat/Development Plan (4th Review)

TRANSMITTAL DATE: March 19, 2008

DUE DATE: April 03, 2008

COMMENTS: Please resubmit revised drawings along a separate response letter for zoning, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The Zoning Review Section verifies that the tentative plat/development plan meets the requirements of the Land Use Code. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the corrected tentative plat to verify that those changes do not affect any zoning requirements.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\cdrc\developmentplan\S07-0101tpdp-4th.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan and additional requested documents.
03/20/2008 FRODRIG2 PIMA COUNTY WASTEWATER Denied January 7, 2008


To: Robert Lane
Dowl Engineers

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

From: Tom Porter, Sr CEA
Development Review Division (Wsatewater)
Pima County Development Services Department

Subject: Riverfront Plaza, Lots 1-4 & Common Area A
Tentative Plat – 4th Submittal
S07-101


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWRD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

You are proposing a direct connection to the 8” public sewer with 6” BCS. This will require the construction of new public manholes at each point of connection. If 4” BCS line is used then a direct connection to the public sewer as shown would be allowed.

Sheet 1: Revise Sewer General Note #1 to read as follows: Add a General Note that states:

THE ON-SITE SANITARY SEWERS, EXCEPT PUBLIC SEWERS WITHIN PUBLIC SEWER EASEMENTS OR RIGHTS-OF-WAY, WILL BE PRIVATE AND WILL BE CONSTRUCTED, OPERATED AND MAINTAINED ON A PRIVATE BASIS, AND IN ACCORDANCE WITH AN APPROVED OPERATION AND MAINTENANCE PLAN, IF REQUIRED. THE LOCATION AND METHOD OF CONNECTION TO AN EXISTING PUBLIC SANITARY SEWER IS SUBJECT TO REVIEW AND APPROVAL BY THE PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT.

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the tentative or preliminary plat. The fee for the next submittal will be $78.00.


A check for the review fee of this submittal in the amount of $78.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and the response letter.

If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above comments, please do not hesitate to contact me.


Sincerely,




Tom Porter , Sr.CEA

CC: Project File
03/20/2008 FRODRIG2 PIMA COUNTY WASTEWATER Denied March 28, 2008


To: Robert Lane
Dowl Engineers

Thru: Patricia Gehlen, CDRC Manager
City of Tucson Development Services Department

From: Tom Porter, Sr CEA
Development Review Division (Wsatewater)
Pima County Development Services Department

Subject: Riverfront Plaza, Lots 1-4 & Common Area A
Tentative Plat - 4th Submittal(rev)
S07-101


The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Regional Wastewater Reclamation Department (PCRWRD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.

The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the development plan as submitted.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.


If you have any questions regarding the above comments, please do not hesitate to contact me.


Sincerely,




Tom Porter , Sr.CEA

CC: Project File
03/26/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approved COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

March 26, 2008

Robert W. Lane PE
DOWL Engineers
166 West Alameda Street
Tucson, Arizona 85701

Subject: S07-101 Riverfront Plaza Tentative Plat

Dear Robert:

Your submittal of March 6, 2008 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

2 Copies Revised Tentative Plat (Wastewater, DSD)










Should you have any questions, please call me at 837-4919.

Sincerely,

Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 624-0384
03/26/2008 ANDY VERA ENV SVCS REVIEW Approved
03/26/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approved COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES
***REVISED***


April 4, 2008

Robert W. Lane PE
DOWL Engineers
166 West Alameda Street
Tucson, Arizona 85701

Subject: S07-101 Riverfront Plaza Development Plan/Tentative Plat

Dear Robert:

The above referenced development plan has been APPROVED by the Community Design Review Committee. Please submit the following documents for sign-off.

1 Double Matte right-reading Océ or Photo Mylar of the COMPLETE SET of the Development Plan, Landscape Plan, and the Native Plant Preservation Plan (if part of the original submittal).
AND
1 Double Matte right-reading Océ or Photo Mylar of the Development Plan.
AND
1 CD that contains all of the drainage/hydrology and other reports submitted for the review and approval of this plan.

The extra Double Matte right-reading Océ or Photo Mylar that you submit will be delivered to Pima County for permanent recording. Additional blackline copies will be made from the complete mylar set and distributed to various review agencies for their files. These copies will be ordered from the City's contracted print company and billed to you unless you already have an account at another printing company. Please let us know which printing company you would prefer to use and list them on your attached transmittal form when submitting your mylars to the CDRC office for sign-off approval. Your printing company will deliver the mylar and two (2) blackline copies to your office. If you are out of town you will need to contact the printing company for pick up or mailing arrangement options.

TO ENSURE A MORE RAPID REVIEW OF THE MYLARS, PLEASE HAVE THE CITY OF TUCSON APPROVAL STAMP PLACED ON EACH SHEET OF THE SUBMITTAL SET, PREFERABLY IN THE LOWER RIGHT HAND CORNER NEAR THE TITLE BLOCK. THE STAMP IS LOCATED AT http://www.ci.tucson.az.us/dsd/CDRC Rezoning/CDRC/CDRC Stamp/cdrc stamp.html.

Should you have any questions, please call me at 837-4919.


Sincerely,



Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/

Via fax: 624-0384