Plan Review Detail
Review Status: Completed
Review Details: RECORD OF SURVEY REVIEW
Plan Number - S07-045
Review Name: RECORD OF SURVEY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/27/2007 | FRODRIG2 | START | PLANS SUBMITTED | Completed | |
| 03/29/2007 | JOSE ORTIZ | COT NON-DSD | TRAFFIC | Denied | March 29, 2007 ACTIVITY NUMBER: S07-045 PROJECT NAME: Record of Survey Morris Park PROJECT ADDRESS: 6017 S Morris Blvd PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer Resubmittal Required: Traffic Engineering does not recommend approval of the Record of Survey; therefore a revised Tentative Plat is required for resubmittal. The following items must be revised or added to the Record of Survey. 1. Include a response letter with the next submittal that states how all comments have been addressed. 2. Locate driveways on adjacent properties to verify compliance with driveway spacing requirements of Tucson City Code Chapter 25 and Access Management Guidelines. There should be 12' of separation between all proposed and existing driveways. Provide a separate exhibit to demonstrate compliance. If you have any questions, I can be reached at 791-4259 x76730 or Jose.Ortiz@tucsonaz.gov |
| 04/02/2007 | TOM MARTINEZ | OTHER AGENCIES | AZ DEPT TRANSPORTATION | Approved | NO COMMENT S07-045 MPK & ASSOCIATES, L.L.C. RECORD OF SURVEY MORRIS PARK -------------------------------------------------------- Confidentiality and Nondisclosure Notice: This email transmission and any attachments are intended for use by the person(s)/entity(ies) named above and may contain confidential/privileged information. Any unauthorized use, disclosure or distribution is strictly prohibited. If you are not the intended recipient, please contact the sender by email, and delete or destroy all copies plus attachments. |
| 04/04/2007 | LIZA CASTILLO | UTILITIES | TUCSON ELECTRIC POWER | Denied | 4350 E. Irvington Road, Tucson, AZ 85714 Post Office Box 711, Tucson, AZ 85702 WR# 179291 April 4, 2007 MPK’s Associates, LLC Attn: David Varela 7090 N Oralce Road #179-151 Tucson, Arizona 85704 Dear Ms. Varela SUBJECT: Record of Survey Morris Park S07-045 Tucson Electric Power Company (TEP) has reviewed the plan submitted March 27, 2007. TEP is unable to approve the plan at this time. There are existing electrical facilities within the boundaries of this project. In order for TEP to approve the plan, we will need a full set of approved site, electrical load, paving off-site improvements and irrigation plans. Did not show existing overhead facilities. Enclosed is a copy of a TEP facility map showing the approximate location of the existing facilities. All costs associated with the relocation of the facilities in conflict will be billable to the developer. Please resubmit two revised bluelines to Pima County Development Services Department for TEP’s review. You may contact the area Designer, Mike Kaiser at 918-8244 should you have any technical questions. Sincerely, Elizabeth Miranda Office Specialist lm Enclosure cc: P. Gehlen and F. Rodriguez, City of Tucson (by e-mail) M. Kaiser, Tucson Electric Power |
| 04/17/2007 | JOE LINVILLE | LANDSCAPE | REVIEW | Approved | |
| 04/18/2007 | ROGER HOWLETT | COT NON-DSD | COMMUNITY PLANNING | Approved | DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS Regarding SUBJECT: Community Design Review Committee Application CASE NUMBER: CASE NAME: DATE SENT S07-045 Record of Survey: Morris Park 04/18/07 () Tentative Plat () Development Plan () Landscape Plan () Revised Plan/Plat () Board of Adjustment (XXXX) Other – Record of Survey CROSS REFERENCE: NEIGHBORHOOD PLAN: Kino Area Plan GATEWAY/SCENIC ROUTE: COMMENTS DUE BY: 04/24/07 SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS: () No Annexation or Rezoning Conditions, Not an RCP - No Comment (XXXX) Proposal Complies with Annexation or Rezoning Conditions () RCP Proposal Complies with Plan Policies () See Additional Comments Attached () No Additional Comments - Complies With Planning Comments Submitted on: () Resubmittal Required: () Tentative Plat () Development Plan () Landscape Plan () Other REVIEWER: drcorral 791-4505 DATE: 04/16/07 |
| 04/19/2007 | JIM EGAN | COT NON-DSD | FIRE | Denied | The building area on Parcel 4 has portions greater than 150 feet from the fire lane and over 400 feet from a fire hydrant. Automatic fire sprinklers need to be provided. |
| 04/20/2007 | KAY MARKS | PIMA COUNTY | ADDRESSING | Approved | 201 N. STONE AV., 1ST FL TUCSON, AZ 85701-1207 KAY MARKS ADDRESSING OFFICIAL PH: 740-6480 FAX #: 740-6370 TO: CITY PLANNING FROM: KAY MARKS, ADDRESSING OFFICIAL SUBJECT: S07-045 RECORD OF SURVEY MORRIS PARK DATE: April 20, 2007 The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project. NOTE: PROVIDE COPIES OF RECORDED DEEDS FOR LOT SPLITS PRIOR TO ADDRESS ASSIGNMENT. jg |
| 04/24/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | TO: Patricia Gehlen; CDRC Coordinator DATE: April 24, 2007 SUBJECT: Engineering review of the Morris Park, Record of Survey. The activity number is S07-045. SUMMARY: The Record of Survey was received by Engineering on March 27th, 2007. Engineering has reviewed the received items and does not recommend approval of the Record of Survey. RESUBMITTAL REQUIRED: RECORD OF SURVEY RECORD OF SURVEY COMMENTS 1. All lettering will be equivalent of 12 point font or greater in size. The purpose of this requirement is when the document is reproduced the information is legible. The bearings and dimensions for parcel 2 and the 16' dimension are too small. Revise the record of survey to use a minimum of 12 point font. DS 2-03.11.7.C. 2. Provide a location map that meets the criteria found in DS 2-3.11.7.D. Specifically 12 point font should be used, the subject property should be centered within a one mile square area and identify any major conditions such as major streets. Revise as requested. 3. Provide the number of proposed lots in the title block. DS 2-03.11.7.F.3. 4. At least one (1) corner of the property will be tied by course and distance to a section corner or a quarter section corner. Provide a description of that corner marker and an indication of how the bearings were determined. Corner tie recordation information is to be provided on the plan. DS 2-03.11.10.A. 5. The 16' dimension for the easement does not scale to 16'. When scaled the dimension is actually 20'. Clarify in the response letter or revise the record of survey. DS 2-03.11.10.B. 6. The basis of bearing must be established from two found physically described monumented points and shown on the plan. Revise the record of survey to show the description of the found monument points. DS 2-03.11.10.C.1.c. 7. In addition to the above comment fully describe all other found monuments shown on the record of survey. DS 2-03.11.10.C.3. 8. Provide the recordation data for all the proposed easements shown on the record of survey. Indicate whether the easements are public or private. DS 2-03.11.12.A. 9. If applicable show no vehicular access easements where applicable. DS 2-03.11.12.B. 10. Show on the record of survey all proposed curb cuts. Be advised of the minimum 12' separation between curb cuts. DS 2-03.11.12.E. |
| 04/24/2007 | FRODRIG2 | COT NON-DSD | REAL ESTATE | Denied | S07-045 Record of Survey Morris Park: Record of Survey Review - No title report provided. It is understood the proposed utility easements w/in Parcels 1 & 3 are intended for the public use. However, a title company should be consulted and provide guidance concerning the conveyance of the utility easement. |
| 04/24/2007 | KAROL ARAGONEZ | ZONING | REVIEW | Denied | CDRC TRANSMITTAL TO: Development Services Department Plans Coordination Office FROM: Karol Aragonez Planner PROJECT: S07-045 Morris Park Record of Survey TRANSMITTAL DATE: April 19, 2007 DUE DATE: April 24, 2007 COMMENTS: Please resubmit revised drawings along a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. All lettering bearings and length, and lettering within the project location must be equivalent to twelve (0.12) point or greater in size. Within the location map enlarge Morris Avenue, Bilby Road, Park Avenue, Valencia Road, Drexel Road, Campbell Avenue, and Nogales Highway. 2. Case number S07-045 has been assigned to this record of survey. Please place this number in the right corner of all sheets of the record of survey and any other associated sheets. 3. Within the title block please provide the proposed number of lots. 4. Please correct lettering (bearings and distance) on the south proposed property line of parcel 2 so it will be readable on sheet 1 of 1 of the survey. 5. Please draw all existing easements on the plan along with recordation information, location, width, and purpose. If an easement is no longer in use and scheduled to be vacated or has been abandoned, so indicate. If none exist provide response to reviewer's comments. 6. Please provide on the site plan the size of the existing water main, location and size of electric and telephone lines. 7. One (1) foot N.A.E. is to be provided along property lines of Parcel 3 to prevent access from driveway to Parcel 1 and 2. 8. Please show locations of all proposed driveways. 9. Per the 2005 aerials it appears that an accessory building may be located on proposed Parcel 4. All accessory structures must be removed from future parcels. If you have any questions about this transmittal, please call Karol Aragonez, (520) 791-5550, ext. 74960. KAA S:\zoning review\karol\planning\cdrc\tentativeplat\S07-045rs.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Record of Survey and additional requested documents. |
| 04/25/2007 | PGEHLEN1 | OTHER AGENCIES | PIMA ASSN OF GOVTS | Passed | |
| 04/25/2007 | ANDY VERA | ENV SVCS | REVIEW | Approved | * Street frontage access off Morris Ave. is sufficient for APC curbside refuse and recycle service for all four lots. |
| 04/25/2007 | GLENN HICKS | COT NON-DSD | PARKS & RECREATION | Approved | DATE: April 24, 2007 TO: Ferne Rodriguez, Development Services FROM: Glenn Hicks Parks and Recreation 791-4873 ext. 215 Glenn.Hicks@tucsonaz.gov CC: Patricia Gehlen SUBJECT: S07-045 Record of Survey Morris Park: Record of Survey Review Parks and Recreation has no comments |
| 04/25/2007 | PGEHLEN1 | TUCSON WATER NEW AREA DEVELOPMENT | REVIEW | Passed | |
| 05/04/2007 | FRODRIG2 | PIMA COUNTY | WASTEWATER | Approved | May 4, 2007 To: John B. Trimble, P.E. Thru: Patricia Gehlen, CDRC Manager City of Tucson Development Services Department ____________________________________ From: Felipe Ip, Sr. Civil Eng. Assistant (520-740-6706), representing the Pima County Departments of Wastewater Management and Environmental Quality Subject: Land Survey Exception, Morris Park Lots 21-22, Block 4 of Southland Park Record of Survey & Site Plan, 1st Submittal, S07-045 The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use: The Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the as submitted. Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality. Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution. CC: Project file |
| 05/07/2007 | PATRICIA GEHLEN | ZONING-DECISION LETTER | REVIEW | Denied | COMMUNITY DESIGN REVIEW COMMITTEE DEVELOPMENT SERVICES May 7, 2007 David W. Varela MPK & Associates, LLC 7090 North Oracle Road, #178-151 Tucson, Arizona 85704 Subject: S07-045 Morris Park Record of Survey Dear David: Your submittal of March 27, 2007, for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed: ALL BLUELINES MUST BE FOLDED 7 Copies Revised Record of Survey (Traffic, TEP, Fire, Real Estate, Engineering, Zoning, DSD), 2 Copies Title Report (Real Estate, DSD) Should you have any questions, please call me at 791-5608, ext 1179. Sincerely, Patricia Y. Gehlen CDRC Manager All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/ Via fax: 844-1105 |
| 05/07/2007 | PATRICIA GEHLEN | ZONING-RECORDATION | REVIEW | Needs Review |