Plan Number: S07-034
Parcel: Unknown

Address:
855 E DREXEL RD

Review Status: Completed

Review Details: RESUBMITTAL - CDRC - FINAL PLAT REVIEW

Plan Number - S07-034
Review Name: RESUBMITTAL - CDRC - FINAL PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/26/2008 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
03/11/2008 FRODRIG2 PIMA COUNTY WASTEWATER Approv-Cond March 5, 2008

To: Joaquin Rincon
Civil Works Engineering

Thru: Patricia Gehlen, CDRC Project Manager
City of Tucson Development Services Department

____________________________________
From: Tom Porter, Sr. Civil Eng. Assistant (520-740-6706), representing the Pima County
Departments of Wastewater Management and Environmental Quality


Subject: Colonia Mariposa, Lots 1-16 & Common Areas A, B-1 - B-16 & C-1 - C-2
Final Plat – 2nd Submittal
S07-034

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


In the Dedication Block, third paragraph, first line after the word PUBLIC add the words ,PIMA COUNTY. Pima County was placed in the wrong part of the sentence.

Subject to the above, the Pima County Department of Environmental Quality and Wastewater Management Department hereby approve the above referenced submittal of the final plat. The required revision(s) may be shown on the Mylars.

Please note the following: Approval of the above referenced submittal does not authorize the construction of public or private sewer collection lines, or water distribution lines. Prior to the construction of such features, a Construction Authorization (Approval To Construct) may need to be obtained from the Pima County Environmental Quality.

Also, air quality activity permits must be secured by the developer or prime contractor from the Pima County Department of Environmental Quality before constructing, operating or engaging in an activity which may cause or contribute to air pollution.

If the number of sheets changes, please adjust the review fee accordingly.

If you have any questions regarding the above mentioned comments, please do not hesitate to contact me.
CC: Project file
03/11/2008 GLYNDA ROTHWELL UTILITIES TUCSON ELECTRIC POWER Denied SUBJECT: COLONIA MARIPOSA

Lots 1-16

S07-034



Tucson Electric Power Company (TEP) has reviewed the final plat
submitted February 26, 2008. TEP is unable to approve the plat at this
time.



See the attached PDF files for changes to the dedication and also a copy
of our preliminary design. TEP requires 10' x 10' easements for the
transformer and pedestal locations.



If you have any questions, let me know.


Liza Castillo, Right of Way Agent
Tucson Electric Power Co.
Unisource Energy Services
offc-(520) 917-8745
fax-(520) 545-1416
lcastillo@tep.com
03/17/2008 TERRY STEVENS ZONING REVIEW Approv-Cond CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Terry Stevens
Lead Planner

PROJECT: S07-034
Colonia Mariposa Lots 1-16
Final Plat

TRANSMITTAL: 03/17/2008

DUE DATE: 3/25/08

COMMENTS:


1. The Zoning Review Section approves the final plat for this subdivision, subject to the following changes on the executed final plat. However, should there be any changes requested by other CDRC members, the Zoning Review Section approval is void, and we request copies of the revised final plat to verify that those changes do not affect any zoning requirements.

2. Please add to the first sheet of the CC&Rs the number of lots and common areas as listed in the title block of the final plat.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961


C\planning\cdrc\finaplat\S07-034fpca
03/19/2008 KAY MARKS PIMA COUNTY ADDRESSING Approved 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S07-034 COLONIA MARIPOSA/REVISED FINAL PLAT
DATE: 3/18/08



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.




***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through Pima
County Addressing. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County’s
Geographic Information System. Your support is greatly appreciated.***

ES
03/21/2008 ANDY STEUART COT NON-DSD REAL ESTATE Approv-Cond -Per 3/20/08 confirmation with DOT/Plans & Permits, change the 8' wide drainage easement from Pulic to a Private Drainage Easement.
03/26/2008 ELIZABETH EBERBACH ENGINEERING REVIEW Denied TO: Patricia Gehlen; CDRC Coordinator
SUBJECT: Colonia Mariposa (S04-166) 2nd Submittal Final Plat and assurances Engineering Review
LOCATION: T15S R14E Section 6
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: S07-034

SUMMARY: The revised Final Plat package including a copy of the revised Final Plat, copy of the revised CC&R's, copy of the title report schedule B with updated sewer easement information, assurance package, location map, and response letter were received by Engineering for review. Engineering does not recommend approval of the Final Plat until are the Final Plat and assurances comments are addressed.

FINAL PLAT COMMENTS:
1) City of Tucson Development Standards (DS) Section No. 2-03.7.1.G: The final plat cannot be scheduled for Mayor and Council consideration until the financial assurances are approved. Address the following for the assurance package:
a) Revise the following for the AGREEMENT TO CONSTRUCT:
i) In the first paragraph, add a comma after Trust No. 766 and before the city of Tucson.
ii) Add a space before C2 in paragraph A of the Recitals.
iii) Attach the exhibits A and B as referenced on page 1 to the Agreement and if additional exhibits are needed for the other portions of the assurance package, provide and attach.
iv) Revise assurable items list to clarify that item 8: "… all off-site and onsite improvements as shown on …"
b) Assure the title block common areas listed in the assurance paperwork match the plat. Please be aware that the City of Tucson's clerk or legal offices may reject the assurance paperwork if the verbiage does not match exactly the verbiage on the Final Plat's Title Block.
c) Revise the subdivision assurance package and in the resubmittal, provide:
i) original copy of the AGREEMENT TO CONSTRUCT SUBDIVISION IMPROVEMENTS / THIRD PARTY TRUST with the assurable items list;
ii) original copy of the AMENDMENT TO TRUST / THIRD PARTY TRUST;
iii) assure that all exhibits are attached, and the case number "S07-034" is at the top of the first page of the AGREEMENT TO CONSTRUCT and AMENDMENT TO TRUST;
iv) copy of the original Trust Agreement;
v) copy of a sample Warranty Deed;
vi) copy of the current Title Report.
2) DS Sec.2-03.6.1.L: Address the following comments:
a) Clarify discrepancy of the common area labeling and the title block description. Common area labels on the planview do not match the title block description.
b) Revise lot 9 frontage length to provide a minimum frontage that allows for driveway or any solid waste pick-up area requirements; typically 20 to 30 ft minimum frontage is needed to provide sufficient access. Also, clarify / revise star symbol location for lot 8 to show that access should not be too close to lot 9.
c) Provide "100-year" floodplain limits for jurisdictional flows of 100 cfs or more, if applicable. State in response letter whether any flows are impacting site to the south of the project and reflect in engineering certification. Call for clarification.
d) Clarify leader line near lot 9 for 457.32 distance as well as the crows feet for this distance as opposed to 637.48.
e) Provide descriptions for each common area A, B, C, and D in title block or general notes.
3) DS Sec.2-03.7.1.B: It is unclear whether there is any jurisdictional floodplain lines within the plat boundary. Any 100-yr floodplains with flows of 100 cfs or more shall be shown on the plat and the certification indicates that there are some. Regarding the engineering certification on sheet 1, any floodplain or erosion hazard setback lines that fall within the project boundary shall be shown on the plat. Verify whether engineering certification is needed if floodplain or EHS lines do not fall within project boundary.
4) DS Sec.2-03.7.1.E: Provide a revised copy of the Declaration of Covenants, Conditions and Restrictions (CC&Rs) addressing the following comments:
a) DS Sec.2-03.6.6: Assure that the CC&R's are revised to include a maintenance checklist as provided in the Drainage Report from the approved Tentative Plat, that outlines the maintenance requirements for the basin and drainageway and any other drainage areas.
b) At Final Plat approval, a signed original copy of the CC&R's will be required to be submitted to CDRC Office.
c) In the CC&R's add maintenance verbiage regarding: revegetation or other permanent erosion control in all easements shall be the responsibility of the Homeowners Association.
5) Show any TEP pedestal or other proposed utility easements on the plat.
6) DS Sec.2-03.6.3.C Add contact person to the Beneficiary paragraph.
7) DS Sec.2-03.6.3.A: For all seals, including any future project submittals, provide the expiration date of the registration below the seal per current AzBTR requirements.
8) DS Sec.2-03.6.5.C.5: Address the following boundary data and survey items:
a) Clarify bearings and distances for tie to section corner from a corner of the project. Tie must be from the section corner through described monuments with bearings and distances to one of the project boundary corners. Tie to a street monument tie is not sufficient.
b) DS Sec.2-03.6.5.C.4.b: Clarify lot 1 southwest survey monument and add to legend.
c) DS Sec.2-03.6.4.F: For any surveyable 100-year floodprone limits if applicable, show frequent ties to intersecting lot lines. It was stated in response letter that ties to intersection lot lines were provided although no floodplain lines are shown. Show any 100-yr floodplain line that enters the plat boundary from any jurisdictional flows from Drexel Road.
d) DS Sec.2-03.6.5.C.3: Provide closure sheet for project boundary with error calculation.
9) DS Sec.2-03.6.4.I: If 100-year ponding limits and basin common area delineation are the same ponding limit line may be deleted from the final plat. All lines must be surveyable. Show minimum geotechnical setback within basin common area.
10) DS Sec.2-03.6.3.D: Address the following for the Recording Data paragraph:
a) Fill in the requestor's name for the Recording Data section on sheet 1. "… Filed for record at the request of (fill in name)____________________________
b) Also add a signature line for the Deputy County Recorder per this section of the standards.
11) DS Sec.2-03.6.3: Consider revising the Approvals section due to more recent directive: The City Clerk, Kathleen S. Detrick, is retiring. Effective February 2, 2008, all correspondence for the City Clerk should be addressed to Roger W. Randolph per the City Clerk's Office. Mr. Randolph will serve as the City Clerk until such time as a City Clerk is appointed by Mayor and Council. Revise Approvals section verbiage on sheet 1 to state: "The undersigned, Roger W. Randolph, Clerk of the City of Tucson, Arizona, hereby certifies that this plat was approved by the Mayor and Council of the City of Tucson, Arizona, on this __ day of ________, 200__.

Submit complete assurance package, copy of the latest title report, revised Final Plat, copy of the revised CC&R's, and response letter. The next submittal should address all the above items. If you have questions or would like to set up a meeting, call me at 837-4934.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services
03/27/2008 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

March 27, 2008

Charles Corrales
Steve Corrales Engineering Corporation
1008 West Saint Mary's Road
Tucson, Arizona 85745

Subject: S07-034 Colonia Mariposa Final Plat

Dear Steve:

Your submittal of February 26, 2008 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

4 Copies Revised Final Plat (TEP, Real Estate Engineering, DSD)

2 Copies Title Report (Engineering, DSD)

2 Copies CC&R's (Engineering, DSD file copy)


Should you have any questions, please call me at 837-4919.


Sincerely,



Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/


Via fax: 622-2554
fpresubmittal