Plan Number: S07-033
Parcel: Unknown

Review Status: Completed

Review Details: REVISION - TENT PLAT & CORE RESUB

Plan Number - S07-033
Review Name: REVISION - TENT PLAT & CORE RESUB
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2016 KROBLES1 START PLANS SUBMITTED Completed
10/07/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved Please note for the record that the applicant acknowledged routing 57 cfs to two 24" diameter culverts instead of the two 36" diameter culverts further to the north where 50 cfs is being conveyed. Comment response referenced headwater calculations that were supposed to be found in appendix D. Only tail water data was found in this appendix. Internal staff calculations were run independantly and it was found that a little over 10 cfs is conveyed over the road at the location with the two 24" diameter culverts in a 100 year storm.
10/10/2016 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/12/2016 KROBLES1 OUT TO CUSTOMER Completed