Plan Number: S06-270
Parcel: Unknown

Address:
6702 S WILMOT RD

Review Status: Completed

Review Details: ASSURANCES

Plan Number - S06-270
Review Name: ASSURANCES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2008 FERNE RODRIGUEZ START ASSURANCES RECEIVED Completed
05/09/2008 ELIZABETH EBERBACH ENGINEERING REVIEW Approv-Cond TO: Patricia Gehlen; CDRC Coordinator
SUBJECT: Littletown and Wilmot Industrial Park Final Plat Engineering 2nd resubmittal Review
REVIEWER: Elizabeth Eberbach
LOCATION: T15S R14E Section 13, Ward 5, East Impact Fee area, FIRM panel 2265K
ACTIVITY NUMBER: S06-270

SUMMARY: The revised Final Plat sheets, a copy of the title report, CC&R's, geotechnical report, assurances, closure calc sheet, and response letter were received by Engineering for review. Engineering recommends conditional approval of the assurances and Final Plat. Contact CDRC as to whether the items below may be addressed at mylar stage.

FINAL PLAT AND ASSURANCES CONDITIONS OF APPROVAL:
1) City of Tucson Development Standards (DS) Section No.2-03.7.1.G: The final plat cannot be scheduled for Mayor and Council consideration until the financial assurances are reviewed and approved. Address the following for the assurance package:
a) For the third party trust, address the following:
i) Address the following comments for the AGREEMENT TO CONSTRUCT SUBDIVISION IMPROVEMENTS / THIRD PARTY TRUST:
(1) Correct assurable item 3 to reflect "public water system …", not sewer, acceptable to Tucson Water.
(2) Revise the assurable items list to include an item for "all off-site and on-site improvements as shown on the Tentative Plat, Final Plat, and Improvement Plans".
(3) Clarify "%" sign in item 24 on page 4, before subdivider's address.
ii) Fill in the case number "S06-270" bottom of pages of the AGREEMENT TO CONSTRUCT and AMENDMENT TO TRUST;
iii) Attach and provide page number for the exhibit A to the AMENDMENT TO TRUST;
iv) Add case number "S06-270" to Exhibit "A" of the AGREEMENT TO CONSTRUCT and AMENDMENT TO TRUST;
v) Clarify whether the exhibits for the Agreement to Construct need page numbers.
vi) After revising the assurance documents, submit a compiled revised set of original assurances to CDRC, including: original copy of the, original copy of the , copy of the original Trust Agreement, copy of the sample Warranty Deed, copy of the current Title Report, and a location map.
2) DS Sec.2-03.6.3.C: Under the BENEFICIARY block, correct verbiage to clarify by stating that the "Beneficiaries of (Title Company Name and Trust Number) are (Names and Addresses)."
3) DS Sec.2-03.7.1.E: Assure the remaining comments are addressed for the CC&R's:
a) Provide page numbering for every and all pages of a revised CC&R's including any table of contents and appendix for CDRC processing.
b) At Final Plat approval, an original copy of the signed revised CC&R's will be required to be submitted to CDRC Office.
4) DS Sec.2-03.6.5.B: Check discrepancy for bearing labeled north of lot 16 on sheet 1 and sheet 2.
5) DS Sec.2-03.6.4.A: Add a note to Final Plat cover sheet stating that Common Area "C" along east boundary (or identify correct location) contains an underground fiber optic cable; all work within this easement must be coordinated with the proper utilities prior to any site construction.
6) For legibility, correct the text overlap for details on sheet 2.

Submit revised Final Plat, title report, revised CC&R's, revised assurances, and response letter. Please call me for clarifications at 837-4934.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services