Review Status: Completed

Review Details: TENTATIVE PLAT REVIEW

Plan Number - S06-262
Review Name: TENTATIVE PLAT REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2007 JOE LINVILLE LANDSCAPE REVIEW Denied 1) The NPPO application for exception has not been approved.
Provide 2:1 mitigation for the viable tree removed and sign the application.

2) Revise the landscape plan to include slope ratios for retention and detention basins. Basin slopes in most instances are required to have slopes no steeper than 4:1 where depths exceed three feet, 3:1 for unprotected slopes and 2: 1 for protected slopes for depths less than three feet.
DS 10-01.4

Per DS 10-01.IV (p.79), retaining walls should be used for no more than 35% of the basin perimeter. Revise as necessary to comply.

3) Revise the plans per LUC 3.7.2.7 to meet dust control requirements in construction areas adjacent to the site in the public right-of-way.

Resubmittal of plans is required.
01/05/2007 TOM MARTINEZ OTHER AGENCIES AZ DEPT TRANSPORTATION Approved NO COMMENT
S06-262
GREGOE ENGINEERING, INC.
CASAS DE LOS ANGELES

--------------------------------------------------------


Confidentiality and Nondisclosure Notice: This email transmission and any attachments are intended for use by the person(s)/entity(ies) named above and may contain confidential/privileged information. Any unauthorized use, disclosure or distribution is strictly prohibited. If you are not the intended recipient, please contact the sender by email, and delete or destroy all copies plus attachments.
01/08/2007 GLENN HICKS COT NON-DSD PARKS & RECREATION Approved DATE: January 8, 2007

TO: Ferne Rodriguez, Development Services

FROM: Glenn Hicks
Parks and Recreation
791-4873 ext. 215
Glenn.Hicks@tucsonaz.gov

CC:


SUBJECT: S06-262 Casas De Los Angeles: Tentative Plat Review


Staff has no comments.
01/18/2007 LIZA CASTILLO UTILITIES TUCSON ELECTRIC POWER Approved 4350 E. Irvington Road, Tucson, AZ 85714
Post Office Box 711, Tucson, AZ 85702


WR#175031 January 16, 2007

Gregor Engineering, Inc.
Attn: Steve Gregor
5232 E. Pima St. Ste. A
Tucson, AZ 85712

Dear Mr. Gregor:

SUBJECT: Casas De Los Angeles
Lots 1 thru 8 and Common Area A
S06-262

Tucson Electric Power Company (TEP) has no objection to the preliminary plat submitted for review December 22, 2007.

The preliminary point where TEP can possibly feed this project is from feed (OMV-2) which is within a 6’ PUE by the plat book-35, Page 9. Feed (LHR2-44) on easement found appears to be located within Teton Road. There are no apparent electrical facilities. Enclosed is a copy of TEP’s facility map showing the approximate location and unit number of the existing facilities.

TEP will provide a preliminary electrical design on the Approved Tentative Plat within fifteen (15) working days upon receipt of the plat. Additional plans necessary for preparation of the design are: building plans including water, electrical, landscape, sidewalk and paving plans. Also, submit the AutoCAD version of the plat on a CD or email to hnoriega@tep.com. Should you have any questions, please contact the Designer for this project Ron Grant at (520) 917-8712


Sincerely,


Henrietta Noriega
Office Specialist
Design/Build
hn
Enclosures
cc:P. Gehlen – City of Tucson (e-mail)
S. Dillard, Developer Owner – Letter only
E.Torres/R. Grant - Tucson Electric Power Company
01/18/2007 ED ABRIGO PIMA COUNTY ASSESSOR Approved Office of the Pima County Assessor


115 N. Church Ave.


Tucson, Arizona 85701



BILL STAPLES

ASSESSOR










TO: CDRC Office

Subdivision Review

City of Tucson (FAX# 791-5559)

FROM: Gary Ault, Mapping Supervisor

Pima County Assessor's Office

Mapping Department



DATE: January 17, 2007





RE: Assessor's Review and Comments Regarding Tentative Plat

S06-262 CASAS DE LOS ANGELES T151314





* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *



x Plat meets Assessor's Office requirements.

_______ Plat does not meet Assessor's Office requirements.





COMMENTS: PLEASE MAKE THE FOLLOWING ADJUSTMENTS BY FINAL PLAT STAGE:

1. ADD BEARINGS AND DIMS FOR ALL LOT LINES.

2. ADD COMPLETE CURVE DATAWHERE APPLICABLE.

3. ADD RECORDING INFO. FOR EXISTING STREETS.



THANK YOU FOR YOUR SUBMITTAL. IF YOU HAVE ANY QUESTIONS PLEASE CALL
ROSANNA WERNER AT 740-4390



NOTE: THE ASSESSOR'S CURRENT INVOLVEMENT IN PROCESSING ITS MANUAL MAPS
TO DIGITAL FORMAT IS EXPEDITED GREATLY BY EXCHANGE OF DIGITAL DATA. IN
THE COURSE OF RECORDING THIS SUBDIVISION YOUR ASSISTANCE IN PROVIDING
THIS OFFICE WITH AN AUTOCAD COPY WOULD BE GREATLY APPRECIATED. THANK
YOU FOR ANY DIGITAL DATA PREVIOUSLY SUBMITTED.













ROSANNA WERNER
01/18/2007 KAY MARKS PIMA COUNTY ADDRESSING Approv-Cond 201 N. STONE AV., 1ST FL
TUCSON, AZ 85701-1207

KAY MARKS
ADDRESSING OFFICIAL
PH: 740-6480
FAX #: 740-6370


TO: CITY PLANNING
FROM: KAY MARKS, ADDRESSING OFFICIAL
SUBJECT: S06-262 CASA DE LOS ANGELES/TENTATIVE PLAT
DATE: 1/17/07



The above referenced project has been reviewed by this Division for all matters pertaining to street naming/addressing, and we hereby approve this project.

NOTE: ON FINAL PLAT:

1.) Delete all street directions on Location Map.




***The Pima County Addressing Section can use digital CAD drawing files when
submitted with your final plat Mylar. These CAD files can be submitted through Pima
County Addressing. The digital CAD drawing files expedite the addressing
and permitting processes when we are able to insert this digital data into the County’s
Geographic Information System. Your support is greatly appreciated.***
01/19/2007 FRODRIG2 PIMA COUNTY WASTEWATER Denied January 18, 2007

To: Steve Gregor, Gregor Engineering

Thru: Patricia Gehlen, CDRC Project Manager
City of Tucson Development Services Department

____________________________________
From: Michael J.Harrington (520-740-6579), representing the Pima County
Departments of Wastewater Management and Environmental Quality

Subject: Casas De Los Angeles
Lots 1 thru 8 & Common Area A
Tentative Plat - 1st Submittal
S06-262

The proposed sewer collection lines for the above-referenced project have been reviewed on behalf of the Pima County Department of Environmental Quality (PDEQ) and the Pima County Wastewater Management Department (PCWMD). This review letter may contain comments pertaining to the concerns of either Department. The following comments are offered for your use.


This project will be tributary to the Roger Road Wastewater Treatment Facility via the Santa Cruz Interceptor. Obtain a letter from the PCWMD's Development Services Section, written within the past 90 days, stating that treatment and conveyance system capacity for the project is available in the downstream public sewerage system and provide a copy of that letter to this office. The required form to request such a letter may be found at:

http://www.pima.gov/wwm/forms/docs/CapResponseRequest.pdf.

The tentative plat for this project cannot be approved until a copy of this letter has been received by this office.

All Sheets: Add the subdivision case number, S06-262, to the title block of each sheet. This number should be shown larger or bolder than any cross reference numbers. No wastewater review fees will be charged for sheets where this is the only required revision.

Sheet 1: You are proposing that Lots 3 and 4 connect to the public sewer system, G-81-21, at the existing manhole, #2739-02. PCWMD will not allow two additional HCS connections into the manhole that already has three existing HCS connections. Also, per PCWMD Design Standards, proposed House Connection Sewers shall be located such that they do not violate the frontage of an adjacent lot(s) while traversing to the point of connection to the public main. And, the overall length of the H.C.S. within the public right of way is to be minimized. Revise the site plan so that:

The public sewer is extended in the Coventry Place right of way, with the construction of a new public sewer, that will front and serve Lots 3 and 4. It may be necessary to reroute the existing connections that enter into manhole # 2739-02 into the new or existing sewer mains.

Sheet 1: Delete General Note #11.

Sheet 1: Add a General Note that states:

THE REQUIRED OFF-SITE PUBLIC SANITARY SEWER EXTENSION WILL BE DESIGNED AND CONSTRUCTED TO PIMA COUNTY WASTEWATER MANAGEMENT DEPARTMENT STANDARDS.

Sheet 1: In the Legend block, show the existing public and proposed public sewer lines using different line-types, so that they can readily be distinguished from each other. Also, show and describe examples of these different line-types in the legend on Sheet 1.

Sheet 1: Revise Keynotes 2-5 so that it each of these keynotes shows the IMS (manhole) numbers. The IMS numbers are the sewer element identification numbers that can be found on the PCWMD Maps and Records (5th floor) basemaps or on PCWMD and PCDOT MapGuide internet websites.

This office will require a revised set of bluelines, and a response letter, addressing these comments. Additional comments may be made during the review of these documents.

Pima County Code Title 13.20.030.A.2 requires that a wastewater review fee be paid for each submittal of the tentative or preliminary plat. The fee for the first submittal is $166 plus $50 per sheet. For the second submittal, the review fee is $50 per sheet. For all subsequent submittals, the review fee is $39 per sheet.

The next submittal of this project will be the second (2nd) submittal. A check for the review fee of this submittal in the amount of $50.00 (made out to PIMA COUNTY TREASURER) must accompany the revised set of bluelines and response letter.

If the number of sheets changes, please adjust the review fee accordingly.


If you have any questions regarding the above mentioned comments, please contact me at the telephone number shown under my signature on the first page of this letter

CC: Project File
01/22/2007 PGEHLEN1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Passed
01/26/2007 HEATHER THRALL ZONING REVIEW Denied CDRC TRANSMITTAL

TO: Development Services Department Plans Coordination Office

FROM: Heather Thrall
Senior Planner

PROJECT: S06-262
Casas De Los Angeles - residential subdivision
Tentative Plat, 1st review

TRANSMITTAL DATE: January 24, 2007

DUE DATE: January 18, 2007

COMMENTS:

1. Section 4.1.7.1, LUC, permits a maximum of one year from the date of application to obtain approval of a tentative plat. If, at the end of that time, the tentative plat has not been approved, it must be revised to be in compliance with all regulations in effect at that time, and must be resubmitted for a full CDRC review. The one-year expiration date for this tentative plat is December 18, 2007.

2. Per DS 2-03.2.1.C, please enlarge the type in the location map (or provide keynotes).

3. Per DS 2-03.2.1.D, please call out Teton and Coventry Streets on the location map, and city limits boundary at Los Reales. In addition, please check the scale of the location map, and the proximity of the industrial park across the freeway. Add the Santa Cruz River on the map as well.

4. Per DS 2-03.2.2.B.1, please add the subdivision case number S06-262 near title block.

5. Per DS 2-03.2.3.H, I see the existing house is to remain. Please provide footprint dimensions and square footage, with building setbacks proposed/existing - and lot coverage calculations.

6. Indicated in title block that common area A is detention basin.

7. Per DS 2-02.2.4.E, please declare if the project will be phased and if so, please provide a development calculation for each phase.

8. Per DS 2-02.2.4.G, RE: ACCESS:
A) with 8 lots, on street guest parking spaces must be provided. - how is this going to be accomplished? neither street can support this requirement
B) show the driveway locations.
C) the streets do not meet the cross sections outlined in DS 3-01 (see Engineering).
D) Access is a problem for nearly all lots - given the drainage way and the proposed extension of the cul de sac- consult traffic engineering and engineering immediately.

9. Per DS 2-02.2.4.J, please ensure all easements are shown on the plan, with applicable recording data.

10. In general notes, revise note and list this site is subject to: LUC. 3.5.7.1. E.F.G & H.

11. Provide CCR's for maintenance of common area.

12. Please provide a note on the plat that states "individual site plan review is required for the issuance of building permits".

13. Please note, further review comments may be forthcoming, depending upon responses provided. Should you have questions on this review, contact me via email at Heather.Thrall@tucsonaz.gov or at 791-5608x1156.

If you have any questions about this transmittal, please call (520) 791-5608.


C:\planning\cdrc\tentativeplat\S06-262 casas de los angeles tp.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised tentative plat, CC&R's and additional requested documents.
02/26/2007 ELIZABETH EBERBACH ENGINEERING REVIEW Denied TO: Patricia Gehlen; CDRC Manager
SUBJECT: Casas De Los Angeles 1st Submittal Tentative Plat Engineering Review
LOCATION: T15S R13E Section 14, Ward 1
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: S06-262

SUMMARY: The Tentative Plat sheets, Drainage Report, and title report paperwork were received by Engineering and does not recommend approval of the Tentative Plat at this time. The Drainage Report was reviewed for Tentative Plat purposes only.

DRAINAGE REPORT COMMENTS:
1) City of Tucson Development Standards (DS) Section No. 10-01.4.3.1: Revise design to show that the basin shape follows design recommendations provided in the Det/Ret manual; varying side slopes and curvilinear shape should be proposed. Specifically, regarding the basin wall design on detail 5 for the basin cross section on sheet 2 of the tentative plat, this retaining wall basin design is not acceptable. Provide natural looking design for the basin per DS Sec 10-01.1.1.2, to show that the proposed design provides a detention/retention facility that is multi-use and visually appealing. The proposed retaining system will not be accepted.
2) DS Sec.10-01.4.3: Multi-purpose basins must be provided. Human activity zones within the basins need 8:1(H:V) side slopes at various locations of pedestrian access for emergency exits, and shall not conflict with inlets to the basins. Clarify / label 8:1(H:V) or shallower grades for some of the side slopes in all drainage basin areas. Also, depict access for maintenance on planview.
3) DS Sec.10-02.2.3.1.6.B: Clarify detention volume for project, providing discussion of calculated detention required and provided. Revise basin design to assure critical basin management reduction is achieved for the 10- and 100-year storm events.
4) DS Sec.10-01.2.2: Soil type "D" is indicated for this site, per TDOT map guide and as stated in the submitted drainage report. Unless geotechnical report shows that percolation is available the project may want to consider proposal to waive retention per section 2.2 of the Det/Ret Manual. If there are subsurface conditions that constrain the project from providing retention, substantiate in a geotechnical report and the City will consider waiving the retention requirement.
5) DS Sec.10-01.III.3.5.1.3.a, 10-02.14.2.6, DS Sec.2-03.2.4.M: Provide a geotechnical report that provides geotechnical recommendations for maximum slope grades, minimum distance from building to side yard swales, infiltration test results for basins, hydro-collapsing soils statement, or test results, and basin setbacks, soil conditions at the site, and other geotechnical considerations.
6) DS Sec.10-01.III.3.5.1.3.a: Discuss results of infiltration testing in drainage report to demonstrate how the drain time for the retained stormwater for the proposed basin meets Water Harvesting and Detention / Retention criteria, including maximum disposal time.
7) DS Sec.10-02.1.5.1: Weir is located at the south side of proposed basin. This location does not match existing flow pattern. Existing drainage patterns should be maintained as closely as possible under developed conditions. Address basin design comments above and assure there is no adverse impact to offsite parcels.
8) DS Sec.10-02.2.3.1.6.A.4.a: Describe in the drainage report and on exhibit(s):
a) Provide bleed pipe inverts and location.
b) Proposed permanent erosion control at basin exit.
c) Provide separate discussion in report that discusses impact from backwater conditions or FEMA floodplain to the southwest of project.
9) DS Sec.2-03.2.3.D: Regarding detail 2/2, clarify existing versus proposed drainage conditions along Teton Street. Offsite improvements such as basins or other proposed drainage improvements that are to be maintained by the owner shall be with in property limits; TDOT rarely approves such improvements in the right-of-way.
10) DS Sec.10-02.2.3.1.3.A.2: Curb and sidewalk will be required on both sides of the project. Provide calculations and depict scuppers for outlet flows from drainageways along Teton.
TENTATIVE PLAT COMMENTS:
11) DS Sec.2-03.2.2.A: The plat sheet 1 indicates owner as Kovrig Builders and the title report indicates Sam Dillard. There are 4 owners indicated on mapguide for the project. This will need to be clarified for permit authorization purposes as well as for final plat ownership and assurances issues. Provide authorization documents for proposed improvements to parcel owners not listed in the Title Report.
12) DS Sec.2-03.2.2.B.1: Provide subdivision case number "S06-262" at lower right hand corner next to title block.
13) DS Sec.2-03.2.1.D.2: On location map, label Santa Cruz river.
14) DS Sec.2-03.2.4.L.3: Provide revised basin information on Tentative Plat.
15) DS Sec.2-03.2.4.L.4: Depict and clarify whether any walls will be proposed and if so where any wall openings will be located.
16) DS Sec.2-03.2.4.F: Provide new 5-foot wide sidewalk is sections 1/ 2 and 2/2.
17) DS Sec.2-03.2.4.L.4: Provide a typical lot grading details. Address the following:
a) Clarify how distances for minimum setbacks provide appropriate area for drainage swales, mechanical equipment, A/C units, slope setbacks for screen walls, slope run-outs, and general access.
b) Assure that the details comply with any recommendations of soils report.
c) Provide in detail the general / typical high point elevation or grade break locations as it relates to the finished pad elevation, as well as minimum flow grades around building pads.
18) DS Sec.2-03.2.4.L.1: On the Tentative Plat plan view, show detention/retention 100-year ponding limits with water surface elevation in basin.
19) DS Sec.10-01.4.3: Show or add note regarding basin security barriers for proposed basin along all sides of basin.
20) DS Sec.2-03.2.4.K: Assure Tentative Plat conforms to geotechnical report, including basin setback from structures.
21) DS Sec.2-03.2.4.M: Show any setback dimensions from basin ponding limits to proposed buildings on plan view.
22) DS Sec.2-03.2.3.A: Provide local benchmark with datum location indicated on plan view.
23) DS Sec.2-03.2.3.B: Clarify boundary data as recorded, calculated, or measured that matches the description provided in title report(s).
24) DS Sec.2-03.2.3.C: All existing easements will be drawn on the plat, and recordation information, locations, widths, and purposes shall be included. If the easement is not in use and proposed for abandonment, so indicate. Blanket easements should be listed in the notes, together with recordation data and their proposed status.
25) DS Sec.11-01: A Grading Plan and Permit will be required.
LANDSCAPE PLAN COMMENTS:
26) DS Sec.3-01.5.1.A.2: Revise Landscape Plan to reflect revised basin design.
27) Assure that no proposed plants are blocking or placed on access ramps for basin.

The next submittal should address all the above items. Submit the revised Tentative Plat sheets, the revised Drainage Report, soils report, and a response letter. You may call to schedule an appointment to go over these comments, or if you have any questions, please call me at 791-5550 extension 2204.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services
02/28/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied COMMUNITY DESIGN REVIEW COMMITTEE
DEVELOPMENT SERVICES

February 28, 2007

Steve Gregor
Gregor Engineering, Inc.
5232 East Pima Street, Suite A
Tucson, Arizona 85712

Subject: S06-262 Casas De Los AngelesTentative Plat

Dear Steve:

Your submittal of December 19, 2006 for the above project has been reviewed by the Community Design Review Committee and the comments reflect the outstanding requirements which need to be addressed before approval is granted. Please review the comments carefully. Once you have addressed all of the comments, please submit the following revised documents and a DETAILED cover letter explaining how each outstanding requirement has been addressed:

ALL BLACKLINES MUST BE FOLDED

8 Copies Revised Tentative Plat (Real Estate, Traffic, Fire, Landscape, Wastewater, Zoning, Engineering, DSD)

4 Copies Revised Landscape Plan (Landscape, Zoning, Engineering, DSD)

2 Copies Revised NPPO Plan (Landscape, DSD)

2 Copies Title Report (Real Estate, DSD)

2 Copies Drainage Report (Engineering, DSD)

2 Copies Soils Report (Engineering, DSD)

Should you have any questions, please call me at 791-5608 extension 1179.

Sincerely,


Patricia Gehlen
CDRC Manager

All comments for this case are available on our website at http://www.ci.tucson.az.us/dsd/
Via fax: 319-1181
02/28/2007 PATRICIA GEHLEN ZONING-DECISION LETTER REVIEW Denied April 29, 2008


Steve Gregor
Gregor Engineering, Inc.
5232 East Pima Street, Suite A
Tucson, AZ 85712

SUBJECT: CLOSURE OF CDRC FILES


Tentative and Final Plat

Per Section 4.1.7.1, Maximum Review Period
The subdivider has one (1) year from the date of tentative plat submittal to obtain approval of the plans. Failure to obtain approval means the review period has expired

Case # Case Name DSD Transmittal Date

S06-262 Casas De Los Angeles December 19, 2006



Please note that this case has been closed and that, in order to continue review of the project, new development plan/tentative plat applications are required which comply with regulations in effect at the time of the new submittals.


Thank you for your assistance.

Sincerely,



Patricia Y. Gehlen
CDRC Manager


xc: CDRC file S06-262
12/18/2006 FERNE RODRIGUEZ START PLANS SUBMITTED Completed
12/18/2006 FERNE RODRIGUEZ COT NON-DSD REAL ESTATE Denied S06-262 Casas de Los Angeles: Tentative Plat Review - No title report provided for parcel 138-22-013Q. Request confirmation of ownership of parcels 138-22-013T & 138-22-013Q.
12/20/2006 JOSE ORTIZ COT NON-DSD TRAFFIC Denied December 20, 2006
ACTIVITY NUMBER: S06-262
PROJECT NAME: Casas De Los Angeles
PROJECT ADDRESS: 941 W Coventry Place
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the Tentative Plat; therefore a revised Tentative Plat is required for re-submittal.

The following items must be revised or added to the plat.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. Local streets must be designed with parking on both sides of the street per (DS 3-01.2.4.D). Ensure that the stub out roadway will be wide enough to handle required parking on both sides. If unable to provide standard roadway widths then a DSMR maybe required through Development Services to allow for the proposed configuration.

3. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.

4. Tucson City Code Chapter 25 Section 38 requires a minimum driveway separation of 12'. Ensure that this Code requirement is being met between the existing lot 13 and the stub out roadway.


If you have any questions, I can be reached at 791-4259 x76730 or Jose.Ortiz@tucsonaz.gov
12/22/2006 MARTIN BROWN COT NON-DSD REAL ESTATE Approved S06-262 Casas de Los Angeles: Tentative Plat Review - No title report provided for parcel 138-22-013Q. Request confirmation of ownership of parcels 138-22-013T & 138-22-013Q.
12/27/2006 FRODRIG2 OTHER AGENCIES PIMA ASSN OF GOVTS Approved Transportation Information for
Rezoning, Subdivision, and
Development Requests
Delivered to:
Date Delivered:
Development Services - City of Tucson
12/22/2006
Case Number Project Name
Average number of daily trips
(ADT) forecasted as a result of the
proposed development
This information is provided for jurisdictional
planning departments to assess the impact of
the proposed residential or commercial
development on surrounding traffic patterns
and roads. If the forecasted daily traffic
exceeds 500 average daily trips, a more
detailed analysis is also provided.
S06-262 77 Casas de Los Angeles
Pima Association of Governments
Sandra C. Holland, Data Services
177 N. Church Ave., Suite 405, Tucson, Arizona
85701-1127
(520) 792-1093 FAX (520) 620-6981
12/27/2006 JCLARK3 ENV SVCS REVIEW Approved * No known landfill within 1000 feet of this development.
* Lots 4 & 8 will havwe to place there refuse infront of lots3 & 7 for service.
12/27/2006 JIM EGAN COT NON-DSD FIRE Denied Please add the following notes to the plan.

1. Additional fire hydrants shall be provided by the developer as required by the fire code in accordance with C.O.T. Standards.

2. An approved water supply capable of supplying the projected fire flow for fire protection shall be provided and extended to serve directly any and all subdivided properties.

3. "NO PARKING FIRE LANE" signs shall be provided as needed to provide 20' clear unobstructed width along all fire apparatus access roadways in accordance with the fire code.

4. On street parking shall be prohibited on both sides and signs shall be installed so indicating.
12/29/2006 ROGER HOWLETT COT NON-DSD COMMUNITY PLANNING Approved DEPARTMENT OF URBAN PLANNING & DESIGN COMMENTS

Regarding

SUBJECT: Community Design Review Committee Application

CASE NUMBER: CASE NAME: DATE SENT

S06-262 Casas De Los Angles 12/29/06

(XXXX) Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Revised Plan/Plat
( ) Board of Adjustment
( ) Other

CROSS REFERENCE:

NEIGHBORHOOD PLAN: 12th Avenue/Valencia

GATEWAY/SCENIC ROUTE:

COMMENTS DUE BY: 01/18/07

SUBJECT DEVELOPMENT PLAN/PLAT HAS BEEN REVIEWED BY COMMUNITY PLANNING AND PRESERVATION, AND STAFF SUBMITS THE FOLLOWING COMMENTS:

( ) No Annexation or Rezoning Conditions, Not an RCP - No Comment
(XXXX) Proposal Complies with Annexation or Rezoning Conditions
( ) RCP Proposal Complies with Plan Policies
( ) See Additional Comments Attached
( ) No Additional Comments - Complies With Planning Comments Submitted on:
( ) Resubmittal Required:
( ) Tentative Plat
( ) Development Plan
( ) Landscape Plan
( ) Other

REVIEWER: D.R. Corral 791-4505 DATE: 12/29/06